HomeMy WebLinkAbout13922-Property Maintenance (06/06/2008) INSPECTION SERVICES DIVISION ROOM 205 CITY OF OSHKOSH
DEPARTMENT OF COMMUNITY DEVELOPMENT 215 CHURCH AVE
OSHKOSH CORRECTION NOTICE PO Box 1130
ON THE WATER OSHKOSH WI 54903 -1130
Issue Date 6/6/2008 4/6/2011 Compliance Date 7/6/2008 Compliance No
Address 1917 MICHIGAN ST
Name Address City State Zip Code
Sent to 0 Owner RICHARD B /DAVID B RASEY 1917 MICHIGAN ST OSHKOSH WI 54902 -6836
[ j Required for Occupancy Occupancy
Introduction As of 4/6/11 the following violations have not been corrected. Please correct the violations immediately and contact Adam
Krause at 236 -5274.
Item # 1 Code NEC 250.119 Compliance No Compliance Date 07/06/2008
Description Individually covered or insulated equipment grounding conductors shall have a continuous outer finish that is either green or
06/06/2008 green with one or more yellow stripes except as permitted in this section. Grounding conductor is currently red.
Last
Updated
L.
Item # 2 Code NEC 200.6(B) Compliance No Compliance Date 07/06/2008
Description n insulated grounded conductor larger than 6 AWG shall be identified by one of the following means:(1)By a continuous white
06/06/2008 r gray outer finish. (2)By three continuous white stripes along its entire length on other than green insulation. (3)Attime of
nstallation, by a distinctive white or gray marking at its terminations. This marking shall encircle the conductor or insulation,
Last
Updated
Item # 3 Code NEC 250.142(B) Compliance No Compliance Date 07/06/2008
Description grounded circuit conductor shall not be used for grounding non - current- carrying metal parts of equipment on the load side of
06/06/2008 he service disconnecting means or on the Toad side of a separately derived system disconnecting means or the
vercurrentdevices for a separately derived system not having a main disconnecting means.
Last
Updated
Item # 4 Code WI Comm 16.09 Compliance No Compliance Date 07/06/2008
Description � electrical installations shall be cleaned and inspected at intervals as experience has shown to be necessary. Any equipment
06/06/2008 Or electrical installation known to be defective so as to endanger life or property shall be promptly repaired, permanently
isconnected, or isolated until repairs can be made. Construction, repairs, additions and changes to electrical equipment and
Last onductors shall be made by qualified persons only. Breaker panel bus shows oxidation and paint.
Updated
Item # 5 Code WI Comm 16.18 Compliance Yes Compliance Date 07/06/2008
Description Listed or labeled equipment shall be installed or used, or both, in accordance with any instructions included in the listing or
08/06/2008 labeling, provided the instructions, listing or labeling do not conflict with this chapter. PVC conduit to be glued /installed
ccording to the manufacturer.
Last
Updated
13922 Page 1 of 3
INSPECTION SERVICES DIVISION ROOM 205 CITY OF OSHKOSH
DEPARTMENT OF COMMUNITY DEVELOPMENT 215 CHURCH AVE
OSHKOSH CORRECTION NOTICE PO Box 1130
ON THE WATER OSHKOSH WI 54903 -1130
Issue Date 6/6/2008 4/6/2011 Compliance Date 7/6/2008 Compliance No
Address 1917 MICHIGAN ST
Name Address City State Zip Code
Sent to [ ✓! Owner RICHARD B /DAVID B RASEY 1917 MICHIGAN ST OSHKOSH WI 54902 -6836
rl Required for Occupancy Occupancy
Introduction As of 4/6/11 the following violations have not been corrected. Please correct the violations immediately and contact Adam
Krause at 236 -5274.
Item # 6 Code NEC 352.30 (A,B) Compliance Yes Compliance Date 07/06/2008
Description Rigid Nonmetallic Conduit shall be secured within 3' of every box, fitting, and conduit termination, as well as every 5' along the
08/06/2008 developed length.
Last
Updated
13922 Page 2 of 3
INSPECTION SERVICES DIVISION ROOM 205 CITY OF OSHKOSH
(. DEPARTMENT OF COMMUNITY DEVELOPMENT 215 CHURCH AVE
OSHKOSH CORRECTION NOTICE PO Box 1130
ON THE WATER OSHKOSH WI 54903 -1130
Issue Date 6/6/2008 4/6/2011 Compliance Date 7/6/2008 Compliance No
Address 1917 MICHIGAN ST
Name Address City State Zip Code
Sent to L7 Owner RICHARD B /DAVID B RASEY 1917 MICHIGAN ST OSHKOSH WI 54902 -6836
Required for Occupancy Occupancy
Introduction As of 4/6/11 the following violations have not been corrected. Please correct the violations immediately and contact Adam
Krause at 236 -5274.
•
Item # 7 Code NEC 314.17(A) Compliance Yes Compliance Date 07/06/2008
Description Openings through which conductors enter shall be effectively closed.
08/06/2008
Last
Updated
_ l
Summary Please correct the above violations immediately and request a re- inspection. If the violations are not corrected by 5/6/11 additional
enforcement action may be pursued in an effort to gain compliance with this notice.
Violations must be corrected and approved within 30 days unless otherwise noted. Call for reinspections prior to concealment
and /or occupancy. Upon completing the corrections, the owner /contractor /agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 7/6/2008
Office hours for obtaining permits are Mon • ay through Friday 7:30 -8:30 a.m. and 12:30 -1:30 p.m. or by appointment. To schedule
inspections please ca e sp/ctio • _ • est line at 236 -5128 noting the address, permit number (when applicable}, and the
nature of what nee tfa ins • ed.
Signature Date V- 6
Inspected by: Adam Krause 236 -5274 akrause @ci.oshkosh.wi.us
I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes.
Print Name Company
Signature Date
Also Sent to: r_ Bldg -
Elec -
HVAC _
Plb
g -
[__j Designer
i Other -
[_% Inspector
13922 Page 3 of 3