HomeMy WebLinkAboutLetter (boiler) - 4/20/2001City of Oshkosh
Division of Inspection Services
215 Church Avenue
PO Box 1130
OlHKOIH Oshkosh WI 54902-1130
Office 920-236-5050
ON THE WATER Fax 920-236-5084
Hauke Real Estate Investments
PO Box 3174
Oshkosh WI 54903-3174
Apri120, 2001
Re: Boiler at 840 John St
Dear Mr. Hauke and Mr. Leich;
After reviewing your letter and the history behind this issue I have found there is a significant safety
issue with this boiler. I am not aware of any boiler manufacturer that would condone or design a boiler
that would allow flames to roll out of the combustion chamber. Additionally, our inspection revealed a
concern with an accumulation of carbon monoxide (CO.)
We have two letters from Gartman Mechanical Services, the first stating the roll out is normal operation
for this boiler and the second letter addressing the CO accumulation. Neither of these letters provides
information from the manufacturer of the boiler stating the flame roll out is acceptable or part of the
design of this boiler. To date we have received no information from the manufacturer stating this is
acceptable.
We have conversed with state building officials regarding the flame roll out and they too find it
unacceptable from an ignition and safety standpoint. At this time I have given our inspector, Brian Noe,
direction to allow you 2 more weeks to resolve this problem. If there is not a resolution in progress by
Monday, May 7, 2001 this office will issue citations. Please keep Mr. Noe (236-5051) informed of the
arrangements and progress you make in complying with the Correction Notice.
If you have additional questions, please call me at 236-5045.
Sincerely,
Allyn off
Directo f spection Services
Hauke Real Estate Investments - PO Box 3174 Oshkosh, WI 54903
Phone: 920-428-7249 for Chris or 920-915-5363 for Kyle
April 5, 2001
Dear Mr. Dannhoff:
I'm writing you this letter in regards to a series of disturbing actions taken by the
housing inspectors you apparently over see.
Over the summer of 2000 my partner and I bought a property located at 840 John
St. Over the summer we invested thousands of dollars in correcting all code violations
that were placed on the home prior to us purchasing it.
One of the code issues was that the boiler in the home had some carbon monoxide
problems due to prior tenants vandalizing the property and tearing down some of the
venting in the basement. That issue was taken care of and we had Tenth Street Station
come over on August 30t~' 2000 to do test for carbon monoxide, and everything checked
out fine.
When the inspectors came back through in early September, all code violations
were fixed, except he felt there was still a problem with the boiler. When the boiler fires
up, the combustion chamber fills with gas, then ignites causing a puff of flames to roll up
to and spit out no more than a'/4 inch from the fire shield. This he thought was a major
problem even though the boiler has been there for the last 20-30 years with no problems.
Therefore we sent out Gartman Mechanical which he recommended us to call and
have them come give us a report on it. We did so again (spending even more money) and
everything checked out fine per their opinion.
After the letter from Gartman was sent to the inspector, he still did not believe this
was sufficient. He then told Gartman that we had carbon monoxide problems with that
boiler, so Gartman wrote us a letter back stating that now the boiler needs to be replaced!
However, remember that we had a carbon monoxide test done, and it was well below
acceptable levels.
After ignoring this letter, because of the sudden reverse opinion of Gartman, the
inspector then sent us a letter stating that he would fine us if we did not replace the boiler.
To me this is unacceptable. We have valid proof that the boiler is working properly and
that it is a normal function for the boiler to work the way it does.
I am asking you to please rectify the opinion of the inspector that has worked on
this issue. I don't mean to cause problems, I have better things to do with my time than
write letters like this because of other peoples irrational opinions on my properties that I
have done nothing but good things for. I'm not willing or able to invest $2000-$3000 on
a boiler that does not need to be replaced.
Please contact me on your thoughts to this situation. Attached are copies of all
letters and service reports. Thank you for your time.
Chris Leitch -Hauke Real Estate Investments
Kyle Hauke
ACC ~C~"
Tenth Street Station, Inc.
Heating & Cooling
924 Ohio Street
Oshkosh, Wl 54902
Phone: (920) 236-8770
Fax: (920j2~y6-01>0
~V1~'vV.il:IltliSU~~tE~itW~f~~ .Lt~ti~l
rl"IV'OIC~
DATE ~ DUE DATE INVOICE #
_ ~ _. ___-
8/30120011 8/30/2000 ]U649 '
3iL~. ; ~ wORK DOhlt=. ;~,T
Taukc° I:~al Estate ~ 840 Ja'tu~i St.
P.(~. Liox. 3174 Oshkosh, WI `4901
Osl~osh, Wl _54903-3174
P.+). NO. -TERMS PROJECT
i
Due on receipt
QUANTITY DESCRIPTION RATE AMOUNT
'Service Call• Service boiler and test chimney for 49.95 ', 149.SSr
proper draft. Bciiler is operating safely Ott this time. ~.
:Chimney and vent connector are both allowable '
sizes oared on National Fuel Gas C•,~de vent tables ~ '~
for capac.ites ul~:~naso,iry ehimay.~ vvitll single wall
vent coiu7ectv3':>.
1 Service Call: 'T'est boiler for carbon monoxide 49.95 49.95T
upon start-up and during burner cycle.
-Found 2 ppm un start-up / l ppm during cycle.
W~.ll below acceptable levels.
Sales "hax 5.00% 9.99
r'Ic:~sc: l;aii siirz +` you liati•c any yucstio~;s• ~`C~~t~~ ~;~(~~9.79
.~
,~ sc;rvice charge of 1.5~•~ per tnortth will ,accrue on ail p~cst ta7ae. tt.nirtuiis. .'~i! co~l5 i~t ci;ll~i:tion:, including~`~
attorneys f, es shat( be paid by the purr,-l~asr;r. Q
*~i'~)1Z 4'OUR%'ONVEMENI~F;, WL ACt t~;P"1' VIS~~, MAS~I F;i~t=:A~, AND DISCOVER**
6ti
Gartman Mechanical Services
G1ViS INC.
P.O. Box 2264
Oshkosh, WI 54903-2264
', Bill To
Hauke Real Estate Investments
15765 Grande Market Drive
Suite A
~, Appleton, Wl 54915 j
~ I
I I
Invoice
Ii Date I Invoice #~
1 / 16/2001 ! 8899
-~ ---
P.O. No. I Terms
GMS, Inc. WO No.
- I Net 30 7300
--- - -- ~
~ Description ~ Amount ~
Service call January 9th at 840 John Street in Oshkosh to check flame roll out problem ,
'; on AO Smith boiler. Found that upon starting the flames fill the combustion chamber
in normal fashion for this style boiler. Check chimney draft and heat exchanger and
for proper operation. j
Labor ` (~ `
/ 1/
I
i
I
~ ~~
--_--- _ -__ 1 ~'
~ S u btota
Please make check payable to Gartman Mechanical Services, Inc. and ~ Sales Tax ~5.~%~
mail to P.O. Box 2264, Oshkosh, WI 54903-2264. Please return one
copy of the invoice with your payment. All past due accounts will be ~ Total
charged an interest rate of 2% per month. Thank you.
~ Payments/Credits
Balance Due
62.OOT I~I
$62e00
$3.10
$65010
----;
$o.oo
$65.10
GMS, INC.
Gartman Mechanical Services
Heating -Ventilating - Sheetmetal -Air Conditioning
P.O. Box 2264 520 W. Southpark Avenue
Oshkosh, WI 54903
Phone: (920) 231-5530 Fax: (920) 231-0486
January 10, 2001
Hauke Real Estate Investments
5765 Grande Market Drive
Suite A
Appleton, WI 54915
ATTN: Kyle Hauke
RE: 840 John Street in Oshkosh
Mr. Hauke,
On January 9~', we inspected the AO Smith boiler at 840 John Street in Oshkosh for a
flame roll out problem. Found that upon start up, flames fill the combustion chamber in a
normal fashion for this style of a boiler.
A step opening gas valve may solve the large cloud of gas at start up, but isn't
recommended as to liability of manufacturers' design.
If you have any further questions or concerns, please give us a call.
Sincerely,
_lf ~ F e
1 f Y r~~~
Mark Weber, service technician
Gartman Mechanical Services
MW/mjh
GMS, INC.
GARTMAN MECHANICAL SERVICES
HEATING • VENTILATING • AIR CONDITIONING • SHEET METAL • CONTRACTORS
P.O. BOX 2264 S20 WEST SOUTH PARK AVENUE,
OSHKOSH, WISCONSIN 54903
(920) 231-SS30 FAX (920) 231-0486
hchnriry 2, 2001
Hauke Real Estate Investments
5765 Grande Market Dr.
Suite A
Appleton, WI 5491 S
ATTN: Kyle Hauke
RE: 840 John St. in Oshkosh
Mr. Hauke,
On January 10th GMS, Inc. sent you a letter in regards to the A.O. Smith heating boiler at 840
John Street. Since then, we have received a letter from Brian Noe the City of Oshkosh heating
inspector. His letter stated that there are a number of concerns with this property, one of those
concerns was the detection of CO.
In the January 10th letter, GMS stated that the flame operation was normal and that a step
opening valve could be installed to alleviate gas buildup during the startup of the system,
however it was not recommended due to liability purposes. In continuation with that theme,
GMS recommends that this boiler be removed and replaced with a new system to insure the
safety of occupants in the future.
The January 10th letter stated that the flame roll was normal for that type of system, however at
that time we did not detect any CO. Since, CO has been detected it is recommended to replace
the unit. Any situation with CO is unsafe.
Thank you for the opportunity to make recommendations to you on your system. To reiterate
what was stated above, tl~e boiler system at 840 John St. needs to be replaced. GMS, Inc. would
be happy to offer a written quotation to you on the replacement costs of a new system and
information. regarding the planned new system.
Copy of this letter turned into the city of Oshkosh for record purposes.
Sincerely,
>~~ -
~~
Dale Weitz
OlHKOIH
ON THE WATER
March 7, 2001
City of Oshkosh
Division of Inspection Services
215 Church Avenue
PO Box 1130
Oshkosh WI 54903-1130
Hauke Real Estate Investments
5765 Grand Market Dr
Suite A
Appleton, WI 54915
ATTN: Kyle Hauke
RE: 840 John St.
As you are aware, we have been working toward a resolution for addressing the flame roll out on the
boiler located at this address. It has been our position, and the fire departments position that there is no
way that a boiler could be considered safe if it has a flame roll out problem. While you did provide us a
copy of a letter from GMS, Inc that stated "flames fill the combustion chamber in normal fashion for this
style of boiler" it did not state this was a safe operating boiler. In fact when this letter was questioned,
GMS would not state that the boiler was operating in a safe manner, and in fact sent a letter
recommending replacement.
As in the past, it is our position that the flame roll out condition is an unsafe situation and is required to
be corrected, either by repair or replacement. We have been very patient in allowing you time to correct
this matter, and must insist that this betaken care of in the next 30 days in order to avoid citations being
issued. Please let me know when I can expect compliance with this matter.
,,~,,.,
If you have any further questions, please give me a ca11236-5051.
Respect
</
Brian Noe
Building Systems Inspector.
PC: Allyn Dannhoff - Director of Inspection
William Griswold -Fire Inspector