City of Oshkosh
Division of Inspection Services
215 Church Avenue
PO Box 1130
Oshkosh WI 54903-1130
www.cLoshkosh.wLus
ON THE WATER
November 22, 2006
Keith Paul
Gartman Mechanical Services
520 W South Park Ave
Oshkosh, WI 54903
Ron Detjen
Landmark LTD III
PO BOX 2366
Oshkosh WI 54903
Site: Plan Number: WI-I09-1106-H
U Bake
374 S KoellerSt.
Oshkosh WI 54903
For:
Description: Tenant space alterations
Object Type: HV AC only
Class of Construction: llB -1653 Sq Ft.; Srinklered
Occupancy: M: Mercantile I Retail
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defmed in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item{s) I Conditions:
. IBC 1101.2/ANSI A117.1-308.2 & 3 - Mechanical system controls shall be located a maximum of 48"
above the finished floor if the floor space allows a forward approach by a wheel chair or if the clear space
allows a parallel approach. Caution on location ofT-Stat above counter space.
. IMC 403.3.4 Balancing Ventilation systems shall be balanced by an approved method. Such balancing
shall verify that the ventilation system is capable of supplying the airflow rates required by Section 403.
. IMC 606.2.1 Smoke detectors shall be installed in return air systems with a design capacity greater than
2000 cfm... .. .Per the plans submitted the total cfm for the system is 1995, which does not required the
installation of a smoke duct detector, however should the balancing of the system to meet [MC 403.3.3
cause this to increase detectors may be required.
. Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documepts that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Comm 61.31(1).
\\OSllKOSfli\:JISFS'I'SFRS'"br:ann'2006 Cornm Plan R",'iew"\VI.II)'J"! {()6 374 $ Ko~lIer $1 HVAC On1\'.doc
Page 1 of2
. Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to connnencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 10 1.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
RespW
~~
Building Systems Consultant
(920) 236-5051 Monday- Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.
bnoe@ci.oshkosh.wi.us
cc: Property file
Fee Required $
Fee Received $
Balance Due $
230.00