Heating and ventilating plans have been reviewed by this office for compliance. All items that are
required to be changed by this letter, must be corrected before commencing that part of the work. This
approval is not a Heating Permit. Necessary city permits must be secured before commencing work.
You are hereby advised that the owner, as defined in Chapter 101.01 (I) ofthe Wisconsin State Statutes, is
responsible for all code requirements not specifically cited herein. Code requirements are set forth in
Chapters 50 through 69 ofthe rules ofthe Department of Commerce.
The building will be inspected during construction and a final inspection will be made after completion to
insure compliance with city and state codes.
The architect, professional engineer, builder or owner shall keep at the building, as evidence of approval,
one set of plans bearing the stamp of approval.
COMM 64.05 Restroom exhaust fans shall be installed to run continuously during occupied hours to
maintain the required negative pressure relative to adjacent areas.
COMM 64.05 Total exhaust shall equal 7.5 CFM per occupant. The system shall be designed based on an
occupant load of 50 sfper person (which equates to approximately 36 occupants.) Based on this occupant
load, total exhaust (with equivalent make up air) shall be 275 CFM. Provide correspondence detailing
how this will be accomplished.