August 30, 2005
Richard Fischer
Fisher & Associates,.LLC
642 Thlosen Drive
Kimberly WI 54136
Ron Detjen
Landmark L TO III
PO Box 2366
Oshkosh WI 54903
Site: Plan Nnmber: P9-63-0805
Landmark Plaza
300 S Koeller Road Suite "K" Kirby Vacuum Sales
Oshkosh WI 54902
For:
Description: Tenant space alterations
Object Type: Building only
Class of Construction: DB - 2480 Sq Ft.; Sprinklered
Occupancy: B: Business Office
Max Number of Occupants 32
The submittal described above has been reviewed for confonnance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) I Conditions:
. mc 505.2 Area limitation. The aggregate area of a mezzanine or mezzanines within a room shall not
exceed one-third of the area of that room or space in which they are located. The enclosed portions of
. rooms shall not be included in a determination of the size of the room in which the mezzanine is located.
In determining the allowable mezzanine area, the area of the mezzanine shall not be included in the area of
the room. Per discussion with Rick Fischer 8/30/05 the area indicated on plans as a mezzanine will be
considered as a 2"d story. In discussion with Henry Kosar~cki with Department of Commerce, the area
limitations are not required to be considered, and no fire barrier is requires to separate this space, as .
the volume of the building is not being increased, and was approved under earlier versions of code with
an unlimited area.
. mc 711.3 Any penetrations of fire rated assemblies are required to be protected with a listed frrestopping
system that matches the rating of the wall assembly being penetrated. Copies of the firestopping systems
are required to be provided at the time of inspection.
. IBC 901.2 Fire protection systems shall be installed, repaired, operated and maintained in accordance with
this code and the international fire code. (Construction of new walls may require the addition and or
relocation of sprinkler heads to maintain required coverage, and not obstruct spray patterns offire
sprinklers)
\\OSHKOSHMISFS\VSERS\briann'.2005 Comm Plan Review,\P9-63-0S05 300 S Koelkr St Bldg Only.doc
Page 1 of3
..
. IFC 901.4 Fire protection systems shall be maintained in accordance with the original installation
standards for that system. Required fire protection systems shall be extended, altered, or augmented as
necessary to maintain and continue protection whenever the building is altered, remodeled or added to.
Alterations to fire protection systems shall be done in accordance with applicable standards. Submit plans
for fire sprinkler modifications.
. IBC 906.1/ IFC 906.3 The maximum travel distance allowed to a frre extinguisher is 75 feet.
. IBC 1003.2.10 Exit signs are required to be installed per this section
. IBC 1003.2.11 Means of egress illumination is required to be installed per this section. All paths of egress
are required to have adequate emergency lighting to meet the performance requirements of IBC
1003.2.11.3. Existing means of egress emergency lighting is permitted to be maintained in compliance
with the code in effect at the time of construction. Any altered path of egress, or new path of egress,
and any new emergency lighting being installed is required to comply with current code requirements.
. IBC 1005.3.2 Exceptions:1. In other than Groups H and I occupancies, a stairway serving an occupant
load of less than 10 not more than one story above the level of exit discharge is not required to be enclosed.
Per discussion with Rick Fischer on 8/30/05, the occupant load will be less than 10, so rated stair
enclosure is not required.
. mc 1209.1 Provide toilet room floors with smooth, hard, nonabsorbent surface extending minimum 6
inches up onto walls.
. mc 2902..1/ Table 2902 Drinking water is required to be provided, since no drinking fountain is shown
on plans a bottled water cooler is required to be provided.
. Comm 61.30(3) This review does not include lighting. Comm 63.0001 Prior to installation, lighting
plans and calculations shall be prepared in compliance with the code. The plans shall be available upon
request.
. Comm 61.30(3) / IMC 507.2 This plan review does not include heating, ventilation, or air
conditioning. HV AC plans are required to be submitted and approved prior to installation ofHV AC
equipment. Be aware that IBC 1004.3.2.4 contains additional restriction for air movement in corridors
. Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Comm 61.31(1).
SUBMIT:
. Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
\'OSJIKOSHM1SFS\USERS\briann\.2005 Comn< Plan Review,\P9..63-0805 300 S Koeller St Blug Only.doc
Page 20f3
..
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning'this correspondence may be made to me at the number listed below or the address on this letterhead.
P..~
~~
Building Systems Inspector.