HomeMy WebLinkAbout0097016-Electric (Annual Permit)
e
OSHKOSH
ON THE WATER
Job Address 3300 MEDALIST DR
CITY OF OSHKOSH
No 97016
ELECTRIC PERMIT. APPLICATION AND RECORD
Owner
SMET INVESTMENTS LLC
Create Date 09/03/2002
Service
b New
o Temp
Category 656 - ANNUAL PERMIT
Type 0 Overhead
Plan
Contractor
G E POWER SYSTEMS / A C COMPRES
o Change
o Underground
o
Switches
Receptacles
o
o
Volts
Circuits
o
o
Fixtures
Amps
Appliances
Use/Nature of ~nnual Permit valid through 6/30/2003
Work
Fees: Valuation
$100,000.01
Plan Approval
$0.00
Permit Fee Paid
$500.00
Date 09/03/2002
Issued By:
o Permit Voided I
In the performance of this work I agree to perform all work pursuant to rules governing the described construction.
Signature
Date
Address
3300 MEDALIST DR
Agent/Owner
Oshkosh
WI 54902 - 0
Telephone Number 920-237-6007
"- ~ " ~ Electric Permit Work Card
Job Address 3300 MEDALIST DR Permit Number 97016 Create Date 09/03/2002
Owner SMET INVESTMENTS LLC Contractor G E POWER SYSTEMS / A C COM PRES
Category 656 - ANNUAL PERMIT
}rvice b New o Change 0 Temp . N/A I Type o Overhead o Underground . N/A I
Volts Circuits 0 Fixtures 0
Amps 0 Switches 0 Receptacles 0
Fee $500.00 0 Value $100,000.01
Appliances
Use/Nature ~rmual Permit valid through 6/30/2003
of Work
Inspections:
Date ~\/~(Otype p~
Inspector
\L, \S .
v
~e.. ~...bb<..c..""e.~ N..c:>Je'e..~
(\
Date/Time requested: ~b "3 : 10 ~ 07 Notice Type:
Access:
Phone Number:
Ready Date/Time: -Y ;).. '4{ b3: A M Requested by:
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
GO'6_-r-"'~b --
-----------------------------------------------------------------------------------.
r
I""
To: Kenin Benner, Brian Noe, Barry Weinbrenner, Tony Neely, Phill Plowman, Jerry
Geweda, Douglas Thurber
On January 22,2003 the city of Oshkosh performed an inspection at GE Power systems
located in Oshkosh. Present was Kevin Benner (Electrical Inspector City of Oshkosh ),
Brian Noe (Building Inspector City of Oshkosh) and Douglas Thurber (Electrical
Superintendent GE Power Systems)
The following findings were noted:
1. Remove power from electric heater in Esther's office and tag DO NOT
ENERGIZE.
2. Need outlet cover in JeffWudi's office.
3. Remove all old wires from new front office project.
4. Support low voltage cable in front office every 5 feet with approved hangers.
5. Old existing conduit in front office not supported, redo
6. Cover open boxes in front office.
7. Leave ceiling open till final inspection is complete.
8. Need backflow preventer on hose spicket by pumping station.
9. Need to add two exit lights to wood shop.
10. Need to add ground bushing on transformer for CMN. (Voss?)
11. Need to install emergency lights between all racks to maintain one-foot candle.
(State Code)
12. Maintain three-foot clearance for electrical panel in wood shop. Paint yellow line
13. Keep exit to maintenance shop clear.
14. Correct double grounds on lug in weld outlet in maintenance
15. Dust collector being installed in wood shop? If not then it may be reclassified as
hazardous location and require more sprinklers and electrical upgrade. Suggest
daily cleaning until system is installed.
16. Locker room emergency lights. Need to verify that lights are connected to
existing light circuit or separate circuit. (277v lights 120v emergency lights? )
17. New 300HP Drive is not listed. Needs independent listing before going into
servIce.
18. Replace J Box for new crane with 6X8 J Box
19. Large Stress Oven Equipment number 86 needs main switch replaced.
20. Buss buckets C177 and C176 need to be relocated to obtain proper clearances.
21. Move panels numbers 28,32, and 36. New wall blocks working clearances