Loading...
HomeMy WebLinkAbout2003-Letter-Code Violations/Requirements y ~ OJHKOJH ON THE WATER City of Oshkosh Division ofInspection Services 2]5 Church Avenue PO Box J 130 Oshkosh WI 54902-] 130 Office 920-236-5050 Fax 920-236-5084 HOBBYTOWN 2075 S KOELLER ST OSHKOSH WI 54902 October 23,2003 Re: 807 Oregon St. Dear Mr. Mazza & Mr. Magritz; The inspection conducted on Tuesday, October 21,2003 revealed several code issues that must be addressed. Additionally it became evident there is some confusion over what improvements and conditions will apply for the use of various areas for RC Vehicle Racing. I hope to clarify code requirements with this letter. Enclosed with this letter is a copy of the August 5, 2003 correspondence I sent to you regarding the conditions of use. Per this letter you will find that the RC Vehicle Racing will be allowed in the various areas as long as the total combined capacity for the 3 rooms in which racing will be conducted does not exceed 50 persons. After the inspection conducted this past Tuesday, I leamedthat the second floor, .... east room only has one exit. As a result, this area will be limited to a maximum of25 occupants, asthis was the code limitation under the previous building code. Since each of the remaining two rooms used for racing has access to two exits, those rooms may be occupied by up to 50 occupants each. Again, keep in mind that at no time may the combined occupancy for these 3 rooms exceed 50 occupants. As stated in the previous correspondence, each ofthese three rooms must be posted with a capacity sign. \Ve will need to discuss verbiage of these signs in the future so as to address the room capacity as well as the total combined capacity. Referencing the August 5th correspondence, please remember that you must obtain specific approval to exceed the 50-occupant limit for each event. To date no submittal has been made indicating when these events may take place, nor has any submittal been made to outline what additional life and fire safety measures will be provided to allow a greater occupancy. Confirming point 3 made in the July 16, 2003 -correspondence (enclosed) submitted on your behalf by Norman Krause, CR Meyer, I do not anticipate approving any temporary approvals that would exceed 100 occupants as this would not have been allowed by the previous Building Code. During this recent inspection it was learned you have already been using this building for RC Vehicle Racing. Please be advised this must cease until you have secured the required Occupancy Permit. This will not be approved until all life and fire safety code issues have been satisfied. The Building and HV AC code issues noted during the October 21, 2003 inspection are as follows: 1. Your present building permit does not cover all of the work witnessed. A review of this permit shows it is for the 3 restrooms, furring and finishing the exterior walls ofthe second floor and installing a suspended ceiling in the second floor. This permit did not include replacing windows on the second floor, installing a room in the west, second floor room or installation of any other various partition walls in this building. A floor plan must be submitted showing the alterations that have I taken plus any other alterations that are planned to obtain a permit for this additional work. 2. The emergency lighting and exit lighting shall be brought into compliance with the present day code standards as previously stated in my August 5, 2003 correspondence. Because the previous lighting was removed and/or altered, it must be reinstalled in compliance with present day code standards. It is suggested that you obtain professional design services to assist you with this as the present day code is more involved than past code standards. 3. The first floor, west room used for racing must be provided with an HV AC system that meets present day standards. This area was previously used for warehousing. Warehousing did not have requirements for fresh air exchange. Due to the conversion to an occupied space, this area must now be provided with an HV AC system that will provide for the required amount of fresh air and exhausted air based on the calculated occupant load as well as meeting the heating needs of this room. HV AC Plans prepared by a Wisconsin Registered HV AC Designer, Architect or Engineer must be submitted for review and approval. 4. The exit path leading to the west, second floor fire escape must be at least 44 inches in width. This may be reduced to 36 inches ifthe occupant load will not exceed 50 occupants. (If you are planning events to exceed 50 occupants, the 44-inch exit path will be required.) 5. All stairs leading to participant platforms shall be provided with uniform stairs. Treads shall be a minimum of 11 ", risers shall not exceed 7", and the risers cannot be open. See Comm 62.1003.3.3, copy provided. 6. Guardrails shall be provided as required in COMM 62.1003.2.12. Refers to participant platforms and the loading dock platform. Copy provided. 7. Handrails shall be provided as required in COMM 61.1003.3.3.11. Refers to the participant platform stairs, loading dock ramp as well as any existing stairs that do not have handrails. Copy provided. "8. . The second floor west bathroom shall have a'door where'the hinges are located at the comer of the rooni. The doorknob/latch must located toward the tenter ofthe wall for handicap accessibility purposes~ The door may swing into the restrooin due'to the size of the restroom. 9. The door for the first floor restroom shall not swing into or obstruct the exit passageway. This door can swing into the restroom due to the size ofthe restroom. 10. Eliminate the trip hazard for the SW comer person platform in the 1 st floor racing room. 11. Grab bars shall be provided on the side and rear walls of the restrooms. 12. Toilet Flush levers shall face the open area of the room, they cannot be on the side ofthe tank adjacent to a wall. 13. The bathroom sink traps and water line valves shall be protected with insulating material to prevent bums and abrasions. 14. Obtain Occupancy Approval prior to use of the Racing Rooms. This list was provided in an attempt to assist you with this remodel. It may not be an all-inclusive list. For this reason you were previously encouraged to seek the services of a design professional. It may still be beneficial for you to consider seeking these services to lessen the likelihood of being presented with unexpected code issues during this project. If you have any questions, please call me at 236-5045. Enclosures ~. OJHKOJH ON THE WATER City of Oshkosh Division ofInspection Services 215 Church Avenue PO Box 1 J30 Oshkosh WI 54902-1130 Office 920-236-5050 Fax 920-236-5084 NORMAN KRAUSE CR MEYER PO BOX 2157 OSHKOSH WI 54903-2157 August 5, 2003 Re: Hobbytown Relocation; 807 Oregon St. Dear Norm, My apologies for not being able to respond sooner. I received your correspondence on July 25, 2003 and find it to be a fair account of the results of the conference call. I wanted to take this opportunity to elaborate further on what I understood to be resolved from the conference call we had with Randy Baldwin, IS Bureau Director, State of Wisconsin Department of Commerce, Division of Safety & Buildings. 1. The su~ject building at 807 Oregon St., will be allowed to use the previously defined areas. for RC', vehicle racing if the total capacity does not exceed 50 persons. As you state,.this occupant load must ' be posted (at the main entrance.) This use will be allowed as the Department has rendered direction that assembly uses not exceeding 50 persons may be considered a type Buses. This is further supported by the Department's "General Guidance Tool for Evaluating changes of Use in Commercial Buildings. " In this report, under Consideration 3, since the proposed RC Racing can be considered an accessory use to the proposed principle Retail use; the RC Racing would not be considered a Change of Occupancy. As a result these combined uses only need to be reviewed for compliance with the previous code. Ifthis review were to show that this structure did not comply with the previous code for the RC Racing use, then any modifications would have to be done in compliance with the current code. Norm, please note, that in item 1 you indicate "as it currently stands, does require any physical changes..." I suspect this was mis-typed and should have read "does not require any..." 2. If the owner has the need to exceed the 50 occupant limit for special events, it is within this office's discretion to review this as a Temporary Use per COMM 61.03(11). This section allows code officials the authority to grant temporary use approval, but also gives the code official the authority to require additional safety measures. Per our discussion after the conference call, it was stated that the owner of Hobbytown was leaning toward the installation of a smoke detection system. A system that complies with NFP A 72 would be a system that would be viewed favorably as it would provide early warning to the occupants. However, this is not to say this would be the only requirement if a request is made for a Temporary Use. Additional input on this would be requested from the Fire Department. Since various areas are undergoing significant remodeling, I would suggest that Mr. Magritz continue consulting with you or another design professional to determine if the building was in compliance. One area of concern I would have would be emergency lighting. I do not know what exists now, but with a building of this size, the previous code would have required emergency lighting. If this lighting was removed in preparation for the remodeling, then it would have to be reinstalled to meet present day standards. This isjust one example of why this building should be reviewed with a design professional, to identify these types of issues early on and avoid delays later in the project. If you have any questions, please call me at 236-5045. Sincerely; Allyn Dannhoff Director of Inspection Services cc: Ken Kraase, CR Meyer Randy Baldwin, Safety & Buildings Bill Magritz, Hobbytown OCT-21-2003 15:16 C.R.MEYER P.01 ( ft1NEYEf Building Solutions Since 1888 (920) 235-3350 Fax (9:20) 235-3419 895 W. 20th Ave. P. O. Box 2157 O!lbk.osh. WI 54903-2157 Fax Cover Sheet DATE~ TO: OCTOBER 21. 2003 Allyn Dannhoff CITY OF OSHKOSH FAX: 920-236-5084 FROM: Teri Ellis REFERENCE: LETTER RE: HOBBY TOWN Number of pages Including cover sheet: 3 Message: Allyn: I was unable to locate correspondence dated July 25th regarding Hobby Town. however I did find the attached letter which is dated July 1601. I hope this is the letter you're looking for. Please call me if I can assist you with anything else. C.R. MEYER FttXFOIW ..... OC1-21-2003 15:16 C.R.MEYER 895 W. 20th Avenue. P.O. Box 2157 ()$hk~.VVI54903"2157 (920) 235-3350 Fox (9'}Jj) 235--3419 t".1::I0::: .; COP" "'.-y . . . .~ .... \ ~ .. I [t4NiYE~ Building Solutions Since 1888 July 16, .2003 Mr. Bill Magrltt Hobby Town USA Aviation Plaza 2075 S. Koeller Road Oshkosh, WI 54902 Reference: New HobbyTown Building Location Main Street - Oshkosh, Wisconsin Dear Bill: This letter is intended to confirm the outcome of a conference call held at 9 a.m. among myself, Ken Kraase, Allyn Dannhoff (City of Oshkosh Building Inspector), Randy Baldwin (State of Wisconsin) on June 26,2003. 1. Your building, as it currently stands, does require any physical changes or alterations to he used as is up to a maximum capacity of 50 people. The capacity will need to be posted. 2. In the event that the 50 person capacity is exceeded (up to a maximum of 100) a conditional use permit would be required by the City of Oshkosh Building Inspector and approved by the Fire Chief. Hobby Town would need to apply for this Conditional Use Permit outlining: . Proposed use. . Quantity of people. . Life Safety measures proposed. . Diagramatic plan showing fixture and location of possible people and in what concentrations. . After review, a determination would be made regarding acceptance or other needed considerations. 3. In the eventthat you exceed 100 people, a Conditional Use Permit may no longer be acceptable and considerable changes may be required; for example, elevator, fire protection. exit widths. etc. Icl\llollOy lown\rrnlgrl\z..o71603 OCT-21-2003 15:16 C. R. MEYER P.03 . ..it " HobbyTown July .16, 2003 Page 2 We hope that the above information gives you the direction you need to move ahead. Yours truly, C.;(~~MPANY Norman L Krause Project Manager cc: Ken Kraase, C. R. Meyer Allyn Dannhoff, City of Oshkosh NLK:tle TOTAL P. 03 i ii II ,\ Ii I \ I ,I ,! III ,I 'I Ii II' ,I Ii II! 'I" II Ii, II! '.i. h ,l ~ ! ~, : Iii !ii ~H ~U . --.- _n'..._'.__,_....______ _.____~_._.__,.______.__..____.,,_.__._'_....__..._._:-;.."___ _.._.m_____._________..:." om._ m .... ..,d' 'n' ..... ._"._......._u...._. "'....n.."...". ..._...__...____,_.;_...___.____._..._...-,_,..._.......... .. .... ......." ...._., .on......... .._. Chapter 6, Plumbing Elements and Facilities 603.2.3 Doors. Doors shall not swing into the clear floor or ground space or clearance for any fixture. EXCEPTION: . Where the room is for indi- vidual use and a clear floor or ground space complying with Section 305.3 is provided . within the room, beyond the arc of the door swing. 603.3 Mirrors. Mirrors shall be mounted with the bottom edge of the reflecting surface 40 inches (1015 mm) maximum above the floor or ground. 603.4 Coat Hooks and Shelves. Coat hooks pro- vided within toiletrooms shaJlaccommodate a for- ward reach or side reach complying with Section . 308. Where provided, a fold-down shelf shall be 40 inches (1015 mm) minimum and 48 inches (1220 mm) maximum above the floor or ground. 604 Water Closets and Toilet Compartments 604.1 General. Accessible water closets and toilet compartments shall comply with Section 604. ' 604.2 Location. The water closet shall be{posi- tioned with a wall or partition to the rear and to one side. The centerline of the water closet shall be 16 inches (405 mm) minimum to 18 inches (455 mm) maximum from the side wall orpartition, except that the water closet shall be centered in the ambu- latory accessible compartment specified in Section 604.8.2. 604.3 Clearance. 604.3.1 S.ize. Clearaflce around the water clos- et shall be 60 inches (1220 inm) minimum, mea.,. sured perpendicular from the side wall, and. 56 inches (1420mm) minimum, measured per- pendicular from the rear wall. No other fixtures <t 16-18 405-455 Fig. 604.2 Water Closet Location 40 ICC/ANSIA117.1-1998 or obstructions shall be within the water closet clearance. 604.3.2 Overlap. The clearance around the wa- ter closet shall be permitteq to overlap the fix- ture, associated grab bars, tissue dispensers, accessible routes, and clear floor or ground space, or clearances at other fixtures and the wheelchair turning space. 604.4 Height. The top of water closet seats shall be 17 inches (430 mm) minimum and 19 inches (485 mm) maximum above the floor or ground. Seats shall not return automatically to a lifted position. ab bars for water closets shall 609. Grab bars shall be pro- vided on the rear wall and on the side wall closest to the water closet. 604.5.1 Side Wall. Side wall grab bar shall be 42 inches (1065 mm) long minimum, 12 inches (305 mm) maximum from the rear wall and extending 54 inches (1370 mm minimum from the rear wall. e * ([ Jl It~6~~i Fig. 604.4 Height of Water Closet ..~". V a ;\~~_..~ ICC/ANSI A117.1-1998 Fig. 604.5.1 , Side Wall Grab Bar for Water Closet c 'E co Nt") .;:::- .... ~ c 'E g lOt") ,... 7-9 180-230 (a) Below Grab Bar ~ Chapter 6. Plumbing Elements and Facilities 1 k d transfer side *36 inches (915 mm) minimum when wall space. permits Fig. 604.5.2 Rear Wall Grab Bar for Water Closet 12 min 305 <t .. + ~..~ E C\I .C\I co .... '<t 7-9 180-230 . (b) Above Grab Bar Fig. 604.7 . Dispenser Location t 604.5.2 Rear Wall. The rear wall grab bar shall be 24 inches (610 mm) long minimum, centered on the water closet.. Where space permits; the bar shall be 36 inches (915 mm) long minimum, with the additional length provided on the trans- fer side of ~he water closet. 604.7 Dispensers. Toilet paper dispensers$,hall comply with. Section 309.4 and 'shall be 7 inches (180 mm) minimum and 9 inches (230 mm) maxi- mum infron! of the water closet. The outlet ofthe dispenser shall be 15 inches (380 mm) minimum and 48 inches (1220 mm) maximum above the floor or ground. There shall be a clearance of 11/2 inches (38 mm) minimum below and 12 inches (305 mm) minimum above the grab bar. Dispensers shall not be of a type that control deliveiy, or thatdon6t allow continuous paper flow. . 604.8 Toilet.. Compartments., Accessible toilet compartments ,shelll comply with Sections 604.8.1 through 604.8.5. Compartments containing more than one plumbing fixture shall comply with Section 603. Water closets in accessible toilet compart- ments shall comply with Sections 604.1 through 604.7. 604.8.1 Wheelchair Accessible Compart- ments. ' 604.8.1.1 Size. Wheelchair accessible . compartments shall be 60 inches (1525 mm) wide minimum measured perpendicu- lar to the side wall, and 56 inches (1420 mm) deep minimum for wall hung water closets and 59 inches (1500 mm) deep 41 ((t <<I ICC/ANSI A117.1-1998 6max ~ 6max ~ 1. ~o EIt) ..... <0 (a) Standard RolI-ln-Type Shower 6max ~ Chapter 6. Plumbing Elements and Facilities 6max ~ ~..ro E It) ..... <0 (b) Roll-in-Type Shower with Seat 6max ~ .~r E It) ..... <0 (c) Alternate Roll-ln-Type Shower Fig. 608.3.2 Grab Bars in Roll-ln-Type Showers the seat at the control wall and shall not be behind the seat. 2. In alternate roll-in-type showers, grab bars shall not be required on the side wall opposite the control. wall and Sl1all not be behind the seat. 608.4 Seats. An attachable or integral seat shall be provided in transfer-type shower compartments. Seats shall comply with Section 610. . 608.5 Controls. Shower or. bathtub/shower facili- ties shall deliver water that is thermal shock pro- tected to 1200F maximum. Faucets and controls shall comply with Section 309.4. Controls in roll-in showers shall be above the grab bar but no higher than 48 inches (1220 mm) above the shower floor. In transfer-type shower compartments, controls, fauce~s, arid the. shower unit shall be on the side wall opposite the.se'at 38 inches (965"mm) minimum and- . 48 inches (1220 mm) maximum above the shower floor. 608.6 Shower Unit. A shower spray unit shall be provided, with a hose 59 inches (1500 mm) long minimum, that can be used as a fixed shower head and as a hand-held shower. In transfer type show- ers, the controls and shower unit shall be on tne con- trol wall within 15 inches (380 mm),Jeft or right, of the centerline of the seat. In roll-in-tYpe showers, shower spray units mounted on the back wall shall be 27 inches (685 mm) maximum from the side wall. If an adjustable-height shower head mounted on a vertical bar is used, the bar shall not obstruct the use of grab bars. . 608.7 Thresholds. Shower compartment thresh- olds shall be1hinch (13 mm) high maximum and shall cqmply with Section 303. . 608.8 Shower Enclosures. Shower compartment enclosures for shower compartments shall not obstruct controls or obstruct transfer from wheel- . chairs onto shower seats. f 609.1 General. Grab bars in accessible toilet or bathing facilities shall comply with Section 609. ' hall have a circular crosS w lameter of 11/4 inch (32 mm) mini- ;- mum and 2 inches (51 mm) maximum, oLshaU pro- 47 i\l Chapter 6. Plumbing Elements and Facilities ICC/ANSI A117.1-199S ~o E C\/ C\/ c:o..... q- 15 max 380 I' 27 max v 685 1 back wall ~ <<: ~ e ~ control~ wall ~ I I I I (a) (b) Fig. 608.5 Controls In Transfer-Type Showers Fig. 608.6 Location of Shower Spray Unit 1: I c .- 0 E c:o 10(') ..... e 4 to 4.8 erimeter, 100-120 (a) Circular (b) (c) Non-Circular Fig. 609.2 Size of Grab Bars Fig. 609.3 Spacing of Grab ears 609.2.1 Non-Circular Cross Sections. Grab bars with other shapes shall be permitted pro- .... vided they have a perimeter dimension of 4 inches (100 mm) minimum and4.8ioches p20 mm) maximum and with edges having a Is inch (3~2 mm) minimum radius. .... EXCEPTION: The space between,the grab bars and shower. controls, shower fittings, and other grab bars above shall be 1112 inches (38 mm) minimum. ft vide equivalentgraspability complying withSectiqn 609.2.1. .. ., rab bars shall be .. a horizontal po ,33 inches (840 mm) minimum and 36 inches (915 mm) maximum above the floor. .. EXCEPTION: Height of grab bars on the back wall .. of a bathtub' shall comply with Sections 607.4.1.1 and ~07 .4.2.1. .. 609.5 Surface Hazards. Grab bars and any wall or other surlaces adjacent to grab bars shall be free of sharp or abrasive elements. Edges shall have a radius of 1/sinch (3 mm) minimum. I) :{ between the wall and 2 es (38mm). The space between the grab bar and objects below and at the ends shall be 11/2 inches' (38 mm)minimum. The space between the grab bar and projecting objects above shall be 15 inches (355mm) minimum. .. 48 ---::: I' ;.k~ ~ .:LEe- At~"-,,,,J v-;,.f.;/- ~_I#<S: 102 TUE 10:19 F~ 920 492 5604 . . ~O'bOlERCE woo:t AccessJble ToDet Rooms per Ch. Ci of ANSI A-117.1-1998 6'-2. &'.oh" OPTION lA' ".t>. ,'4' :r .... 9 ";b OPTION IC' ~ ~ ~ OPTION 'B' OPTION -0- OPTION 'E' OPTION fF' '5~. ,,'4 ~E:: v.....,,\.-<;l" .. .... ~ ot~ ~ ~\l1JJ'4 ll'!llv TO snb. "~ 10 tw:H Sloa FOP. ~.~~~~K'U.. nu:. !lI1c 5ILI; ~ I:;. l'~' WlDE x1'-6' oW' ,. TC:llLET 9lOI'ltl EXTi:NDS .2~" FROM PlNl5Hl!P ~ gI-lADS) ....REA D~ 5O'1C4&. GLEAA t=LaoR ARJYt. fU!61J1Rl!t' ~ iWClR ~1oIGS INW ~ (:l.fAA Fl-OOR AP!iA AND/OR 'I\IRt4I/'ICI ~ l1ef PICAl1I~ (;Q\IR're;'I" Of. DESIGN UNLIMITED OPTION 'GI OPTION 'HI ~.~N DANlI'i. J. tlElHI6, MGtil~T. NA MEANS OF EGRESS ~ )f at least one handrail complying with Section 1003.3.3.11 is provided within 30 inches (762 mm) of the centerline of the normal path of egress travel on the stair. 3. An aisle serving seating that has a difference in ele- vation less than 12 inches (305 mm) is permitted at locations not required to be accessible by Chapter 11, provided that the risers and treads comply with Section 1008.9 and the aisle is provided with a handrail complying with Section 1008.11. Any change in elevation in a corridor serving non ambulatory persons in a Group 1-2 occupancy shall be by means of a ramp or sloped walkway. 1003.2.8 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. 1003.2.9 Elevators, escalators, and moviug walks. Eleva- tors, escalators and moving walks shall not be used as a component of a required means of egress from any other part of the building. Exceptiou: Elevators used as an accessible means of egress in accordance with Section 1003.2.13.3. xit signs shall comply with Sections ough 1003.2.10.5. Ig _ ,.,_ .'Cre required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to ex- its shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immedi- ately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) from the nearest visible exit sign. Exceptions: 1. Exit signs are not required in rooms or areas which require only one exit or exit access. 2. Main exterior exit doors or gates which obvi- ously and clearly are identifiable as exits need not have exit signs where approved by the build- ing official. 3. Exit signs are not required in occupancies in Group R-3 as applicable in Section 101.2, Group U, guestrooms in Group R-1, dwelling units in Group R-2 as applicable in Section 101.2 and sleeping rooms. 4. Exit signs are not required in sleeping room areas in occupancies in Group 1-3. 5. In occupancies in Groups A-4 and A-5 that in- clude grandstand seating arrangements, exit signs are not required on the seating side of vomitories or openings into seating areas where 2002 WISCONSIN ENROLLED COMMERCIAL BUILDING CODE 1003.2.8 - 1003.2.11 exit signs are provided in the concourse that are readily apparent from the vomitories and egress lighting is provided to identify each vomitory or opening within the seating area in an emer- gency. 1003.2.10.2 Graphics. Every exit sign and directional exit sign shall have plainly legible letters not less than 6 inches (152 mm) high with the principal strokes of the letters not less than 0.75 inch (19.1 mm) wide. The word "EXIT" shall have letters having a width not less than 2 inches (51 mm) wide except the letter "I", and the mini- mum spacing between letters shall not be less than 0.375 inch (9.5 mm). Signs larger than the minimum estab- lished in this section shall have letter widths, strokes and spacing in proportion to their height. The word "EXIT" shall be in high contrast with the background and shall be clearly discernible when the exit sign illumination means is or is not energized. If an arrow is provided as part of the exit sign, the construction shall be such that the arrow direction cannot be readily changed. 1003.2.10.3 Stairway exit signs. A tactile sign stating "EXIT" and complying with Chapter 11 shall be pro- videdadjacent to each door to an egress stairway. ~sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an in- tensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. . Exceptions: 1. Approved self-luminous exit signs that provide evenly illuminated letters shall have a mini" mum luminance of 0.06 foot-Iamberts (0.21 cdlm2). 2. Tactile signs required by Section 1003.2.10.3 need not be provided with illumination. ~rce. Exit signs shall be illumi- ~To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the exit signs shall be connected to an emer- gency electrical system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with the ICC Electrical Code. Exception: Approved exit signs that provide continu- ous illumination independent of external power sources for a duration of not less than 90 minutes, in case of primary power loss, are not required to be con- nected to an emergency electrical system. ..l e means of '1'- egress, inc u ng e eXIt discharge, s illuminated at all times the building space served by the means of egress is occupied. Exceptions: 1. Occupancies in Group U. I i(( 8-183 1003.2.11.1 -1003~2.12.2 * 2. Aisle accessways in Group A. 3. Guestrooms in Group R-I, dwelling units and sleeping rooms in Groups R-2 and R-3 as applica- ble in Section 101.2. 4. Sleeping rooms and areas of Group I occupancies. e means of egress il- ummation level shall not be less than 1 foot-candle (11 lux) at the floor level. Exception: For auditoriums, theaters, concert or op- era halls and similar assembly occupancies, the illu- mination at the floor level is permitted to be reduced during performances to not less than 0.2 foot-candle (2.15 lux) provided that the required illumination is automatically restored upon activation of a premise's fire alarm system where such system is provided. he power supply for means of egress 1 ununation shall nor- mally be provided by the premise's electrical supply. In the event of power supply failure, an emergency system shall automatically illuminate all of the following areas: 1. Exit access corridors, passageways, and aisles in rooms and spaces which require two or more means of egress. 2. Exit access corridors and exit stairways located in buildings required to have two or more exits. 3; Interior exit discharge elements, as permitted in Section 1006.1, in buildings required to have two or more exits. 4. The portion of the exterior exit discharge immedi- ately adjacent to exit discharge doorways in build- ings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with the ICC Electrical Code. rgency light- ing facilities shall be arranged to provide initial illumina- tion that is at least an average of 1 foot-candle (11 lux) and a minimum at any point of 0.1 foot-candle (1 lux) measured along the path of egress at floor level. Illumi- nation levels shall be permitted to decline to 0.6 foot-can- dle (6 lux) average and a minimum at any point of 0.06 foot-candle (0.6 lux) at the end of the emergency lighting time duration. A maximum-to-minimum illumination uniformity ratio of 40 to 1 shall not be exceeded. ds shall be located along open- S1 e w , mezzanines, industrial equipment platforms, stairways,ramps and landings which are located more than 30 inches (762mm) above the floor or grade be- low. Guards shall be adequate in strength and attachment in accordance with Section 1607.7. Guards shall also be lo- cated along glazed sides of stairways, ramps and landings that are located more than 30 inches (762 rom) above the floor or grade below where the glazing'provided does not * ~ B-184 MEANSOF EGRESS meet the strength and attachment requirements in Section 1607.7. Exception: Guards are not required for the following lo- cations: 1. On the loading side of loading docks or piers. 2. On the audience side of stages and raised plat- forms, including steps leading up to the stage and raised platforms. 3. On raised stage and platform floor areas such as runways, ramps and side stages used for entertain- ment or presentations. 4. At vertical openings in the performance area of stages and platforms. 5. At elevated walking surfaces appurtenant to stages and platforms for access to and utilization of spe- ciallighting or equipment. 6. Along vehicle service pits not accessible to the public. . 7. In assembly seating where guards in accordance with Section 1008.12 are permitted and provided. _1'1 m ]~ ..lards shall form a protective bar- rier not less than 42 inches (1067 mm) high, measured vertically above the leading edge of the tread, adjacent walking surface or adjacent seatboard. . Exception: For occupancies in Group R-3, and within individual dwelling units in occupancies in Group R- 2, both as applicable in Section 101.2, guards whose top rail also serves as a handrail shall have a height not less than 34 inches (864 mm) and not more than 38 inches (965 mm) measured vertically from the lead- ing edge of the stair tread nosing. . Open guards shall have balusters or ornament pa ems such that a 4-inch- diameter (102 mm) sphere cannot pass through any opening up to a height of 34 inches (864 mm). From a height of 34 inches (864 mm) to 42 inches (1067 rom) above the adjacent walking surfaces, a sphere 8 inches (203 mm) in diameter shall not pass. Exceptions: 1. The triangular openings formed by the riser, tread and bottom rail at the open side of a stair- way shall be of a maximum size such that a sphere of 6 inches (152 mm) in diameter cannot pass through the opening. 2. At elevated walking surfaces for access to and use of electrical, mechanical, or plumbing sys- tems or equipment, guards shall have balusters or be of solid materials such that a sphere with a diameter of 21 inches (533 mm) cannot pass through any opening. 3. In occupancies in Group 1-3, F, H or S, balus- ters,horizontal intermediate rails or other con- struction shall not permit a sphere with a diameterof21 inches (533 rom) to pass through any opening. Y:: K 2002 WISCONSIN ENROLLED COMMERCIAL BUILDING CODE MEANS OF EGRESS i< 1003.3.2 Gates. Gates serving the means of egress system shall comply with the requirements of this section. Gates used as a component in a means of egress shall conform to the applicable requirements for doors. Exception: Horizontal sliding or swinging gates exceed- ing the 4- foot maximum (1219 mm) leaf width limitation are permitted in fences and walls surrounding a stadium. 1003.3.2.1 Stadiums. Panic hardware is not required on gates surrounding stadiums where such gates are under constant immediate supervision while the public is pres- ent, and further provided that safe dispersal areas based on 3 square feet (0.28 m2) per occupant are located between the fence and enclosed space. Such required safe dispersal areas shall not be located less than 50 feet (15240 rom) from the enclosed space. See Section 1005 for means of egress from safe dispersal areas. 1003.3.2.2 Educational uses. School grounds are per- mitted to be fenced and gates therein are permitted to be equipped with locks, provided that safe dispersal areas based on 3 square feet (0.28 m2) per occupant are located between the school and the fence. Such required safe dis- persal areas shall not be located less than 50 feet (15 240 rom) from school buildings. See Section 1005 for means of e ess from safe dispersal areas. I ys shall comply with Sections 1003.3.3.1 through 1003.3.3.12.1. 1003.3.3.1 Stairway width. The width of stairways shall be determined as specified in Section 1003.2.3 but such width shall not be less than 44 inches (1118 rom). See Section 1003.2.13.2 for accessible means of egress stair- ways. Exceptions: 1. Stairways serving an occupant load of 50 or less shall have a width of not less fl. J I 1-. . (914 rom). 2. Spiral stairways as provided for in Section 1003.3.3.9. 3. Aisle stairs complying with Section 1008. 4. Where a stairway lift is installed on stairways serving occupancies in Group R-3, or within dwelling units in occupancies in Group R-2, both as applicable in Section 101.2, a clear pas- sage width not less than 20 inches (508 mm) shall be provided. 1003.3.3.2 Headroom. Stairways shall have a minimum headroom clearance of 80 inches (2032 mm) measured vertically from a line connecting the edge of the nosings. Such headroom shall be continuous above the stairway to the point where the line intersects the landing below, one tread depth beyond the bottom riser. The minimum clear- ance shall be maintained the full width of the stairway and landing. Exception: Spiral stairways complying with Section 1003.3.3.9 are permitted a 78-inch (1981 mm) head- room clearance. 'f<' 2002 WISCONSIN ENROLLED COMMERCIAL BUILDING CODE 100:p.2 ~.1003.3.3.;3.1 'f;- . riser heights sha mm) maxImum and 4 inches (102 rom) minimum. Stair tread depths shall be 11 inches (279 mm) minimum. The riser height shall be measured verti- cally between the leading edges of adjacent treads. The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at right angle to the tread's leading edge. Exceptions: 1. Circular stairways in accordance with Section 1003.3.3.7. 2. Winders in accordance with Section 1003.3.3.8. 3. Spiral stairways in accordance with Section 1003.3.3.9. 4. Aisle stairs in assembly seating areas where the stair pitch or slope is set, for sightline reasons, by the slope of the adjacent seating area in ac- cordance with Section 1008.9.2. 5. In occupancies in Group R-3, as applicable in Section 101.2, within dwelling units in occu- pancies in Group R-2, as applicable in Section 101.2, and in occupancies in Group D, which are accessory to an occupancy in Group R-3, as applicable in Section 101.2, the maximum riser height shall be 7.75 inches (197 rom) and the minimum tread depth shall be 10 inches (254 rom). A nosing not less than 0.75 inch (19.1 mm) but not more than 1.25 inches (32 mm) shall be provided on stairways with solid risers where the tread depth is less than 11 inches (279 mm). 6. See Section 3402.4 for the replacement of exist- ing stairways. :w.,&J!". -"..I.Ui~ Stair treads and risers shall be of uniform size and shape. The tol- erance between the largest and smallest riser or be- tween the largest and smallest tread shall not exceed 0.375 inch (9.5 mm) in any flight of stairs. Exceptions: 1. Nonuniform riser dimensions of aisle stairs complying with Section 1008.9.2. 2. Consistently shaped winders, complying with Section 1003.3.3.8, differing from rect- angular treads in the same stairway flight. Where the bottom or top riser adjoins a sloping public way, walkway or driveway having an estab- lished grade and serving as a landing, the bottom or top riser is permitted to be reduced along the slope to less than 4 inches (102 mm) in height with the varia- tion in height of the bottom or top riser not to exceed one unit vertical in 12 units horizontal (8-percent slope) of stairway width. The nosings or leading edges of treads at such nonuniform height risers shall have a distinctive marking stripe, different from any other nosing marking provided on the stair flight. The ~ 8-191 1 003.3.3.3.Z,-:: ,1.0l)3.:p. to.t '. MEANS OF EGRESS'. -* distinctive marking stripe shall be visible in descent o.f the stair and shall have a slip-resistant surface. Marking stripes shall have a width o.f at least 1 inch (25.4 mm) but no.t mo.re than 2 inches (51 mm). . J,~ 11l111r nBlIiIsadius o.f curvature at the leading edge o.f the treadShall be no.t greater than 0.5 inch (12.7 mm). Beveling o.f no.sings shall no.t exceed 0.5 inch (12.7 mm). Risers shall be so.lid and vertical o.r slo.ped fro.m the underside o.f the leading edge o.f the tread abo.ve at an angle no.t mo.re than 30 degrees (0.52 rad) from the vertical. The leading edge (no.sings) o.f treads shall pro.ject no.t mo.re than 1.25 inches (32 mm) beyo.nd the tread belo.w and all projectio.ns o.f the leading edges shall be o.f unifo.rm size, including the leading edge o.f the flo.o.r at the to.p o.f a flight. Exceptions: 1. So.lid risers are no.t required fo.r stairways that are no.t required to' co.mply with Sectio.n 1003.2.13.2, pro.vided that the o.pening be- . tween treads do.es no.t permit the passage o.f a sphere with a diameter o.f 4 inches (102 mm). 2. So.lid risers are no.t required fo.r occupancies in Group 1-3. 1003.3.3.4 Stairway landings. There shall be a flo.o.r o.r landing at the to.p and bo.tto.m o.f each stairway. The width of landings shall no.t be less than the width of stairways they serve. Every landing shall have a minimum dimen- sio.n measured in the direction o.f travel equal to' the width of the stairway. Such dimensio.n need no.t exceed 48 inches (1219 mm) where the stairway has a straight run. Exceptions: 1. Aisle stairs co.mplying with Sectio.n 1008. 2. Do.o.rs o.pening onto. a landing shall no.t reduce the landing to' less than o.ne-half the required . width. When fully o.pen, the do.o.r shall no.t pro- ject mo.re than 7 inches (178 mm) into. a land- ing. 1003.3.3.5 Stairway construction. All stairways shall be built o.f materials co.nsistent with the types permitted fo.r the type o.f co.nstructio.n o.f the building, except that wood handrails shall be permitted fo.r all types o.f co.n- structio.n. 1003.3.3.5.1 Stairway walking surface. The walk- ing surface o.f treads and landings o.f a stairway shall no.t be slo.ped steeper than o.ne unit vertical in48 units ho.nzo.ntal (2-percent slo.pe) in any directio.n. Stair- way landings shall have a so.lid surface. Finish flo.o.r surfaces shall be securely attached. Exception: In Gro.up F, H and S o.ccupancies, o.ther than areas o.f parking structures accessible to. the public, o.penings in treads and landing plat- fo.rms shall no.t be pro.hibited pro.vided a sphere with a diameter o.f 1.125 inches (29 rom) canno.t pass thro.ugh the o.pening. B-192 1003.3.3.5.2 Outdoor conditions. Outdoor stairways and o.utdo.or approaches to. stairways shall be de- signed so. that water will no.t accumulate o.n walking surfaces. In o.ther than o.ccupancies in Gro.up R-3, and occupancies in Gro.up U that are accesso.ry to' an occu- pancy in Gro.up R-3, treads, platfo.rms and landings that are part o.f exterio.r stairways in climates subject to' sno.w o.r ice shall be protected to. prevent the accu- mulatio.n o.f same. 1003.3.3.6 Vertical rise. A flight o.f stairs shall no.t have a vertical rise greater than 12 feet (3658 mm) between flo.o.r levels o.r landings. Exception: Aisle stairs co.mplying with Sectio.n 1008. 1003.3.3.7 Circular stairways. Circular stairways shall have a miuimum tread depth and a maximum riser height in acco.rdance with Sectio.n 1003.3.3.3 and the smaller radius shall no.t be less than twice the width o.f the stair- way. The minimum tread depth measured 12 inches (305 mm) from the narro.wer end o.f the tread shall no.t be less than 11 inches (279 rom). The minimum tread depth at the narro.w end shall uo.t be less than 10 inches (254 rom). Exception: Fo.r o.ccupancies in Group R-3, and within individual dwelling units in occupancies in Gro.up R- 2, bo.th as applicable in Sectio.n 101.2, the smaller ra- dius restrictio.n shall no.t apply and the minimum tread depth at the narro.w end shall no.t be less than 6 inches (152 rom). 1003.3.3.8 Winders. Wmders are no.t permitted in means o.f egress stairways except within a dwelling unit. Winders shall have a tread depth o.f no.t less than 11 inches (279 rom) at a point no.t mo.re than 12 inches (305 mm) from the narro.w edge. The minimum tread depth shall no.t be less than 6 inches (152 rom). 1003.3.3.9 Spiral stairways. Spiral stairways are per- mitted to' be used as a co.mpo.nent in the means o.f egress o.nly within dwelling units o.r fro.m a space no.t mo.re than 250 square feet (23 m2) in area and serving no.t mo.re than five occupants, o.r from galleries, catwalks, and gridiro.ns in acco.rdance with Sectio.n 1007.5. A spiral stairway shall have a 7.5-inch (191 mm) mini- mum clear tread depth at a po.int 12 inches (305 rom) from the narro.w edge. The risers shall be sufficient to' pro.vide a headro.o.m o.f 78 inches (1981 mm) minimum, but riser height shall no.t be mo.re than 9.5 inches (241 rom). The minimum stairway width shall be 26 inches (660 rom). 1003.3.3.10 Alternating tread devices. Alternating tread devices are limited to' an element o.f a means o.f egress in buildings o.f Gro.ups F, H and S from a mezza- nine no.t mo.re than 250 square feet (23 m2) in area and which serves no.t mo.re than five occupants; in buildings o.f Gro.up 1-3 fro.m a guard to.wer, o.bservatio.n statio.n o.r co.ntro.l roo.m no.t mo.re than 250 square feet (23 m2) in area; and fo.r access to' unoccupied roofs. 1003.3.3.10.1 Handrails of alternating tread de- vices. Handrails shall be pro.vided o.n bo.th sides o.f al- 2002 WISCONSIN ENROLLED COMMERCIAL BUILDING COOl;: MEANS OF EGRESS 4- ternating tread devices and shall conform to Section 1003.3.3.11. 1003.3.3.10.2 Treads of alternating tread devices. Alternating tread devices shall have a minimum pro- jected tread of 5 inches (127 mm), a minimum tread depth of8.5 inches (216 mm), a minimum tread width of 7 inches (178 mm) and a maximum riser height of 9.5 inches (241 mm). The initial tread of the device shall begin at the same elevation as the platform, land- ing or floor surface. Exception: Alternating tread devices used as an element of a means of egress in buildings from a mezzanine area not more than 250 square feet (23 m2) in area which serves not more than five occu- pants shall have a minimum projected tread of 8.5 inches (216 rom) with a minimum tread depth of 10.5 inches (267 rom). The rise to the next alternat- ing tread surface should not be more than 8 inches (203 rom). ays shall have handrails 1 be adequate in strength and attachment in accordance with Section 1607.7. Exceptions: 1. Aisle stairs provided with a center handrail need not have additional handrails. 2. Stairways within dwelling units, spiral stair- ways and aisle stairs serving seating only on one side are permitted to have a handrail on one side only. 3. Decks, patios, and walkways that have a single change in elevation where the landing depth on each side of the change of elevation is greater than what is required for a landing do not re- quire handrails. 4. In Group R-3 occupancies, a change in eleva- tion consisting of a single riser at an entrance or egress door does not require handrails. 5. Changes in room elevations of only one riser within dwelling units in Group R-2 and R-3 oc- cu ancies do not require handrails. andrail height, measured above stair tread nosings, or finish surface of ramp slope, shall be uniform, not less than 34 inches (864 and not more than 38 inches (965 rom). ermediate handrails are required so that all portions of the stair- way width required for egress capacity are within 30 inches (762 rom) of a handrail. On monumental stairs, handrails shall be located along the most direct path of egress travel. r f 'x-.. C"""'" ails with a CITC ar cross sec on s a ave an outside diameter of at least 1.25 inches (32 mm) and not greater than 2 inches (51 mm) or shall provide equivalent graspability. If the handrail is not circular, it shall have 2002 WISCONSIN ENROLLED COMMERCIAL BUILDING CODE 1003.3.3.10;2....1003;3.3;12 a perimeter dimension of at least 4 inches (102 rom) and not greater than 6.25 inches (159 rom) with a maximum cross-section dimension of 2.25 inches (57 rom). Edges shall have a minimum radius of 0.125 inch (3.2 rom). ~~~~JbL. ~.. . ~rail-gripping sur- :{::: faces shall be continuous, without interruption by newel posts or other obstructions. Exceptions: i 1. Handrails within dw 'ling units are permit- ted to be interrupted y a newel post at a stair landing. 2. Within a dwelling nit, the use of a volute, turnout or starting asing is allowed on the lowest tread. 3. Handr. ai.l brack<et p,r balust.ers attaChedtto the bottom surfac f the handrail that do ot project horizontal beyond the sides of he handrail within 1.5 inches (38 rom) of the bottom of the handrail shall not be con id- ered to be obstructions. andrails shall: K re urn 0 a w , g g surface or shall! be continuous to the handrail of an adjacent stair: flight. Where handrails are not continuous between flights, the handrails shall extend horizontally at least 12 inches (305 rom) beyond the top riser and continue to slope for the depth of one tread beyond the bottom riser. Exceptions: 1. Handrails within a dwelling unit that is not required to be accessible need extend only from the top riser to the bottom riser. 2. Aisle handrails in Group A occupancies in accordance with Section 1008.11. Clear space between a .V han an ace shall be a mini- 7'- mum of 1.5 inches (38 rom). A handrail and a wall or other surface adjacent to the handrail shall be free of any sharp or abrasive elements. ~ ill _~l~~v _Projections f: into e required width at each handrail shall not ex- ceed 4.5 inches (114 rom) at or below the handrail height. Projections into the required width shall not be limited above the minimum headroom height re- quired in Section 1003.3.3.2. 1003.3.3.12 Stairway to roof. In buildings four or more stories in height above grade, one stairway shall extend to the roof surface, unless the roof has a slope steeper than four units vertical in 12 units horizontal (33-percent slope). In buildings without an occupied roof, access to the roof from the top story shall be permitted to be by an alternating tread device. . 8-193 1003.3.3.12.1- ,1 003.~.4.8 MEANS OF'EGRESS k 1003.3.3.12.1 Roof access. Where a stairway is pro- vided to a roof, access to the roof shall be provided through a penthouse complying with Section 1509.2. Exception: In buildings without an occupied roof, access to the roof shall be permitted to be a roof hatch or trap door not less than 16 square feet (1.5 m2) in area and having a minimum dimension of2 feet(61O mm . used as a component of a means of egress s a 1 conform to the provisions of Sections 1003.3.4.1 through 1003.3.4.9. Exceptions: 1. Ramped aisles within assembly rooms or spaces shall conform to the provisions in Section 1008.9. 2. Curb ramps shall comply with ICC AIl7.1. 1003.3.4.1 Slope. Ramps used as part of a means of egress shall have a running slope not steeper than one unit vertical in 12 units horizontal (8-percentslope). The slope of other ramps shall not be steeper than one unit vertical in eight units horizontal (12.5-percent slope). Exception: Aisle ramp slope in occupancies of Group A shall comply with Section 1008.9. 1003.3.4.2 Cross slope. The slope measured perpendic- ular to the direction of travel of a ramp shall not be steeper than one unit vertical in 48 units horizontal (2- percent slope). 1003.3.4.3 Rise. The rise for any ramp shall be 30 inches (762 mm) maximum. 1003.3.4.4 Minimnm dimensions. The minimum di- mensions of means of egress ramps shall comply with Sections 1003.3.4.4.1 through 1003.3.4.4.3. 1003.3.4.4.1 Width. The minimum width of a means of egress ramp shall not be less than that required for corridors by Section 1004.3.2.2. The clear width of a ramp and the clear width between handrails, if pro- vided, shall be 36 inches (914 mm) minimum. 1003.3.4.4.2 Headroom. The minimum headroom in all parts of the means of egress ramp shall not be less than 80 inches (2032 mm). 1003.3.4.4.3 Restrictions. Means of egress ramps shall not reduce in width in the direction of egress travel. Projections into the required ramp and landing width are prohibited. Doors opening onto a landing shall not reduce the clear width to less than 42 inches (1067mm). 1003.3.4.5 Landings. Ramps shall have landings at the bottom and top of each ramp, points of turning, entrance, exits and at doors. Landings shall comply with Sections 1003.3.4.5.1 through 1003.3.4.5.5. 1003.3.4.5.1 Slope. Landings shall have a slope not steeper than one unit vertical in 48 units horizontal (2- percent slope) in any direction. Changes in level are not permitted. B-194 1003.3.4.5.2 Width. The landing shall be at least as wide as the widest ramp run adjoining the landing. 1003.3.4.5.3 Length. The landing length shall be 60 inches (1525 mm) minimum. Exception: Landings in nonaccessible Group R - 2 and R-3 individual dwelling units, as applicable in Section 101.2, are permitted to be 36 inches (914 mm) minimum. 1003.3.4.5.4 Change in direction. Where changes in direction of travel occur at landings provided between ramp runs, the landing shall be 60 inches (1524 mm) minimum by 60 inches (1524 mm) minimum. Exception: Landings in nonaccessible Group R - 2 and R-3 individual dwelling units, as applicable in Section 101.2, are permitted to be 36 inches (914 mm) by 36 inches (914 mm) minimum. 1003.3.4.5.5 Doorways. Where doorways are located adjacent to a ramp landing, maneuvering clearances required by ICC A 117.1 are permitted to overlap the required landing area. 1003.3.4.6 Ramp construction. All ramps shall be built of materials consistent with the types permitted for the type of construction of the building; except that wood handrails shall be permitted for all types of construction. Ramps used as an exit shall conform to the applicable re- quirements of Sections 1005.3.2 and 1005.3.4 for verti- cal exit enclosures. 1003.3.4.6.1 Ramp surface. The surface of ramps shall be of slip-resistant materials that are securely at- tached. 1003.3.4.6.2 Outdoor conditions. Outdoor ramps and outdoor approaches to ramps shall be designed so that water will not accumulate on walking surfaces. In other than occupancies in Group R-3, and occupan- cies in Group U that are accessory to an occupancy in Group R-3, surfaces and landings which are part of exterior ramps in climates subject to snow or ice shall be designed to minimize the accumulation of same. ~~ . .Jti.ps with a rise greater than 6 :f:- inches (152 mm) shall have handrails on both sides com- plying with Section 1003.3.3.11. J.f~rotectim1 ~ protection complying It with~....~."l'.~l 'orl003.3.4.8.2shall be pro- vided on each side of ramp runs and at each side of ramp landings. Exceptions: 1. Edge protection is not required on ramps not re- quired to have handrails, provided they have flared sides that comply with the ICC Al17.1 curb ramp provisions. 2. Edge protection is not required on the sides of ramp landings serving an adjoining ramp run or stairway. 3. Edge protection is not required on the sides of ramp landings having a vertical dropoff of not 2002 WISCONSIN ENROLLED COMMERCIAL BUILDING CODE