HomeMy WebLinkAbout2007-Electric (set up/racking system)
e
OSHKOSH
ON THE WATER
Job Address 1075 N WASHBURN ST
CITY OF OSHKOSH
No
127484
ELECTRIC PERMIT - APPLICATION AND RECORD
Owner
LOWES HOME CENTERS INC
Create Date 10/22/2007
Contractor
NEI/ NORTHERN ELECTRICIANS INC
Category 643 - Commercial-Addition/Remodels
Plan
Service
~ew
277 / 480
o Change 0- Temp
. ~!~~
Type 0 Overhead
-----D_~~_~!:.ground _
Volts
Circuits
Luminaires
412
Amps
Switches
Receptacles 365
Appliances
I
i
I
I
i
I
~--
___.1
Use/Nature of [(Lowe's) Wiring foilhe storeset=up7kTosk & racking system---------------------------------------------
Work i
-----------------1
i
I
I
I
I
I
i
i
._______._._.._J
Fees: Valuati~_V'V,(I~~448.00
Issued By: ~
Plan Approval _JO.OO
Permit Fee Paid _...J~~O..Q
Date 10/25/2007
o Permit Voided I
Parcelld # 1621500000
In the performance of this work I agree to perform all work pursuant to rules governing the described construction.
While the City of Oshkosh has no authority to enforce easement restrictions of which it is not a party, if you perform the work
described in this permit application within an easement, the City strongly urges the permit applicant to contact the easement
holder(s) and to secure any necessary approvals before starting such activity.
Signature Date
Agent/Owner
Address
PO BOX 550 ST CROIX FAll WI 54024 - 550
Telephone Number (715) 483-3854_
To schedule inspections please call the Inspection Request line at 236-5128 noting the Address, Permit Number, Type of
Inspection (i.e. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue if the inspection is not performed within two business days from the time the project is ready.
City of Oshkosh
Division of Inspection Services
P.O. Box 1130
Oshkosh, VVI54903-1130
Phone (920) 236-5050
Fax (920) 236-5084
~
OF . OfHKOfH
COtv'lMUNITV DEVELOPMENT
E LE CTRICAL PE RMJ3ttA;t;tPi~re'ACf:f(:)NISION
All information after bold categories must be provided.
Incomplete applications will not be processed.
OCT 24 2007
ON THE WATER
· Application(s) and fee(s) can be brought to City Hall, Room 205 or mailed to Inspection Services, PO Box 1128,
Oshkosh WI 54903-1128. Commencing work without permit(s) will result in fees being doubled or $100.00 plus the
normal permit fee, which ever is greater.
OR
If you are a contractor varticivating in the Permit Fee Account System and have adequate funds. check here
if yOU want this vrocessed through your account D
JOB ADDRESS 107 S ;./. lPC4.-;"b<Jr;'\
OWNER Lt!XAe.s <S~
CONTRACTOR NE:t . 'o'~e.rA i:fee:J./'It"c..ftJ.^' ~"" 7/1) - ~3 - 3i"5"'(
P.o. b SSOJ f::fJ5' ~1~ ~~k~ ~~. (h~Je' f;,,{{~ ;<.UI. S'f02.'+
CHECK 0 ALL APPLICABLE
DATE
OS/' kosi....) WI
lolu.. /07
I I
S tf'i'oy
USE CATEGORY
DSingle Family
DDuplex
DMulti-Family
DRental ~mmercial Dlndustrial
TYPE OOverhead ~ot Applicable
DUnderground
SERVICE ONew
OChange
o Temporary
~ot Applicable
FILL IN THE APPROPRIATE BLANK WITH THE NUMBER
Volts
Phase
Amps
~77;
3i$ /
,/-fj),;
~
Receptacles #
Switches #
3bS
J
Circuits #
Fixtures #
4-IL
CHECK 0 ALL APPLICABLE
ORange
OFan OR Blower
DMotors
ODishwasher
OFumace
DGas Pumps
OGarbage Disposal
~er ~-k~ ~f- DBpC Sign
S-k>~ <;~ Of
o Dryer
OWater Heater
DESCRIPTION OF ALL WORK BEING DONE
t><2rJV\;f -J;e- fflV\Cu~1 15J3~
eo
VALUE (Including labor and all materials including light fixtures) $ 9<1 if'! <6' -
MASTER ELECTRICIAN j()~A. M. ~~ # /7::<ocr2-
,va A('-~r" EloeJ-^~~o..4I\.~ :IA...c.. # /D!;/'12L
3/02
Electric Permit Work Card
Job Address 1075 N WASHBURN ST Permit Number 127484
Create Date 10/22/2007
Owner LOWES HOME CENTERS INC
Service b New 0 Change 0 Temp . NIA
Volts 277 I 480 Circuits
Amps
Contractor NEil NORTHERN ELECTRICIANS INC
I Type 0 Overhead 0 Underground . NIA
Luminaires 412
Value
$99,448.00
Use/Nature
of Work
Switches Receptacles 365
643 - Commercial-Addition/Remodels (Lowe's) Wiring for the store set-up / kiosk & racking system
Inspections:
Date 10/25/2007 Type Rough In Inspector Kevin Benner not approved
Ext 5050 / Wants to know if you want to come and check their work. Work is about half done. Electrians were not on site at the time of
inspection.
DatelTime requested: 10/25/2007 07:45 AM
Access:
Requested by: NEI/ NORTHERN ELECTRICIANS INC - C
o Reinspect Fee 0 Fee Wavied D Reinspect Fee Paid
Notice Type:
Ready DatelTime: 10/25/2007 07:45 AM
Phone Number: 715-553-0410
Date 10/29/2007 Type Rough In Inspector Kevin Benner not approved
RevieWed the violations with Craig & Mitch & I also emailed the violations with the code sections to Mitch Davis: Work Space for OCPD's @
he buss duct, EMT drops need support for the raceways every 10', Luminaire I Fixture displays require the boxes toinstalled flush with the
Inish surface. (mitcheldavis@earthling.net)
DatelTime requested: 10/25/2007 01:24 PM
Access: Call when on site or have him paged
Requested by: Northern Electricians Inc.
Notice Type:
Ready Date/Time: 10/29/200701:24 PM
Phone Number: 715-553-0410 Craig
o Reinspect Fee 0 Fee Wavied
D Reinspect Fee Paid
Date 11/08/2007 Type Final Inspector Kevin Benner approved w/cond.
EXT 50481 Cont. Sales - J-Box accessibility, Window Sales- fix light that was hit by fork lift, Track Lt Display- MC cable fittings not
properly installed in the boxes. 11/8/7 1 :32 PM, Craig from NEI called & stated the above noted vio.'s have been correted. The Electrical
:Contractor portion of the installation is approved with the conditions that the vio.'s have been corrected. Track Light Display is not correct
but is the responsibility of the manufacture not the E.C. Faxed to LOWES 11/8/7232-7424
DatelTime requested: 11/07/2007 10:30 AM
Access:
Requested by: NEil NORTHERN ELECTRICIANS INC
o Reinspect Fee 0 Fee Wavied D Reinspect Fee Paid
Notice Type:
Ready DatelTime: 11/08/2007: PM
Phone Number: Craig 715-553-0410
Date 11/08/2007
Type Note
Inspector Kevin Benner
The Track Light Display is not correct but this the responsibility of the manufacture not the E.C. This is being addressed with Mitch Davis of
he merchandising installer. UL Reg. #962, 26UC
DatelTime requested: 11108/2007 01 :42 PM
Access:
Requested by:
o Reinspect Fee 0 Fee Wavied
Notice Type:
Ready DatelTime: 11/08/2007 01 :42 PM
Phone Number:
D Reinspect Fee Paid
Lowes 10/29/07 AM Inspection
Page 1 of3
Benner, Kevin
From: Benner, Kevin
Sent: Monday, November 12, 200710:41 AM
To: 'Mitch Davis'; Benner, Kevin
Cc: Denny.F.Bauguss@Lowes.com; 'Brett Cothren'; James.j.Cline@Lowes.com
Subject: RE: Lowes 10/29/07 AM Inspection
Hi Mitch,
Attached is Comm 16 for your viewing pleasure.
This AM I was on site for the Emergency Generator & Illumination Test. The G.C. was on site & he stated that they had
the same issue in Wauwatosa. I am not sure what the correction was for that store, but I assume that the same could be
done here also.
Thanks for your assistance in correcting this issue.
Best Regards,
Kevin Benner
City of Oshkosh
Electrical Inspector
920-236-5046
http://nxt.legis.state.wi.us/nxtlqateway.dll?f=templates&fn=default.htm&vid=WI : Default&d=code&jd=ch. %20Comm %20 16
-----Original Message-----
From: Mitch Davis [mailto:MitcheIDavis@earthlink.net]
Sent: Friday, November 09,20076:35 AM
To: kbenner@ci.oshkosh.wi.us
Cc: Denny.F.Bauguss@Lowes.com; 'Brett Cothren'; James.j.Cline@Lowes.com
Subject: RE: Lowes 10/29/07 AM Inspection
Hear is the pictures you asked for. I could not get one that you could read the UL tag clearly. The tag stated the
following
Elite Displays
26UC
For Commercial Use Only
120 V 10 Max
You may notice I have copied a couple on this email. Thy are my contacts for getting this resolved. James Cline
from the Lowe's Office will probably be contacting you today (Friday 11/9) to make sure where we go from hear.
I will be on sight today threw about lunch time. After that I will be moving on to the next project.
Where can I download "COM 80" so we can better avoid future problems?
Thank You.
11/20/2007
Lowes 10/29/07 AM Inspection
Page 2 of3
Mitch Davis
Mi!~t!s;l1Qgyj~_@~QIthliOKnE:2t
From: Mitch Davis [mailto:MitcheIDavis@earthlink.net]
Sent: Wednesday, November 07,20075:55 PM
To: Denny.F.Bauguss@Lowes.com; 'Brett Cothren'
Subject: FW: Lowes 10/29/07 AM Inspection
Mitch Davis
MitcheIDavi~@E:2grthlink. net
From: Benner, Kevin [mailto:kbenner@ci.oshkosh.wi.us]
Sent: Wednesday, November 07, 2007 10:27 AM
To: 'Mitch Davis'
Subject: RE: Lowes 10/29/07 AM Inspection
Hi Mitch,
Sorry for the delay in my response, the dynamics of my week have been interesting to say the least.
# 1 Kyle form Thomas Electric has called me in reference to this. I am not positive as to all of their solutions, but I
think he understood the concept.
#2 This installation will be interesting. The NEC code reference for your installation based on your response would
be 110.3(b). The State of Wisconsin reference to this installation would be Comm. 16.18 which states as follows:
"Substitute the following wording for NEC 11 0.3(B): Listed or Labeled equipment shall be installed or used, or both,
in accordance with any listing or labeling, provided the instructions, listing or labeling do not conflict with this
chapter". The words "this chapter" means the state codes and the codes in the NEC which is adopted by the State
of WI through Comm 16. Which means that the listing is fine great, but the installation must still comply with the
state and national codes.
#3 It is appropriate to install uni-strut for the required EMT support per NEC 358.30(A)
Regards,
Kevin Benner
City of Oshkosh
Electrical Inspector
920-236-5046
-----Original Message-----
From: Mitch Davis [mailto:MitcheIDavis@earthlink.net]
Sent: Thursday, November 01, 20077:18 PM
To: 'Benner, Kevin'
Subject: RE: Lowes 10/29/07 AM Inspection
Thank You for the curtsy inspection you did last Monday. I just wonted to
touch base with you on what is in process on these items to be sure they met
with your approval.
11/20/2007
Lowes 10/29/07 AM Inspection
Page 3 0[3
#1 Bus Duct location- The onsite project manager for Lowe's has forwarded
this back to the building GC for handling as this work was done on his
contract.
#2 Display, fixture wire wall penetration - In discussing this with the
manufacture he pointed out to us that the display as a hole has a UL label
and was manufactured under UL Reg # 962. After talking with him he told me
the UL tag was on the front of the display and I then found the tag as he
stated. This display has tag # 26UC on it.
#3 Raceway support - We plan to take a piece of un-a-strut and attach it to
the rack upright and run it up 2'-4' then attach the EMT to it. The current
distance from the top of the rack to the bottom of the ceiling is 12' 5".
Please let me know if you feel this will take care of items 2 and 3.
Thank You
Mitch Davis
Mitchel Davis@earthlink.net
From: Benner, Kevin [mailto:kbenner@ci.oshkosh.wLus]
Sent: Monday, October 29, 20073:09 PM
To: 'mitcheldavis@earthlink.net'
Subject: Lowes 10/29/07 AM Inspection
Greetings Mitch,
I wanted to follow-up with you for clarification of this mornings inspection. The following is the code sections
to the violations that we discussed:
#1 Buss Duct electrical panel "Work Space" requirements: NEC 11 0.26(A)(1)
#2 Electrical box installation for the Fixture / Luminaire Display that is mounted on slat-board: NEC 314.20
#3 Raceway support for the EMT drops to the racking: NEC 358.30
Any questions or concerns please feel free to contact me.
Kevin Benner
City of Oshkosh
Electrical Inspector
920-236-5046
11/20/2007