HomeMy WebLinkAbout13242-Electrical maintenance
o
OSHKOSH
ON THE WATER
Issue Date 10/17/2007
INSPECTION SERVICES DIVISION ROOM 205
DEPARTMENT OF COMMUNITY DEVELOPMENT
CORRECTION NOTICE
CITY OF OSHKOSH
215 CHURCH AVE
PO Box 1130
OSHKOSH WI 54903-1130
Compliance Date 11/16/2007
Compliance No
Address
227 MASON ST
Sent to
~ Owner
Name
I DANIEL H GEFFERS
Address
227 MASON ST
City
OSHKOSH
State Zip Code
WI 54902 -5638
Introduction
U Required for Occupancy Occupancy
While conducting the service inspection it was noted that code violations are present on your property. The wiring to the
urnace is noncomliant. Please contact an electrician to make corrections.
Item # Code NEC 314.17(A) Compliance NO Compliance Date 11/16/2007
Description Openings through which conductors enter shall be effectively closed. A knockout is open (thermostat wires exit it) in the hand i-box at the
urnace.
10/17/2007
Last
Updated
13242
Page 1 of 2
e
OSHKOSH
ON THE WATER
Issue Date 10/17/2007
Address 227 MASON ST
INSPECTION SERVICES DIVISION ROOM 205
DEPARTMENT OF COMMUNITY DEVELOPMENT
CORRECTION NOTICE
CITY OF OSHKOSH
215 CHURCH AVE
PO Box 1130
OSHKOSH WI 54903-1130
Compliance Date 11/16/2007
Compliance No
Sent to
l!J Owner
Name
DANIEL H GEFFERS
Address
227 MASON ST
City
OSHKOSH
State Zip Code
WI 54902 -5638
Introduction
, hile conducting the service inspection it was noted that code violations are present on your property. The wiring to the
'furnace is noncomliant. Please contact an electrician to make corrections.
U Required for Occupancy
Occupancy
Item # 2 Code NEC 725.26(B) Compliance No Compliance Date 11/16/2007
Description pables and conductors of Class 2 and Class 3 circuits shall not be placed in any cable, cable tray, compartment, enclosure, manhole, outlet
ibox, device box, raceway, or similar fitting with conductors of electric light, power - thermostat wires in conduitwith 120 volt conductors.
10/17/2007
Last
Updated
Summary Please make arrangements to have these violations corrected in the next 30 days. Feel free to contact me with any concerns
or questions at 236-5274.
Violations must be corrected and approved within 30 days unless otherwise noted. Call for reinspections prior to concealment
and/or occupancy. Upon completing the corrections, the owner/contractor/agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 11/16/2007
Office hours for obtaining permits are Monday through Friday 7:30-8:30 a.m. and 12:30-1 :30 p.m. or by appointment. To schedule
inspections please call the Inspection Request line at 236-5128 noting the address, permit number (when applicable), and the
nature of wha,~ nee~ to tc;ected.
Signature lHl# ~ ,~.. Date liZ/7oll}
../
Inspected by: Adam Krause 236-5274 akrause@ci.oshkosh.wi.us
I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes.
Print Name
Company
Signature
Date
Also Sent to: U Bldg I
U Elec I
U HVAC I
U Plbg I
U Designer I
U Other I
U Inspector I
13242