HomeMy WebLinkAboutPlumbing ZZ2-271-0907-P (Phase 2)
~
OJHKOJH
City of Oshkosh
Inspection Services
215 Church Ave., PO Box 1130
Oshkosh, WI 54902-1130
(920) 236-5052 (920) 236-5184 FAX
ON THE WATER
October 18,2007
J. T. Schmidt Plumbing Inc.
419 S. Washington St.
Combined Locks, WI 54113
Ref: Plumbing Plan Approval:
Comfort Suites (Phase II water distribution)
400 S Koeller St. Oshkosh, WI
Plan ID# ZZ2-271-0907-P
Dear Sirs,
Examination of the plumbing plans and specifications for this project has been completed. In accord
with Chapter 145, Wisconsin Statute, and COMM 81 through 85, Wisconsin Administrative Code, the
plumbing plans and specifications are approved contingent upon compliance with the stipulation(s)
noted below.
1. Hot water distribution branch lines shall not exceed 25 feet developed length from circulated
temperature maintenance system per COMM 82.40
2. Hotwater distribution system circulated for temperature maintenance shall be insulated for
thermal loss protection per COMM 82.40
3. Pressure boost system for water distribution shall be provided a low pressure cut off per
COMM 82.40(7)
4. Emergency eye wash supply shall provide minimum gallon per minute flow required by
manufacturer to meet OSHA requirements based on water calculation.
5. Point of use backflow protection required for mix systems directly connected to the
distribution system per COMM 82.41
6. Corzan distribution pipe system meeting ASTM standard 441 shalf be limited to cold water
distribution only in pipe size 3" diameter and above per Alternate Approval dated 8/16/06.
7. Installation shall include thermal expansion compensation per manufacturer requirements.
In the event installation of this plumbing system has not commenced within two years from this date, this
approval shall become void. A new application accompanied by full examination fees shall be filed and
an updated approval received before work may commence.
In granting this approval, the City of Oshkosh or its representative does not hold itself liable for any
defects in plans or specifications, plan omissions, examination oversight, construction or any damage
that may result in or after installation. The City of Oshkosh reserves the right to order changes or
additions should conditions arise making this necessary. It shall be necessary for the installing plumber
to obtain a plumbing permit from the City of Oshkosh before proceeding with actual installation of this
plumbing system or any of its parts.
Respectfu lIy,
Richard Wood,
Plumbing Inspector