HomeMy WebLinkAbout2007- Electric (low voltage)
e
OSHKOSH
ON THE WATER
Job Address 1075 N WASHBURN ST
CITY OF OSHKOSH
No
126997
ELECTRIC PERMIT - APPLICATION AND RECORD
Owner
LOWES HOME CENTERS INC
Create Date 09/28/2007
Contractor
TOWN & COUNTRY ELECTRIC
Category 643 - Commercial-Addition/Remodels
Service
b New
o Change 0 Temp
. N/A
Type 0 Overhead
Plan
o Underground
Volts
Circuits
Luminaires
Amps
Switches
Receptacles
Appliances
Use/Nature of COMM / LOW VOLTAGE WIRING TO INCLUDE FIRE ALARM, SECURITY SYSTEM CONDUIT AND CABLING **check #814208
Work
Fees: valua~
Issued By: 0
$33,100.00
Plan Approval
$0.00
Permit Fee Paid
$315.00
Date 09/28/2007
o Permit Voided I
Parcelld # 1621500000
In the performance of this work I agree to perform all work pursuant to rules governing the described construction.
While the City of Oshkosh has no authority to enforce easement restrictions of which it is not a party, if you perform the work
described in this permit application within an easement, the City strongly urges the permit applicant to contact the easement
holder(s) and to secure any necessary approvals before starting such activity.
Signature Date
AgenUOwner
Address
PO BOX 627
APPLETON WI 54912 - 627
Telephone Number (920) 225-6507
To schedule inspections please call the Inspection Request line at 236-5128 noting the Address, Permit Number, Type of
Inspection (i.e. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue if the inspection is not performed within two business days from the time the project is ready.
~31S .00
City of Oshkosh
Division ofInspection Services
P.O. Box 1130
Oshkosh, WI 54903-1130
Phone (920) 236-5050
Fax (920)236-5084
I
~..Ilr.'...'..,.,..,.....\....:.......,"..::.....'..........
.
OfHKOfH
SEP 2 7 2007
. _....i;l.EPJ\B..TMENT Of
ELECTRICAL PE~iAHe~i'fR!Jl;t
All information after bohl~ fiiUSw~~~I~Ja~
Incomplete applications will not be processed.
ON THe: WATe:R
. Application(s) and fee(s) can be brought to City Hall, Room 205 or mailed to fuspection Services, PO Box 1128,
Oshkosh WI 54903-1128. Commencing work without permit(s) will result in fees being doubled or $100.00 plus the
normal permit fee, which ever is greater.
OR
If yOU are a contractorparticipatinf!: in the Permit Fee Account System and have adequate funds. check here
if vou 'Want this processed through your account 0
DATE 9-25-07
JOBADDRESS 10'75" N. WdShbuen St,
OWNER LOWES
CONTRACTOR Faith -rechno/~ies J Tnt..
CHECK 0 ALL APPLICABLE
USE CATEGORY
DSingle Family
DDuplex
OMulti-Farnily
o Rental
~Commercial DIndustrial
o Overhead ONot Applicable
OUnderground'
SERVICE ONew
o Change
o Temporary
ONot Applicable
TYPE
FILL IN THE APPROPRIATE BLANK WITH THE NUMBER
I
Receptacles #
Circuits #
Volts .
Phase
Amps
Switches #
Fixtures #
CHECK 0 ALL APPLICABLE
ORange
OFan OR Blower
DMotors
ODishwasher
OFurnace
DGas Pumps
OGarbage Disposal
ONe
o Other
ODryer OWater Heater
OElectric Sign
DESCRIPTION OF ALL WORK BEING DONE Fi~e AJaem and Secue;t:~
5ystem conduit and Cdbl/~~
VALUE (Including labor and all materials including light fixtures) $ 33.. 100.00
MASTER ELECTRICIAN ~rui a.~)~. }1Vf.
3/02
Electric Permit Work Card
Job Address 1075 N WASHBURN ST Permit Number 126997
.
Create Date 9/28/2007
Owner LOWES HOME CENTERS INC
Service b New 0 ChangeO Temp . N/A
Volts
Amps
Circuits
Switches
Contractor TOWN & COUNTRY ELECTRIC
I Type 0 Overhead 0 Underground . N/A
Luminaires
Value
$33,100.00
Receptacles
Use/Nature 643 - Commercial-Addition/Remodels COMM / LOW VOLTAGE WIRING TO INCLUDE FIRE ALARM, SECURITY
of Work SYSTEM CONDUIT AND CABLING **check #814208
Inspections:
Date 10/09/2007 Type Rough In Inspector Kevin Benner not approved
Reviewed with Steve & Jason of Thomas Electric who was to review with the G.C. who would forward the notice to the appropriate
~ontractors.
DatelTime requested: 10/09/2007 00:00 AM
Access:
Requested by:
o Reinspect Fee 0 Fee Wavied
Notice Type: FC Ready DatelTime: 10/09/200700:00 AM
Phone Number:
o Reinspect Fee Paid
Date 11/14/2007 Type Final Inspector Kevin Benner not approved
Reviewed with Tyler. Data Rm: insulator & effectively close a 2" EMT conntector used as a cable conn., connector required for a 12V Pwr
supply cable. Elec. Rm.: Bond FACP doors, k.o. plug, NFPA 72 10 req.'s, fix the breaker in the "on" position & 10 red.
DatelTime requested: 11/14/2007 00:00 AM
Access:
Requested by: G.C. Scott Eigner
o Reinspect Fee 0 Fee Wavied
Notice Type:
Ready DatelTime: 11/14/2007 12:30 PM
Phone Number: 608-215-2675 Scott Eigner
o Reinspect Fee Paid
Date 11/16/2007 Type Re Final Inspector Kevin Benner approved w/cond.
Field Request The 2" raceway in the Data Room is to be corrected. The G.C. stated that this will be done in the PM 11/16/7. 11/16/7 1:28
PM Tyler Zerbo called and stated the violations have been corrected.
DatelTime requested: 11/15/2007 08:16 AM
Access:
Notice Type:
Ready DatelTime: 11/15/2007 08: 16 AM
Requested by: TOWN & COUNTRY ELECTRIC Tyler
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Phone Number: