HomeMy WebLinkAboutHVAC Z2-2042-0807-H
J
~
OJHKOfH
. ., City of Oshkosh
. Division ofInspection Services'
215 Church Avenue.
PO Boxlf30
Oshkosh WI 54903-1130
www.ci.oshkosh.wLus
ON THE WATER
September 27, 2007
William R Hagerty
Auer Steel and Heating Supply Company
785CountyRd CB
Neenah, WI 54956
Randy Schmiedel
Bros LLC
222 Ohio Street
Oshkosh, WI 54902
Site: Plan Number: Z2-2042-0807-H
Anytime Fitness
312 Koeller St
Oshkosh WI 54901
For:
Description: Tenant space alterations
Object Type: HV AC only
Class of Construction: lIB - 4820 Sq Ft.; Unsprinklered
Occupancy: A3: Assembly
other occupancies in same building - B: Business Office, M Mercantile / Retail - Separated Uses
Maximum No of Occupants: 80 .
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Hem(s) / Conditions:
· Note: EF2 shown in equipment schedule was not identified on plan. This fan is to be located in janitors
closet that has been relocated per the attached revised floor plan and identified as JAN 111.
· IMC 405.1 Mechanical ventilation systems shall be provided with manual or automatic controls that will
operate such systems whenever the spaces are occupied. Air conditioning systems that supply required
ventilation air shall be provided with controls designed to automatically maintain the required outdoor air
supply rate during occupancy. Verify that exhaust and Make-up air is being controlled to provide the
required air change rate whenever the building is occupied. The general notes include conflicting
control specifications i.e. occupancy switched on exhaust fans, VS. interlock with make-up air.
· Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted'
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Corom 61.31(1).
I:',!n::ipe"tiui');;\Phn Review\O\I1lIWon:ial Pi:m R",vit'\\' 20D7\Z2-2D42-0807-H .3 i 2 Kudlt'f $., JIVAC Only.de".'
Page 1 of2
SUBMIT:
· Comm 61.50 (4) Supervision. Prior to the initial oc'cupancy of an alteration the supervising professional
.shall file a compliance statement form SBD-9720 with.this office.
· IECC 503.3.3.7 [Comm 63.0503(2)(1)] Balancing and documentation of the HV AC system shall conform
to the IMC. Balancing report required to be submitted prior to final occupancy being allowed.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
~
~~
Building Systems Consultant
(920) 236-5051 Monday- Friday 7:30 AM. to 8:30 AMand 12:30 AM to 1:30 P.M.
bnoe@ci.oshkosh.wi.us
cc: Property file
Fee Required $
Fee Received $
Balance Due $
300.00
300.00
0.00
I:\Insped)uj]s\Plal1 I(<:vi<:w\('omm<:n:ial Pian Rev!<:w :!.OOTZ2-2042/)807-H .1! 2; KoeUer St nVAC On!y.doc
Page 2 of2