HomeMy WebLinkAboutLetter-Ahern (Fire Protection System Installation)
J. F. AHERN CO.
MECHANICAL & FIRE
PROTECTION CONTRACTORS
201 Morris Court, P.O. Box 1316
Fond du Lac, WI 54936-1316
(920) 921-9020 p. (920) 921-8666 f
www.jfahern.com
September 12, 2007
Building Inspector -- Brian N oe
City of Oshkosh
215 Church Avenue -- PO Box 1130
Oshkosh, VVI 54901
T -920/236-5051
F-920/236-1130
RE: FIRE PROTECTION SYSTEM INST ALLA TION
HUNTERS RIDGE CONDOMINIUMS BUILDING #9
3190 WHITE TAIL LANE
OSHKOSH, WISCONSIN 54904
AHERN FIRE PROTECTION PROJECT No. 995253
Dear Brian:
RE
IV
SEP 1 3 2007
DEPARTMENT OF
COMMUNITY DEVELOPMENT
INSPECTION SERVICES DIVISION
Enclosed is a copy of the Contractor's Material and Test Certificates covering the above-referenced
Fire Protection System Installation for your files.
Very truly yours,
AHERN FIRE PROTECTION
A division of J. F. Ahem Co.
~!R$~
Mark L. Jozefowski, Superintendent
MLJlksj
Enclosure
LCITY09-12-2007.DOC2
Building the Midwest Since 1880
An Equal Opportunity Employer
AHERN FIRE PROTECTION
Contractor's Material and Test Certificate for Aboveground Piping
PROCEDURE
Upon completion of work, inspection and tests shall be made by the contractor's representative and witnessed by an owner's representative. . All defects shall be
corrected and system left in service before contractor's personnel finally leave the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and contractor. It is understood the
owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving
authoritv's requirements or local ordinances.
PROPERTY NAME Hunters Ridge Condominiums AFP W.O. #: 995253 I DATE: April 3, 2007
PROPERTY ADDRESS 3190 White Tail Lane ~~~I J:~MA m,.. .
ACCEPTED BY APPROVING AUTHORITIES (NAMES) . n I: I V~
1. Oshkosh Fire Department (Battalion Chief -- Stu Schrottky) .,:, "
2. City of Oshkosh (Building Inspector -- Brian Noe) SEP I 3 2007
3.
4. ,..."'. DEPARTMENT OF
ADDRESS -V"W'UI'o!l I r UcVELOPMENT
Plans 1. 101 Court Street - Oshkosh, WI 54901 INSPECTION SERVICES DIVISIOri
2. 215 Church Avenue -- PO Box 1130 -- Oshkosh, WI 54901
3.
4. .
INSTALLATION CONFORMS TO ACCEPTED PLANS i;ES DNO
EQUIPMENT USED IS APPROVED YES DNO
IF NO, EXPLAIN DEVIATIONS
t "
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION {S[ YES DNO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT?
INSTRUCTIONS IF NO, EXPLAIN
HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES:
Item No.'s 2& 3 will 1. SYSTEM COMPONENTS INSTRUCTION YES DNO
be folWarded by AFP
at closeout time. 2. CARE AND MAINTENANCE INSTRUCTIONS ~~S DNO
3. NFPA 25 ES DNO
LOCATION OF SUPPLIES BUILDINGS
SYSTEM Building #9
MAKE MODEL YEAR OF K- QUANTITY TEMPERATURE
MANUFACTURE FACTOR RATING
Central LFII TY2234 Pendent 1/2" White 2007 4.9 54 155 Dea,
SPRINKLERS
PIPE AND TYPE OF PIPE CPVC
FITTINGS TYPE OF FITTINGS CPVC
FLOW ALARM DEVICE MAXIMUM TIME TO OPERATE
THROUGH TEST CONNECTION .
TYPE MAKE MODEL MIN. SEC.
Water Flow Detector System Sensor WFD 7_'1
N/A
EXPLAIN ANY ALARM PROBLEMS:
ALARM
DEVICES . LOW AIR ALARM DEVICE ALARM OPERATED
~E I MAKE MODEL PRESSURE PROPERLY
l N/A) SETTING PSI I
YES NO
-- I
EXPLAIN ANY ALARM PROBLEMS;
Ahern Fire Protection
CENTRAL MONITORING SIGNALS RECEIVED
ALARM SERVICE LOCATION(S)
TYPE OR PRESSURE
NAME OF REMOTE WATERFLOW SWITCH LOW-AIR OTHER
SERVICE DETECTOR FLOW SUPERVISORY
SUPERVISING LOCATION(S):
STATION
(ON-SITE)
REMOTE REMOTE NAME OF SERVICE:
MONITORING
ALARM SERVICE
SIGNALING (OFF-SITE)
PHONE:
~V~ OTHER: LOCATION(S):
EXPLAIN ANY ALARM SIGNALING PROBLEMS:
DRY VALVE Q.O.D.
MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO.
~'V: TIME WATER ALARM
TIME TO TRIP WATER TRIP POINT AIR
THROUGH TEST AIR PRESSURE REACHED TEST OPERATED
CONNECTION,,2 PRESSURE PRESSURE OUTLET '.2 PROPERLY
DRY PIPE MIN. SEC. PSI PSI PSI MIN. SEC. YES NO
OPERATING WITHOUT
TEST Q.O.O.
WITH
Q.O.o.
IF NO, EXPLAIN:
~~ OPERATION: o PNEUMATIC 0 ELECTRIC o HYDRAULIC .
PIPING SUPERVISED DYES ONO DETECTING MEDIA SUPERVISED DYES ONO
DOES VALVE OPERATE FROM THE MANUAL TRIP, REMOTE, OR BOTH CONTROL STATIONS DYES ONO
IS THERE AN ACCESSIBLE FACILITY IN EACH IF NO, EXPLAIN
DELUGE & CIRCUIT FOR TESTING
PREACTION DYES ONO
VALVES
DOES EACH CIRCUIT DOES EACH CIRCUIT MAXIMUM TIME TO
OPERATE SUPERVISION OPERATE VALVE RELEASE OPERATE RELEASE
MAKE MODEL LOSS ALARM
YES NO YES NO MIN. SEC.
~\' LOCATION & MAKE & MODEL SETTING STATIC PRESSURE RESIDUAL PRESSURE FLOW RATE
FLOOR (FLOWING)
PRESSURE " INLET OUTLET INLET OUTLET FLOW
REDUCING
VALVE TEST " (PSI) (PSI) (PSI) (PSI) (GPM)
1 MEASURED FROM TIME INSPECTORS TEST CONNECTlbN IS OPENED.
2 NFPA 13 ONLY REQUIRES THE 60-SECONO LIMITATION IN SPECIFIC SECTIONS.
2
TEST
DESCRIPTION
TESTS
BLANK
TESTING
GASKETS
WELDING
CUTOUTS
(DISCS)
HYDRAULIC
DATA
NAMEPLATE
REMARKS
Ahern Fire Protection
ROSTA TIC' Hydrostatic tests shall be made at not less than 200 psi (13.6 bars) for two hours or 50 psi (3.4 bars) above static pressure in
excess 0 .150 psi (10.2 bars) for two hours. Differential dry-pipe valve clappers shall be left open during test to prevent damage. All
aboveground piping leakage shall be stopped.
PNEUMATIC: Establish 40-psi (2.7 bars) air pressure and measure drop, which shall not exceed 1-1/2 psi (0.1 bars) in 24 hours. Test
pressure tanks at normal water level and air pressure and measure air pressure drop, which shall not exceed 1-1/2 pSi (0.1 bars) in 24 hours.
ALLPIPING HYDROSTATICALLY TESTED AT PSI '-Bar) for_ HRS. IF NO, STATE REASON
DRY PIPING PNEUMATICALLY TESTED &/'/\ 0 YES 0 NO
EQUIPMENT OPERATES PROPERLY ,..l" 0 YES 0 NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM
SILICATE OR DERIVATIVES OR SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT USED
~9R TESTING SYSTEMS OR STOPPING LEAKS?
BI YES 0 NO
DRAIN READING OF GAUGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST
TEST SUPPLY TEST CONNECTION~ PSI ( Bar) CONNECTION OPEN WIDE: '::IS- PSI LBar)
UNDERGROUND MAINS AND LEAD IN CONNECTIONS TO SYSTEM RISER OTHER EXPLAIN
FLUSHED BEFORE CONNECTION MADE TO SPRINKLER PIPING.
VERIFIED BY COpy OF THE CONTRACTOR'S MATERIAL AND TEST ~
CERTIFICATE FOR UNDERGROUND PIPING. 0 YES 0 NO
FLUSHED BY INSTALLER OF UNDERGROUND SPRINKLER PIPING 0(YES 0 NO
IF POWDER-DRIVEN FASTENERS ARE USED IN CONCRETE, HAS
REPRESENTATIVE SAMPLE TESTING BEEN SATISFACTORILY COMPLETED?
N~ OYESO NO
NUMB~USED LOCATIONS
WELDED PIPING 0 YES NO
IF NO, EXPLAIN
NUMBER REMOVED
IF YES...
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING
PROCEDURES COMPLY WITH THE REQUIREMENTS OF AT LEAST AWS B2.1?
DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS 0 YES
QUALIFIED IN COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST AWS 82.1?
DYES
ONO
ONO
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A
DOCUMENTED QUALITY CONTROL PROCEDURE TO ENSURE THAT ALL DISCS
ARE RETRIEVED, THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAG AND
OTHER WELDING RESIDUE ARE REMOVED, AND THAT THE INTERNAL
DIAMETERS OF PIPING ARE NOT PENETRATED?
DYES
ONO
DO YOU CERTIFY THAT YOU HAVE A CON
CUTOUTS (DISCS) ARE RETRIEVED?
NAME PLA1E.,PROVIDED
aYES 0 NO
ROL FEATURE TO ENSURE THAT ALL
DYES 0 NO
IF NO, EXPLAIN
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN:
NAME OF SPRINKLER CONTRACTOR
AHERN FIRE PROTECTION, 201 MORRIS COURT':" FOND DU LAC, WI 54935
TESTS WITNESSED BY
ISDICTlON (SIGNED)
>:./;HL, /I Flit €..
GNED)
;.....-) -01
~THQ..RITJES
SIGNATURES ~~
FOR PROPERTY OWNE
t::!tl 8
TITLE
DATE
q-tl~6
DATE
DATJ=
'1'-'f/~