Loading...
HomeMy WebLinkAboutLetter-Witzke Electric (Added electrical load) 'kJ~ Ciecbue, JH,C. Residential, Industrial and Commercial Installations 155 E. Packer Avenue Post Office Box 102 Oshkosh, Wisconsin 54903-0102 Phone (920) 235-6572 FAX (920) 235-6582 Monday, January 08,2007 City of Oshkosh Attention: Kevin Benner Division of Inspection PO Box 1130 Oshkosh, VV154903-1130 Telephone (920) 236-5050 Fax 236-5084 Re: Boy's & Girl's Club Of Oshkosh Inc. 501 East Parkway Ave. The following are calculations requested for supporting the added electrical load on the existing electrical service at the Boy's & Girl's Club. Please call and let me know if this is what you are looking for. Present service is rated at 800 amp 120/208 volt 3 phase 4 wire. Highest demand on the service per VVPS was 111.2 KW in August of 2006. Existing Demand 111.2 KW x 1,000 = 111,200 Watts 111,200 Watts + 360 (208 volt x 1.73) = 308.89 Amps Existing demand @ 125%, Section 220.35 2 New Air Conditioners @ 71.6 Amps Each General Lighting by Occupancy, Table 220.3 (A) 14,670 Sq, Ft. @ 2 Watts = 29,340 29,340 + 360 = 81.5 Amps Total Load Respectfully Submitted, --~~---~ Tim Olk _IVISA] 386 Amps 143 82 611 Amps Rt E.' [1 ,....;. E IVE D JAN 0 9 2007 DEPARTMENT OF COMMUNITY DEVELOPMENT