September 4, 2007
Building Inspector -- Brian Noe
City of Oshkosh
215 Church Avenue -- PO Box 1130
Oshkosh, WI 54901
T -920/236-5051
F-920/236-1130
RE: FIRE PROTECTION SYSTEM INSTALLATION
WYLDEWOOD CONDOS - BUILDING 9
376 WYLDEWOOD
OSHKOSH, WISCONSIN 54901
AHERN FIRE PROTECTION PROJECT No. 995644
Dear Brian:
Enclosed is a copy of the Contractor's Material and Test Certificates covering the above-referenced
Fire Protection System Installation for your files.
Very truly yours,
AHERN FIRE PROTECTION
A division ofJ. F. Ahem Co.
~fl}.$~
Mark L. Jozefowski, Superintendent
MLJ/ksj
Enclosure
LCITY09-04-2007.DOC
RECEIVED
SEP 5 2007
DEPARTMENT OF
COMMUNITY DEVELOPMENT
INSPECTION SERVICES DIVISION
Building the Midwest Since 1880
An Equal Opportunity Employer
AHERN FIRE PROTECTION
Contractor's Material and Test Certificate for Aboveground Piping
PROCEDURE
Upon completion of work, inspection and tests shall be made by the contractor's representative and witnessed by an owner's representative. All defects shall be
corrected and system left in service before contractor's personnel finally leave the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and contractor. It is understood the
owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving
authority's requirements or local ordinances.
PROPERTY NAME Wyldewood Condominiums AFP W.O. #: 995644 I DATE: June 13,2007
PROPERTY ADDRESS 376 Wyldewood Oshkosh, WI 54901
ACCEPTED BY APPROVING AUTHORITIES (NAMES)
1. City of Oshkosh (Building Inspector -- Brian Noe)
2. Oshkosh Fire Department (Battalion Chief - Stu Schrottky)
3.
4.
ADDRESS
Plans 1. 215 Church Avenue -- Oshkosh, WI 54901
2. 101 Court Street -- Oshkosh, WI 54901
3.
4.
INSTALLATION CONFORMS TO ACCEPTED PLANS ~YES DNO
EQUIPMENT USED IS APPROVED ~ES DNO
IF NO, EXPLAIN DEVIATIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION l8'YES DNO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT?
INSTRUCTIONS IF NO, EXPLAIN
HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES:
Item No.'s 2 & 3 will 1. SYSTEM COMPONENTS INSTRUCTION ~r DNO
be forwarded by AFP 2. CARE AND MAINTENANCE INSTRUCTIONS YES DNO
at closeout time.
3. NFPA 25 ES DNO
LOCATION OF SUPPLIES BUILDINGS
SYSTEM Building #9
MAKE MODEL YEAR OF K- QUANTITY TEMPERATURE
MANUFACTURE FACTOR RATING
CentralLF II TY2234 Res. Pendent White 2007 4.9 59 155 Deq.
SPRINKLERS
PIPE AND TYPE OF PIPE Liahtwal/ Non-Threadable. Thinwall Threadable. Black
FITTINGS TYPE OF FITTINGS Grooved. Threaded. Mechanical Tees
FLOW ALARM DEVICE MAXIMUM TIME TO OPERATE
THROUGH TEST CONNECTION
TYPE MAKE MODEL MIN. SEC.
Water Flow Detector System Sensor WFD t7
N/A
EXPLAIN ANY ALARM PROBLEMS:
ALARM
DEVICES LOW AIR ALARM DEVICE ALARM OPERATED
U'eE MAKE I MODEL PRESSURE PROPERLY
lN/A\ . D It:' '" C'1~1e r , YES I NO
.........." II ""~ ~i 'fI ~. ~ I
EXPLAIN ANY ALARM PROBLEMS: SEP 5 2007
DEPARTMENT OF
, .....,... If- AI"" .... ,.....
-- I .41'......-;... _J~_ ,,11.0..
!NSPECTION SERVICES DIVISION
CENTRAL MONITORING SIGNALS RECEIVED
ALARM SERVICE LOCA TION(S)
TYPE OR PRESSURE
NAME OF REMOTE WATERFLOW SWITCH LOW-AIR OTHER
SERVICE DETECTOR FLOW SUPERVISORY
SUPERVISING LOCATION(S):
~~ STATION
(ON-SITE)
REMOTE REMOTE NAME OF SERVICE:
MONITORING
ALARM SERVICE
SIGNALING (OFF-SITE)
PHONE:
OTHER: LOCA TION(S):
EXPLAIN ANY ALARM SIGNALING PROBLEMS:
DRY VALVE Q.O.D.
MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO.
N~ TIME WATER ALARM
TIME TO TRIP WATER TRIP POINT AIR
THROUGH TEST PRESSURE AIR PRESSURE PRESSURE REACHED TEST OPERATED
CONNECTION',2 OUTLET ',2 PROPERLY
DRY PIPE MIN. SEC. PSI PSI PSI MIN. SEC. YES NO
OPERATING WITHOUT
TEST Q.O.D.
WITH
Q.O.D.
IF NO, EXPLAIN:
.
OPERATION: o PNEUMATIC 0 ELECTRIC o HYDRAULIC
~~ PIPING SUPERVISED DYES DNO DETECTING MEDIA SUPERVISED DYES DNO
DOES VALVE OPERATE FROM THE MANUAL TRIP, REMOTE, OR BOTH CONTROL STATIONS DYES DNO
IS THERE AN ACCESSIBLE FACILITY IN EACH IF NO, EXPLAIN
DELUGE & CIRCUIT FOR TESTING
PREACTION DYES DNO
VALVES
DOES EACH CIRCUIT DOES EACH CIRCUIT MAXIMUM TIME TO
OPERATE SUPERVISION
MAKE MODEL LOSS ALARM OPERATE VALVE RELEASE OPERATE RELEASE
YES NO YES NO MIN. SEC.
~ LOCATION & MAKE & MODEL SETTING STATIC PRESSURE RESIDUAL PRESSURE FLOW RATE
PRES E FLOOR (FLOWING)
. INLET OUTLET INLET OUTLET FLOW
REDUCING (PSI) (PSI) (PSI) (PSI) (GPM)
VALVE TEST
.
Ahern Fire Protection
1 MEASURED FROM TIME INSPECTORS TEST CONNECTION IS OPENED.
2 NFPA 13 ONLY REQUIRES THE SO-SECOND LIMITATION IN SPECIFIC SECTIONS.
2
TEST
DESCRIPTION
TESTS
BLANK
TESTING
GASKETS
WELDING
CUTOUTS
(DISCS)
HYDRAULIC
DATA
NAMEPLATE
REMARKS
SIGNATURES
Ahern Fire Protection
HYDROSTATIC' ydrostatic tests shall be made at not less than 200 psi (13.6 bars) for two hours or 50 psi (3.4 bars) above static pressure in
exces psi (10.2 'bars) for two hours. Differential dry-pipe valve clappers shall be left open during test to prevent damage. All
aboveground piping leakage shall be stopped.
PNEUMATIC: Establish 40-psi (2.7 bars) air pressure and measure drop, which Shall not exceed 1-1/2 psi (0.1 bars) in 24 hours. Test
pressure tanks at normal water level and air pressure and measure air pressure drop, which shall not exceed 1-1/2 psi (0.1 bars) in 24 hours.
ALL PIPING HYDROSTATICALLY TESTED AT PSI (_Bar) for -k HRS. IF NO, STATE REASON
DRY PIPING PNEUMATICALLY TESTED J ,v"\ YES D NO
EQUIPMENT OPERATES PROPERLY fV!"I DYES D NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM
SILICATE OR DERIVATIVES OR SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT USED
eO,.R TESTING SYSTEMS OR STOPPING LEAKS?
QrYES D NO
DRAIN READING OF GAUGE LOCATE2tEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST
TEST SUPPLY TEST CONNECTION: PSI ( Bar) CONNECTION OPEN WIDE: ~ PSI LBar)
UNDERGROUND MAINS AND LEAD IN CONNECTIONS TO SYSTEM RISER OTHER EXPLAIN
FLUSHED BEFORE CONNECTION MADE TO SPRINKLER PIPING.
VERIFIED BY COpy OF THE CONTRACTOR'S MATERIAL AND TEST
CERTIFICATE FOR UNDERGROUND PIPING. ~YES D NO
FLUSHED BY INSTALLER OF UNDERGROUND SPRINKLER PIPING ~ES D NO
IF POWDER-DRIVEN FASTENERS ARE USED IN CONCRETE, HAS IF NO, EXPLAIN
REPRES1lNTATIVE SAMPLE TESTING BEEN SATISFACTORILY COMPLETED?
W~ D~Doo
NUMBER USED LOCATIONS NUMBER REMOVED
o
WELDED PIPING
IF YES...
NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING
PROCEDURES COMPLY WITH THE REQUIREMENTS OF AT LEAST AWS B2.1?
DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS DYES
QUALIFIED IN COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST AWS B2.1?
DYES
DNO
DNO
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A
DOCUMENTED QUALITY CONTROL PROCEDURE TO ENSURE THAT ALL DISCS
ARE RETRIEVED, THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAG AND
OTHER WELDING RESIDUE ARE REMOVED, AND THAT THE INTERNAL
DIAMETERS OF PIPING ARE NOT PENETRATED?
DYES
DNO
DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL
CUTOUTS (DISCS) ARE RETRIEVED?
NAME PLAlEPROVIDED
-I8:T YES D NO
ES D NO
IF NO, EXPLAIN
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN:
NAME OF SPRINKLER CONTRACTOR
AHERN FIRE PROTECTION, 201 MORRIS COURT .- FOND DU LAC, WI 54935
TESTS WITNESSED BY
G JURISDICTION (SIGNED). TITLJQ
J..-- ~ ;A1-
FOR PROPERTY OWNER (SIGNED) TITLE
"2 -'7
TTLE
1~mtf ill
DATE
~:) --7
3
~sconSin
Assembly Location
I
~5
Assembly Type
~E
o DC Detector
se, ~~O~ /
Initial Test
1 '1:;t check
Closed tight
Leaked j L /
Static j 7
Final Test
';",0 Closed tight
, Static
PSID
2'nd'check
Closed tight
Leaked ,
StaH2- I, ,
--------------
PSID
- - - - - - - - - - -. - - - - -
PSID
o Closed tight 2'nd check
Static PSID
DETECTOR BYPASS ASSEMBLY INITIAL TEST
),1'st check 2'nd check
,; 0 Closed tight 0 Closed tight
o Leaked 0 Leaked
Static PSlD Static
- - - - - - - - ~.>;,,,,.,;
DETECTOR BYPASS ASSEMBLY FINAL TEST
o Closed tight 0 Closed tight
Static PSID Stalie"
PSID
-----------------------
PSID
SEP 5 2007
DEPARTfvlENT OF
COMMUNITY DEVELOPMENT
ASSEMBLIES IN FIRE PROTECTION SYSTEMS
Forward Flow Test -:) J./,
Designed flow rate v I <; ,
Note: Include hose stream demand where applicable
- - - - - - ~ - -- - - -
GPM
Actual flow rate
GPM
IndiCating Control Valves
o No. one control valve open
Partes) Replaced/Comments
------------------------------
o Locked
I HEREBY CERTIFY THE TEST RESULTS ARE TRUE AND THE TEST WAS CONDUCTED BY ME PERSONALLY.
Tester Name (PD, nt) ~~ ~ IY1@RegistartionNoJ]J"l'Z.5.TimeofDay
Tester Signature >~ Phone No. ~ 'I) J'r Date 0/ Jc}/tJ :;