HomeMy WebLinkAbout2007-Building/HVAC Z2-2054-0807 ~ OJHKOfH City of Oshkosh Division of Inspection Services 215 Church Avenue PO Box 1130 Oshkosh WI 54903-1130 www.ci.oshkosh.wLus ON THE WATER August 21, 2007 Coutland Morgan Coutlan Morgan Architect 711 Fielder Rd Arlington, TX 76012 Scott Fisher Prime Retail 217 E Redwood St 20th Floor Baltimore MD 21202 Site: Plan Number: Z2-2054-0807 DEB 3001 S Washburn S1. Space D210-D230 Oshkosh WI 54904 For: Description: Tenant space alterations Object Type: Building & BV AC Class of Construction: DB - 9000 Sq Ft.; Sprinklered Occupancy: M: Mercantile I Retail Maximum No of Occupants: 264 The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defmed in Chapter 101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements Key Item(s) I Conditions: · IBC 711.3 Any penetrations of fire rated assemblies are required to be protected with a listed firestopping system that matches the rating of the wall assembly being penetrated. Copies of the firestopping systems are required to be provided at the time of inspection. · IBC 901.2 Fire protection systems shall be installed, repaired, operated and maintained in accordance with this code and the international fire code. Construction of new walls may require the addition and or relocation of sprinkler heads to maintain required coverage, and not obstruct spray patterns of fire sprinklers · IBC 906.1/ IFC 906.3 The maximum travel distance allowed to a fire extinguisher is 75 feet. · IBC 1003.2.11 Means of egress illumination is required to be installed per this section. All paths of egress are required to have adequate emergency lighting to meet the performance requirements ofIBC 1003.2.11.3. Existing means of egress emergency lighting is permitted to be maintained in compliance with the code in effect at the time of construction. Any altered path of egress, or new path of egress, and any new emergency lighting being installed is required to comply with current code requirements. The relocated exterior doors require emergency light on the exterior side of doors. \\OSHKOSHM1SFS'j)epartmur(s',rnSrKdinns\Plan Rcyicw\Oim!11ereial Pian Review Z()(l7\Z2-2054-0~()7 3UOi S Washburn St Bidg & I IV:\Cdoe Page 1 of3 · IMC 602.2.1 Materials exposed within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.4, materials exposed within plenums shall be noncombustible or shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E 84. Caution on materials and equipment - i.e. speakers security equipment being located above ceiling within the plenum space. · IMC 606.2.1 Smoke detectors shall be installed in return air systern:s with a design capacity greater than 2000 cfin...... · IMC 606.4.1 The duct smoke detectors shall be connected to a fire alarm system. The actuation of a smoke detector shall activate a visible and audible supervisory signal at a constantly attended location. · IMC 606.4.1 Exception 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identifies as air duct detector trouble. · Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve rules under this code and which are made to construction documents that have previously been granted approval by the department or its authorized representative, shall be submitted to the office that granted the approval. All revisions and modifications to plans shall be approved in writing by the department or its authorized representative prior to the work involved in the revision or modification being carried out. A revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with Comm 61.31(1). · MUN 30 This review does not include review for signage. Applications for and questions regarding signage permits should be directed to Todd Muehrer- Associate Planner (920) 236-5057 SUBMIT: · IBC 1003.2.11 Means of egress illumination is required to be installed per this section. All paths of egress through The Retail Display area are required to have adequate emergency lighting to meet the performance requirements ofIBC 1003.2.11.3. Provide complete emergency lighting plan showing compliance with these requirements prior to installation of emergency lighting system. · Comm 61.30(3) This review does not include lighting. Comm 63.0001 Prior to installation, lighting plans and calculations shall be prepared in compliance with the code. Please submit lighting work sheets. · Comm61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional shall file a compliance statement form SBD-9720 with this office. A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to be obtained prior to commencement of work. \\( )SH K()SH M ISFS\JkpartmcntS.,InstX'di"ns\Plan RGI'iew\Comm.:rcial Plan Rev!cw 2007\Z2-2054-0,,07 3<)()! S Washburn ST Bldg & HV:\C.doc Page 2 of3 In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this review shall relieve the designer of the responsibility for designing a safe building, structure, or component. Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead. nan oe Building Systems Consultant (920) 236-5051 Monday- Friday 7;30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M. bnoe@ci.oshkosh.wi.us cc: Property file Fee Required $ Fee Received $ Balance Due $ 860.00 860.00 0.00 \\OSHKOSHMJSFS\Dcpmtmcm~\!nsJKctinns\Plan R(}vj;)\\".Commcrcia! Finn RGvicw 2007\Z2..20.54..0;:;07 .:JO() 1 S Washburn S, Bidg & HV:\C.(\o(; Page 3 00