HomeMy WebLinkAbout0126319-Electric
e
OSHKOSH
ON THE WATER
Job Address 2737 HARRISON ST
CITY OF OSHKOSH
No
126319
ELECTRIC PERMIT - APPLICATION AND RECORD
Owner
OSHKOSH TRUCK CORP ,
Create Date 08/15/2007
Contractor
NORTHLAND ELECTRICAL SERVICES L
Category 643 - Commercial-Addition/Remodels
Plan
Service
b New
o Change 0 Temp
. N/A
Type 0 Overhead
o Underground
Volts
Circuits
Luminaires
Amps
Switches
Receptacles
Appliances
Use/Nature of Factory/Interior alterations - remodel first floor office area under existing mezzanine and office build out of existing unfinished
Work mezzanine level.
Issued By:
$100,000.00
~
Plan Approval
$0.00
Permit Fee Paid
$513.00
Fees: Valuation
Date 08/17/2007
o Permit Voided I
Parcelld # 1519600000
In the performance of this work I agree to perform all work pursuant to rules governing the described construction.
While the City of Oshkosh has no authority to enforce easement restrictions of which it is not a party, if you perform the work
described in this permit application within an easement, the City strongly urges the permit applicant to contact the easement
holder(s) and to secure any necessary approvals before starting such activity.
Signature Date
Agent/Owner
Address
1100 ORVILLE DR
NEW LONDON WI 54961 - 9418
Telephone Number 920-531-1197
To schedule inspections please call the Inspection Request line at 236-5128 noting the Address, Permit Number, Type of
Inspection (i.e. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue if the inspection is not performed within two business days from the time the project is ready.
ftt'5( 3 -
City of Oshkosh
Division of Inspection Services
P.O. Box 1130
Oshkosh, WI 54903-1130
Phone (920) 236-5050
Fax (920) 236-5084
(f)
OfHKOfH
ON THE WATER
ELECTRICAL PERMIT APPLICATION
. All information after bold categories must be provided.
Incomplete applications will not be processed.
. Application(s) and fee(s) can be brought to City Hall, Room 205 or mailed to Inspection Services, PO Box 1128,
Oshkosh WI 54903-1128. Commencing work without permit(s) will result in fees being doubledor $100.00 plus the
normal permit fee, which ever is greater.
OR
I ou are a contractor artici atin in the Permit Fee Account S stem and have ade check here
if vou want this processed through vour account 0
DATE 8-13-2007
JOB ADDRESS 2737 Harrison street
OWNER
Oshkosh Truck Corporation
CONTRACTOR Northland Electrical Services
CHECK lii ALL APPLICABLE
USE CATEGORY
OSingle Family ODuplex
DMulti- Family
DRental
GlCommercial
Dlndustrial
SERVICE ONew
OChange
OTemporary
&INot Applicable
TYPE OOverhead
OUnderground
1XIN0t Applicable
FILL IN THE APPROPRIATE BLANK WITH THE NUMBER
I
Receptacles # .
Circuits #
Volts
Phase
Amps
Switches #
Fixtures #
CHECK &i ALL APPLICABLE
ORange
OFan OR Blower
o Motors
ODishwasher
OFurnace
DGas Pumps
OGarbage Disposal
OAlC
DOther
ODryer OWater Heater
OElectric Sign
,,:;\0...
9..,\t
DESCRIPTION OF ALL WORK BEING DONE
office s ace includin
Wiring of 8,000 sq. ft. additional
Ii htin and rece tacles.
MASTER ELECTRICIAN Tom Co] lrlr
SUBMITTED BY~1~ce
REGEWEC
AUG 1 7 2007
DEPARTMENT OF
COMMUNITY DEVELOPMENT
?s- \ yo?r- INSPECTION SERVICES DIVISION
Manager, Northland Electrical
VALUE (Including labor and aU materials including light fixtures) $ 1 n n , non _ 00
--_
Electric Permit Work Card
JQL+-Address 2737 HARRISON ST Permit Number 126319 Create Date 8/15/2007
Owner OSHKOSH TRUCK CORP Contractor NORTHLAND ELECTRICAL SERVICES L
Service New Q Change Q Temp ~ N/A~ Type Q Overhead Q Underground ~ N/A
Volts Circuits Luminaires
Amps Switches Receptacles Value $100,000.00
Use/Nature
of Work
i43 -Commercial-Addition/Remodels Factory/ Interior alterations -remodel first floor office areaunder existing
nezzanine and office build out of existing unfinished mezzanine level.
Inspections:
Date 10/16/2007
Type Rough In_
Inspector Kevin Benner
approved w/cond.
2EQUEST LINE /WILL BE READY FOR AN INSPECTION TO THE UPSTAIRS MEZZANINE
the offices have one receptacle in each one that there are 470 degrees of bends in the ENT that serves it. I reviewed what the correction
:ould be with Chuck. Chuck called @ 10/16/7 @ 11:57AM & stated that the violations have been corrected. also reviewed the power
listribution system, 8 I discussed that the plumbing pipes in the dedicated space for a control panel would have to be relocated.
Date/Time requested: 10/15/2007 01:06 PM Notice Type: Ready Date/Time: 10/15/2007 01:06 PM
Access: Electrician on site Chuck (920) 538-2432
Requested by: NORTHLAND ELECTRICAL SERVICES LL Phone Number:
Q Reinspect Fee Q Fee Wavied ^ Reinspect Fee Paid
-------------------------------------------- -- ----- - - ------- ------------------------------------------------------------------------------------------
Date 11/01/2007 Type Roughln Inspector Kevin Benner approved
tEQUEST LINE /READY FOR A ROUGH INSPECTION
temainder of the second floor.
"Please inspect 11/1 the electrician will be on site"`
Date/Time requested: 10/31/2007 03:11 PM Notice Type: Ready Date(fime: 11/01/2007 00:00
Access: Electrician will be on site
Requested by: NORTHLAND ELECTRICAL SERVICES LL Phone Number: (920) 538-2432 Chuck
Q Reinspect Fee Q Fee Wavied ^ Reinspect Fee Paid
- - - - ------ --------------------------------------
Date 11/19/2007 Type Roughln Inspector Kevin Benner approved
tEQUEST LINE /READY FOR A ROUGH INSPECTION OF THE 1ST FLOOR ONLY
)iscussed the HVAC contractor installation of EMT connectors for chase nipples. Chuck agreed to discuss this with the contractor. Also
liscussed the installation of suspended luminaires inthe offices.
Date/Time requested: 11/16/2007 09:49 AM Notice Type: Ready Date/Time: 11/16/2007 09:49 AM
Access•
Requested by: NORTHLAND ELECTRICAL SERVICES LL
Q Reinspect Fee Q Fee Wavied ^ Reinspect Fee Paid
Date 11/29/2007 Type Rough In Inspector Kevin Benner
approved
tEQUEST LINE /WOULD LIKE A 1ST FLOOR MEZZANINE INSPECTION
Date/Time requested: 11/28/2007 08:45 AM Notice Type: Ready Date/Time: 11/28/2007 08:45 AM
Access:
Phone Number: (920) 538-2432 Chuck
Requested by: NORTHLAND ELECTRICAL SERVICES LL Phone Number: (920) 538-2432 Chuck
Q Reinspect Fee Q Fee Wavied ^ Reinspect Fee Paid
Electric Permit Work Card
.fob Address 2737 HARRISON ST Permit Number 126319 Create Date 8/15/2007
Owner OSHKOSH TRUCK CORP Contractor NORTHLAND ELECTRICAL SERVICES L
Service New Q ChangeQ Temp ~ N/A Type Q Overhead Q Underground ~ N/A _J
Volts Circuits Luminaires
Amps Switches Receptacles Value $100,000.00
Use/Nature 3 -Commercial-Addition/Remodels Factory/ Interior alterations -remodel first floor office area under existing
of Work ezzanine and office build out of existing unfinished mezzanine level.
Inspections:
Date 11!29/2007 Type Service Inspector Kevin Benner not approved
;EQUEST LINE /WOULD LIKE A SERVICE INSPECTION
luilding steel bond to be a minimum of 1/0 CU
:ales for the bus duct that the XFMR was fed from.
DatelTime requested: 11/28/2007 08:45 AM Notice Type: Ready Date/Time: 11/28/2007 08:45 AM
Access:
Requested by: NORTHLAND ELECTRICAL SERVICES LL Phone Number: (920) 538-2432 Chuck
Q Reinspect Fee Q Fee Wavied ^ Reinspect Fee Paid
------------------------------------- -- - - -- -- --- ------------------ ------------------------------------------------------------------- - - ---- - - - - -- -----
Date 12/13/2007 Type Abv Ceiling Inspector Kevin Benner not approved
nd Floor Only. \ Already started installing tiles /ENT in the Air-Plenum Ceiling, Removal of the old CL2 cables,CL2 cable support, MC
upport (bathrooms & RTU). Reviewed with Chuck.
Date/Time requested: 12/12!2007_ 02:48 PM Notice Type: Ready DatelTime: 12/12/2007 02:48 PM _
Access:
Requested by: NORTHLAND ELECTRICAL SERVICES LL Phone Number: 538-2432 Chuck
Q Reinspect Fee Q Fee Wavied ^ Reinspect Fee Paid
- ------------------------------------------------------------------------ --------------------
Date 12/13/2007 Type Abv Ceiling Inspector Kevin Benner approved w/cond.
____
1st Floor North Side =Approved
2nd Floor Re-Inspect Partial =Need to do partial inspections through tiles throughout the installation. (North Conf .Rm no access above th
ceiling)
Date/Time requested: 12/13/2007__ 01:00 PM Notice Type: Ready Date/Time: 12/13/2007 01:00 P_M_ __
Access:
Requested by: NORTHLAND ELECTRICAL SERVICES LL Phone Number: 538-2432 Chuck
Q Reinspect Fee Q Fee Wavied ^ Reinspect Fee Paid
------------------------------------- - ----- --- - - ------------------------------- --------------------------------------------------------------- - --- -- ---- - - --
Date 12/17/2007 Type Abv Ceiling Inspector Kevin Benner
- _-..._
st Floor South side
nd Floor Re-Inspect
AC cable support (add ceiling wires), Unused raceway to be closed, box cover.
teviewed with Chuck
Date/Time requested: 12/17/2007 08:02 AM Notice Type: Ready Date/Time: 12/17/2007 08:02 AM
Access•
Requested by: NORTHLAND ELECTRICAL SERVICES LL
Q Reinspect Fee Q Fee Wavied ^ Reinspect Fee Paid
Phone Number: 538-2492 Chuck
Electric Permit Work Card
Job Address 2737 tiARRISON ST Permit Number 126319 Create Date 8/15/2007
Owner OSHKOSH TRUCK CORP Contractor NORTHLAND ELECTRICAL SERVICES L
Service New Q Change Q Temp ~ N/A Type Q Overhead Q Underground ~ N!A J
Volts Circuits Luminaires
Value $100,000.00
Amps Switches Receptacles
UseMature 3 -Commercial-Addition/Remodels Factory/ Interior alterations -remodel first floor office area under existing
of Work ezzanine and office build out of existing unfinished mezzanine level.
Inspections:
Date 12/17/2007 Type Consultation Inspector Kevin Benner _ not approved
're-Final Inspection
IFPA 72 requirements, Panet Schedules, Add-A -Depth rings, Again requested the talc's for the buss duct which feeds the area.
Date/Time requested: 12/17/2007 00:00 PM Notice Type: Ready DatelTime: 12/17/2007 00:00 PM
Access:
Requested by: NORTHLAND ELECTRICAL SERVICES LL Phone Number: 538-2492 Chuck
Q Reinspect Fee Q Fee Wavied ^ Reinspect Fee Paid
--------------------------------------------------------------------------------------------------
Date 12/18/2007 Type Abv Ceiling Inspector Kevin Benner
te-Inspect _ ".- --
Aore MC support & raceway to be closed
Date/Time requested: 12/17/2007 00:00 PM Notice Type: Ready DatelTime: 12/18/2007 00:00 AM
Access:
Requested by: NORTHLAND ELECTRICAL SERVICES LL
Phone Number: 538-2492 Chuck
Q Reinspect Fee Q Fee Wavied ^ Reinspect Fee Paid
Date 12/21/2007 Type Final Inspector Adam Krause
Notice Type: Ready Date/Time:
'artial Final Inspection -Awaiting talcs. of bus duct tap. -- -
Date/Time requested: 12/18/2007 00:00 AM Notice Type: _ Ready Date/Time: 12/19!2007 00:0.0_AM
Access:.
Requested by: NORTHLAND ELECTRICAL SERVICES LL Phone Number: 538-2492 Chuc_ k
Q Reinspect Fee Q Fee Wavied ^ Reinspect Fee Paid
Date 09/23/2008 Type Note Inspector Allyn Dannhoff
-wner & Electrical contractor failed to provide Electrical Calculations demonstrating the Buss Du
rea is properly sized or the Buss Duct can support the additional electric demand. See attached
0/14/8
DatelTime requested:
Access•
Requested by:
Q Reinspect Fee Q Fee Wavied
approved w/cond.
approved w/cond.
ding electrical power to
Muerman nEngineering.
^ Reinspect Fee Paid
Phone Number:
Benner, Kevin
From: Fred Muermann [Fred@me-pe.com]
Sent: Tuesday, October 14, 2008 12:43 PM
To: Benner, Kevin
Subject: RE: FW: Oshkosh truck MEZZANINE PROJECT
Yes I do
thank you
Kind regards
Fred Muermann
President
Muermann Engineering
116 Fremont St.
Kiel, WI 53042
Phone 920.894.7800 ext. 102
Fax 920.894.7916
-----Original Message-----
From: Benner, Kevin [mailto:kbenner@ci.oshkosh.wi.us]
Sent: Tuesday, October 14, 2008 12:41 PM
To: Fred Muermann
Subject: RE: FW: Oshkosh truck MEZZANINE PROJECT
Hi Fred,
I assume by this communication that you agree with this data. If so than this email is
acceptable.
Kevin Benner
Electrical Inspector
City of Oshkosh
920-236-5046
kbenner@ci.oshkosh.wi.us
-----Original Message-----
From: Fred Muermann [mailto:Fred@me-pe.com]
Sent: Tuesday, October 14, 2008 10:42 AM
To: Benner, Kevin
Cc: Fred Muermann RMeyers@defense.oshkoshcorp.com; Corey Defferding
Subject: RE: FW: Oshkosh truck MEZZANINE PROJECT
Hello Kevin
The Electrical contractor has completed the code required 30 day electrical metering, on
the bus duct, feeder, through the summer during a time when there is maximum expected load
-the maximum measured load during that time was 485 amps this is on the 1600 amp bus duct
with a 1600 amp feeder.
Do you need any further information on this? Or do you need this information furnished in
another way to you
Kind regards
Fred Muermann
President
Muermann Engineering
116 Fremont St.
Kiel, WI 53042
1
Phone 920.894.7800 ext. 102
Fax 920.894.7916
From: Benner, Kevin [mailto:kbenner@ci.oshkosh.wi.us]
Sent: Monday, April 14, 2008 9:15 AM
To: Fred Muermann
Subject: RE: Oshkosh truck MEZZANINE PROJECT
The section that you reference would be Comm 16.23(2). If this would be the case I would
expect that a typical July or August would be in order.
Kevin Benner
City of Oshkosh
Electrical Inspector
920-236-5046
kbenner@ci.oshkosh.wi.us
From: Fred Muermann [mailto:Fred@me-pe.com]
Sent: Monday, April 14, 2008 8:50 AM
To: Benner, Kevin
Subject: RE: Oshkosh truck MEZZANINE PROJECT
Yes I would agree- many changes over the years - What we could do is have it recorded for
30 days( in the summer) I believe that the NEC allows that as a method of load
determination of existing systems that of course would be the added load with the existing
load.
Kind regards
Fred Muermann
President
Muermann Engineering
116 Fremont St.
Kiel, WI 53042.
Phone 920.894.7800 ext. 102
Fax 920.894.7916
From: Benner, Kevin [mailto:kbenner@ci.oshkosh.wi.us]
Sent: Monday, April 14, 2008 8:43 AM
To: Fred Muermann
Subject: RE: Oshkosh truck MEZZANINE PROJECT I give up. I assume we do not know how to
calculate the load.
Kevin Benner
City of Oshkosh
Electrical Inspector
920-236-5046
2
kbenner@ci.oshkosh.wi.us
From: Fred Muermann [mailto:Fred@me-pe.com]
Sent: Monday, April 14, 2008 7:15 AM
To: Benner, Kevin
Subject: RE: Oshkosh truck MEZZANINE PROJECT
Hello Kevin
There is existing miscellaneous load that has a measured ampacity of 300 amps. This was
measured prior to the office addition, the EC installed a recording amp meter and recorded
for two weeks during the summer of 2007.
Kind regards
Fred Muermann
President
Muermann Engineering
116 Fremont St.
Kiel, WI 53042.
Phone 920.894.7800 ext. 102
Fax 920.894.7916
From: Benner, Kevin [mailto:kbenner@ci.oshkosh.wi.us]
Sent: Monday, April 14, 2008 7:10 AM
To: Fred Muermann
Subject: RE: Oshkosh truck MEZZANINE PROJECT Fred, Am I to assume that this panel board
is the only item on this buss duct?
Kevin Benner
City of Oshkosh
Electrical Inspector
920-236-5046
From: Benner, Kevin [mailto:kbenner@ci.oshkosh.wi.us]
Sent: Friday, April 11, 2008 2:22 PM
To: Fred Muermann
Subject: RE: Oshkosh truck MEZZANINE PROJECT It does not necessarily need to be a letter
an email would be fine. The communication needs to include the actual equipment that is
connected to this just as you would if you were to design this from scratch to determine
your design and equipment.
Kevin Benner
City of Oshkosh
Electrical Inspector
920-236-5046
kbenner@ci.oshkosh.wi.us
From: Fred Muermann [mailto: Fred@me-pe.com)
Sent: Friday, April 11, 2008 2:17 PM
To: Benner, Kevin
3
Subject: RE: Oshkosh truck MEZZANINE PROJECT
Opps sorry- I will do a letter
Kind regards
Fred Muermann
President
Muermann Engineering
116 Fremont St.
Kiel, WI 53042.
Phone 920.894.7800 ext. 102
Fax 920.894.7916
From: Benner, Kevin [mailto:kbenner@ci.oshkosh.wi.us)
Sent: Friday, April 11, 2008 12:24 PM
To: Fred Muermann
Subject: RE: Oshkosh truck MEZZANINE PROJECT No. Please reference the previous
correspondence.
Kevin Benner
City of Oshkosh
Electrical Inspector
920-236-5046
kbenner@ci.oshkosh.wi.us
From: Fred Muermann [mailto:Fred@me-pe.com)
Sent: Friday, April 11, 2008 11:24 AM
To: Benner, Kevin
Cc: Russ Eilers; Corey Defferding
Subject: RE: Oshkosh truck MEZZANINE PROJECT
Hello Kevin
The office mezzanine electrical Load was connected to a 1600 amp bus duct that is fed from
a 1200 amp breaker. Last summer( before the addition of the new load) the electrical
contractor did a multiday load study and found that the highest was 300 amp, the added NEC
calculated demand for the mezzanine office is 227 KVA or 274 amps.
The contractor( Chuck at Northland Electric) measured the load again today and found the
highest reading to be 360 amps, of course that would be without the AC operating and most
likely with out the Elevator-- in any case the bus duct has adequate capacity for the
added load
Does this information suffice or do you need a letter from our office?
Kind regards
Fred Muermann
President
Muermann Engineering
116 Fremont St.
Kiel, WI 53042.
Phone 920.894.7800 ext. 102
Fax 920.894.7916
4
From: Benner, Kevin [mailto:kbenner@ci.oshkosh.wi.us]
Sent: Wednesday, April 09, 2008 12:16 PM
To: Fred Muermann
Subject: RE: Oshkosh truck project
Hi Fred,
Do not make this harder than it has to be! I just need know what the connected loads are
on the buss duct and the total ampacity. You do not need to very specific just the
general equipment and its load. This can be done with a document, we do not a line
diagram.
Kevin Benner
City of Oshkosh
Electrical Inspector
920-236-5046
kbenner@ci.oshkosh.wi.us
From: Fred Muermann [mailto:Fred@me-pe.com]
Sent: Wednesday, April 09, 2008 9:32 AM
To: Benner, Kevin
Cc: Corey Defferding; RMeyers@oshtruck.com
Subject: RE: Oshkosh truck project
Hello Kevin
How shall the information be presented to you? do you need a revised one line diagram? do
you need a revised overall floor plan showing where the bus duct is ?
Is there a form or something that you need to show the load calculations
Kind regards
Fred Muermann
President
Muermann Engineering
116 Fremont St.
Kiel, WI 53042.
Phone 920.894.7800 ext. 102
Fax 920.894.7916
From: Benner, Kevin [mailto:kbenner@ci.oshkosh.wi.us]
Sent: Tuesday, April 08, 2008 7:51 AM
To: Fred Muermann
Subject: RE: Oshkosh truck project:
Hi Fred,
The project that you stated has been completed for a year was allowed to occupy 12/19/07.
My calendar says that this is four months and in the four months from late December
through early April I would not imagine that the air conditioning has been utilized in the
worst case scenario with the elevator running and all other amenities that come with full
occupancy.
The first order for calculations was requested on 11/28/07. As the E.C.
was
allowed to not follow your engineered plans, I am certain that for future alterations this
knowledge would or should be necessary.
The occupancy of this project was allowed with the understanding that calculations would
5
be provided immediately. As always once someone gets what they want (occupancy) we do not
get what we need to complete the project on our end, and then our customers complain that
our office is being difficult.
If your E.C. would have followed your engineered drawings I would not be questioning the
installation.
Kevin Benner
City of Oshkosh
Electrical Inspector
920-236-5046
kbenner@ci.oshkosh.wi.us
From: Fred Muermann [mailto:Fred@me-pe.com]
Sent: Thursday, April 03, 2008 10:43 AM
To: Benner, Kevin
Cc: Kari Gehde; RMeyers@oshtruck.com
Subject: RE: Oshkosh truck project
Thank you Kevin
Regarding the Bus Duct I will have to follow up with the owner, the contractor was to
provide that- we initially had the load connected to another bus duct that had no load-
the contractor elected to connect it to a different bus duct that was determined had load
capacity .
This office that is fed from the bus duct is up and operating for a year now, can I assume
all that is required is a amperage reading on the duct feeder during occupied hours when
the duct is loaded?
Kind regards
Fred Muermann
President
Muermann Engineering
116 Fremont St.
Kiel, WI 53042.
Phone 920.894.7800 ext. 102
Fax 920.894.7916
From: Benner, Kevin [mailto:kbenner@ci.oshkosh.wi.us]
Sent: Thursday, April 03, 2008 9:56 AM.
To: Fred Muermann
Subject: RE: Oshkosh truck project
Hi Fred,
On another note I did require calculations for the bus duct in which we tapped a large
load to serve the office installations that we did this past winter. Those offices are
occupied and I have not received those calculations to date.
Kevin Benner
City of Oshkosh
Electrical Inspector
920-236-5046
6
kbenner@ci.oshkosh.wi.us