HomeMy WebLinkAbout12988-Electrical maintenance
e
OSHKOSH
ON THE WATER
Issue Date 8/8/2007
Address 1824 MICHIGAN ST
Name
I JEANNE M SCHMUDE
INSPECTION SERVICES DIVISION ROOM 205
DEPARTMENT OF COMMUNITY DEVELOPMENT
CORRECTION NOTICE
CITY OF OSHKOSH
215 CHURCH AVE
PO Box 1130
OSHKOSH WI 54903-1130
Compliance Date 9/7/2007
Compliance No
Sent to
l!:J Owner
Address
1824 MICHIGAN ST
City
OSHKOSH
State Zip Code
WI 54902 -6835
Introduction
WPS personnel informed the inspection department of code violations pertaining to your electrical service. I have verified the
rviolations and now request that you address the situation.
U Required for Occupancy
Occupancy
Item # Code Mun. Code 11-50 Compliance Not Checked Compliance Date 09/07/2007
Description I'n the event of damage to an electrical service, whether by storm, deterioration, vandalism, or other causes, all electrical services, 60 Amperes
or less shall be replaced with a minimum of 100 Ampere service.
08/08/2007
Last
Updated
Item # 2 Code NEC 230.51 Compliance No Compliance Date 09/07/2007
Description Service entrance conductors shall be supported by staples or other approved means. 12" from service heads and enclosures, 30" intervals.
08/08/2007
Last
Updated
12988
Page 1 of 2
e
OSHKOSH
ON THE WATER
Issue Date 8/8/2007
Address 1824 MICHIGAN ST
INSPECTION SEFMCES DIVISION ROOM 205
DEPARTMENT OF COMMUNITY DEVELOPMENT
CORRECTION NOTICE
CITY OF OSHKOSH
215 CHURCH AVE
PO Box 1130
OSHKOSH WI 54903-1130
Compliance Date 9/7/2007
Compliance No
Sent to
l!J Owner
Name
I JEANNE M SCHMUDE
Address
1824 MICHIGAN ST
City
OSHKOSH
State Zip Code
WI 54902 -6835
Introduction
IWpS personnel informed the inspection department of code violations pertaining to your electrical service. I have verified the
violations and now request that you address the situation.
U Required for Occupancy
Occupancy
Item # 3 Code 230.54 Compliance No Compliance Date 09/07/2007
Description Service conductors and raceways shall be provided with a properly supported service-head or goose-neck installed according to
manufacturer's specifications.
08/08/2007
Last
Updated
Summary I appreciate your cooperation on this matter. Please correct these problems as soon as possible. If comliance is not achieved
by the below-mentioned date, WPS will receive orders to disconnect your electrical service as of 12:00 P.M., Sept. 7th, 2007,
ror a $217.50 citation may be issued, possibly daily, from the date of correction notice issuance.
Violations must be corrected and approved within 30 days unless otherwise noted. Call for reinspections prior to concealment
and/or occupancy. Upon completing the corrections, the owner/contractor/agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 9/7/2007
Office hours for obtaining permits are Monday through Friday 7:30-8:30 a.m. and 12:30-1 :30 p.m. or by appointment. To schedule
inspections please call the Inspection Request line at 236-5128 noting the address, permit number (when applicable), and the
nature of what needs to be inspected.
Signature Date
Inspected by: Adam Krause 236-5274 akrause@ci.oshkosh.wi.us
I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes.
Print Name
Company
Signature
Date
Also Sent to: U Bldg
U Elec
U HVAC
U Plbg
U Designer
U Other
U Inspector
WPS-ERIC STRANGEWAY
3300 N MAIN ST
PO BOX 420
WI 54901 - 0420
12988