HomeMy WebLinkAbout0074645-Plumbing (interior)
~ ~ \~,
o
OSHKOSH
ON THE WATER
Job Address 1935 HICKORY LN
Vi
Contractor
Bathtub
Whirlpool
Lavatory
Toilet
Res. Sink
Bar Sink
Water Heater
Site Drain
Roof Drain
Use/Nature
of Work
Valuation
Issued By
CITY OF OSHKOSH
PLUMBING PERMIT - APPLICATION AND RECORD
No 0074645
Owner
JAY H KLINGER
Create Date 10/21/1999
JIM'S PLUMBING
2 Shower 2 Ejector/Grind
- -
1 Floor Drain 1 Water Softner
7 Lndry Tray 1 Local Waste
- -
4 Lndry Stndp 1 Clothes Wshr
1 Disposal 1 Bidet
-
Dishwasher 1 Beer Tap
2 Sump Pump 1 Dent. Oper.
Classrm Sink Lab Sink
Breakrm Sink Sterilizer
Category 410 - Residential-I nterior
Plan
Gar Drain
Soda Disp
Coffee Maker
Int Grease Trap
Ext Grease Trap
2
Dip Well
Drink Ftn
Wait. St.
Ice Chest
Exam Sink
Sculry Sink
Hand Sink
Plaster Sink
Surgeons Sink
F Prep Sink
Serv Sink
Shamp Sink
FlrlWst Sink
Catch Basin
Wash Ftn
Urinal
Standp Rec
Ice Maker
NSFR
Size Material Type # Conn. Type
Sanitary Sewer
Storm Sewer
Water Service
$16,000.00
$0.00
Permit Fees
$112.00
Plan Approval
Date 12/06/1999
D Permit Voided I
Signature
In the performance of this work, I agree to perform all work pursuant to rules governing the described construction.
Date
Address W-6166 GREENVILLE DRIVE
Agent/Owner
GREENVILLE WI 54942 - 0000 . Telephone Number 757-5258 OR 757-64
{~~~
Owner
~tegory
.htub
Roof Drain
Use/Nature
of Work
Sanitary Sewer
Storm Sewer
water Service
Date 00/00/0000 Type
F?q~ ,of>l
Lndry Tray
Lndry Stndp
Disposal
Dishwasher
Sump Pump
Classrm Sink
Breakrm Sink
}J S f'~
Size
Plumbing Permit Work Card
Permit Number 0000000 1'119 L/5
Contractor JIM'S PLUMBING
i . /-t;",y fJ d Plan
JaY"
Ejector/Grind LL Dip Well
Water Softner Drink Ftn
Local Waste Wait. St.
Clothes Wshr Ice Chest
Bidet Exam Sink
Beer Tap Sculry Sink
Dent. Oper. Hand Sink
Lab Sink Plaster Sink
Sterilizer Surgeons Sink
11-
LL
LL
LL
~
~
ilL
Material
#
Conn.Type
Type
t<\ (y 1:>-/ c.{j 1
f 7/~1 0;;
F Prep Sink
Serv Sink
Shamp Sink
FlrlWst Sink
Catch Basin
Wash Ftn
Urinal
Standp Rec
Ice Maker
1-~ h 'j{
lIt 2--
cD 3 we. f~ Q?--/ 3 ,,( I-
(9f~DP>v~
Inspector
U Approved
Create Date 10/21/1999
Value
JIlt, I ~ CO $O:OCr
II Z-
Job Address 1935 HICKORY LN
JAY H KLINGER
""0
III 't. Shower
Whirlpool --.!.L Floor Drain
Lavatory " "'ffi.i..7
Toilet II~
Res. Sink ~
Bar Sink
Water Heater , I 'Z....
Site Drain
~.
Gar Drain
Soda Disp
Coffee Maker
Int Grease Trap
Ext Grease Trap
.'
. ,
r-\
FIXTURE LISTING SHEET
!
Purchaser1s name here
Reference: Fox Cities Construction
Date: 12-03-1999
City: Oshkosh
Address: 1935. Hickory Lane
NO. NONPUBLIC USE FIXTURES
1 Automatic Clothes Washer -------------------
1 Bath Tub With or Without Shower Head -------
1 Dishwasher ---------------------------------
6 Hose Bib 1/2 -------------------------------
1 Kitchen Sink -------------------------------
1 Laundry Tray -------------------------------
3 Lavatory -----------------------------------
2 Bathtub, Lav & Water Closet-FT -------------
2 Shower, Lav & Water Closet-FT --------------
Total water supply fixture units
Hot Cold Total
1.0 1.0 1.5
1.5 1.5 2.0
1.0 0.0 1.0
0.0 18.0 18.0
1.0 1.0 1.5
1.0 1.0 1.5
1.5 1.5 3.0
4.0 7.0 8.0
3.0 6.0 7.0
Hot Cold Total
14.00 37.00 43.50
25.4 Demand of building in gallons per minute. Predominate flush tank
0.0 Gallons per min added for Cont. Flow Special fixtures & equip.
r-'\ 0.0 Water Supply Fixture Units added for Intermittent Flow equip.
6.7 Pressure available for uniform loss. For table use. - 7.0
Controlling fixture & location:
MAXIMUM ALLOWABLE LOAD FOR COPPER TUBE TYPE M
PIPE SZ 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4
GPM 3.0 7.5 15.0 26.0 40.0 80.0 120 175 280
WSFU 148.0 .
FM 0.0 0.0 5.0 9.0 27.0 36S 740 1630
WSFU FT 3.0 9.5 22.0 45.0 87.0 275.0 475 780 1630
~
,
,'"
WATER DISTRIBUTION DATASHEET
Date: June 29, 2000
?""'"\
./
"""~
Name: JIMS PLUMBING
Project: NSFR
Street:
Street: 1935 HICKORY LN
City:
City:
1. 25.4 Gallon per minute buiding demand, predominatly Flush Tank.
2. 54.0 Low pressure at the Main in Street.
3. .9 Lb loss from a 2.0 ft difference in elevation from Main in Street to the Water M~ter.
4a.~ Lb loss from a 15.0 ft I" Copper Tube Type K ASTM B88 water service from the Main in Street to the curb stop.
Pressure loss detemined using a C value of 130, inside diameter of .995 and a velocity of 10.5 ft per sec.
4b.~ Lb loss from a 35.0 ft I" Copper Tube Type K ASTM B88 water service from the curb stop to the Water Meter.
Pressure loss detemined using a C value of 130, inside diameter of .995 and a velocity of 10.5 ft per sec.
5. 9.7 Lb loss from a 3/4in Meter
6. 32.1 Lbs of pressure available at the Water Meter. This value is entered in (B) below.
The (A) value listed below is determined by using the following formula, then rounding the result up.
A = B-(C+D+E) x 100
F
~
A. --2. Pressure available for uniform loss (psi/l00 feet of pipe).
B. ~ Lbs of pressure available at the Water Meter.
c. ~ Pressure needed at the controlling fixture. PRSR BLNC TIS VALVE-MASTER BATH
D. ~ Lb loss resulting from a 9.0 ft difference in elevation from the Water Meter to the controlling fixture.
E. ~ Lb pressure loss due to a no pressure loss devices serving the controlling fixture.
F. 97.5 Ft Developed length from the 65.0 ft actual length of piping from the Water Meter to the controlling fixture.
Maximun Allowable load for Copper Tube Type M, ASTM B88
Nominal Size 1/2 5/8 3/4 1 1 1/4 1 1/2 2 21/2 3 4
Actual1. D. .569 0 .811 1.055 1.291 1.527 2.009 2.495 2.981 3.935
Value ofC 130 130 130 130 130 130 130 130 130 130
Velocity in ft per sec. 8 8 8 8 8 8 8 8 8 8
Maximum Gpm 3.5 0 9 18 30 45 79 121 174 303
Maximum FM WSFU 0 0 0 6 14 38 144 369 731 1833
Maximum FT WSFU 3.5 0 11.5 26.5 55 110 270 480 776 1833
/"'\
)
i
WATER DISTRIBUTION DATASHEET
Date: June 29, 2000
~
I
d"
Name: JIMS PLUMBING
Project: NSFR
Street:
Street: 1935 HICKORY LN
City:
City:
1. 25.4 Gallon per minute buiding demand, predominatly Flush Tank.
2. 54.0 Low pressure at the Main in Street.
3. .9 Lb loss from a 2.0 ft difference in elevation from Main in Street to the Water Meter.
-- i
4a. 3.4 Lb loss from a 15.0 ft 1" Copper Tube Type K ASTM B88 water service from ~he Main in Street to the curb stop.
- Pressure loss detemined using a C value of 130, inside diameter of .995 and a v:elocity of 10.5 ft per sec.
4b. 8.0 Lb loss from a 35.0 ft 1" Copper Tube Type K ASTM B88 water service from the curb stop to the Water Meter.
- Pressure loss detemined using a C value of 130, inside diameter of .995 and a velocity of 10.5 ft per sec.
5. 3.7 Lb loss from a lin Meter
6. 38.1 Lbs of pressure available at the Water Meter. This value is entered in (B) below.
The (A) value listed below is determined by using the following formula, then rounding the result up.
A = B-(C+D+E) x 100
F
.~
A. ~ Pressure available for uniform loss (psillOO feet of pipe).
B. ~ Lbs of pressure available at the Water Meter.
C. ~ Pressure needed at the controlling fixture. PRSR BLNC TIS V AL VE-MASTE~ BATH
D. ~ Lb loss resulting from a 9.0 ft difference in elevation from the Water Meter to *e controlling fixture.
E. .0 Lb pressure loss due to a no pressure loss devices serving the controlling fixture.
F. 97.5 Ft Developed length from the 65.0 ft actual length of piping from the Water Meter to the controlling fixture.
Maximun Allowable load for Copper Tube Type M, ASTM B88
Nominal Size 1/2 5/8 3/4 1 1 1/4 11/2 2 21/2 3 4
Actual I. D. .569 0 .811 1.055 1.291 1.527 2.009 2.495 2.981 3.935
Value ofC 130 130 130 130 130 130 130 130 130 130
Velocity in ft per sec. 8 8 8 8 8 8 8 8 8 8
Maximum Gpm 4.5 0 11.5 21.5 32 45 79 121 174 303
Maximum FM WSFU 0 0 4 7 16 !38 144 369 731 1833
Maximum FT WSFU 5 0 16 34 60 '110 270 480 776 1833
~
..!
~ ."
WATER CALCULATION WORKSHEET
(.21\rChaSer1 s name here For: Fox Cities construc1tion
1. 25.4 Demand of building in gallons per minute.
2. 45.0 Low pressure at main in street (or at external pressure tank).
3. 2.0 Difference in elevation from main to m~ter (or external pressure
tank to building control valve) .
4. 1 Size of water meter (if applicable).
5a. 15.0 Developed length from main to curb stop (if no curb stop then from
main to meter, or external pressure tank to building control valve) .
5b. 35.0 Developed length from curb stop to meter.
You Must First Find the Available Pressure After the Water Meter
(or at building control valve). To obtain this pressure, you must:
6a. 3.6
6b. 6.5
7. 0.9
f\ 3.7
9. 30.4
WHERE:
A. 7.0
B. 30.4
C. 20.0
D. 3.9
E. 0.0
f'
lo. 97.5
Find pressure loss due to friction in
service main to curb (If no curb stop
Find pressure loss due to friction in
service curb to meter.
1 K inch water
then from main to meter) .
1 Sc40 inch water
Find pressure loss due to elevation, main to meter (or external
pressure tank to building control valve). Multiply the difference
in elevation by .434 p.s.i./ft.
I
Find pressure loss due to meter (from manufacturer or AWWA) .
Subtract the loss due to friction (Step 6), loss due to elevation
(Step 7), and loss due to meter (Step 8) from the low main pressure
(or low pressure at external pressure tank). This calculation is the
available pressure after the water meter (or at the building control
valve). This answer is entered in lineB, below.
A = ((B -(C + D + E)) divided by F) X 100
Pressure available for uniform loss (p.s.i./1QO' of pipe) .
Available pressure after water meter (at the building control valve
or low pressure at internal pressure tank). (See item 9. above).
Pressure needed at controlling fixture.
Difference in elevation between water meter (building control valve
or iIi-ternal pressure tank) and controlling fixture
in feet 9.0 x .434 p.s.i./ft.
Pressure loss due to water softeners, water treatment ,devices,
instantaneous water heaters and backflow preventers wkich serve the
controlling fixture. Conventional water heaters usualry do not have
a pressure loss.
Developed length from water meter (building control valve or
internal pressure tank) to controlling fixture in feet 65 x 1.5.
''''t . .,. -eo
Fixture Listing
Date: June 29, 2000
o
)
Name: JIMS PLUMBING
Project: NSFR
Street:
Street: 1935 HICKORY LN
City:
City:
Non Public Use Fixtures
Hot
Cold
Total
1 Automatic Clothes Washer 1.00 1.00 1.50
1 Bathtub, with or without shower head 1.50 1.50 2.00
1 Dishwashing Machine 1.00 .00 1.00
6 Hose Bib, 1/2" diameter .00 18.00 18.00
1 Kitchen Sink 1.00 1.00 1.50
1 Laundry Tray, 1 or 2 compartment 1.00 1.00 1.50
3 Lavatory 1.50 1.50 3.00
2 Bathtub, lavatory and water closet - FT group 4.00 7.00 8.00
2 Shower Stall, lavatory and water closet FT - group 3.00 6.00 7.00
Total Water Supply Fixture Units
14.00
37.00
43.50
25.4 Gallon per minute demand of the building. Predominatly Flush Tank
14.5 Pressure available for uniform loss. For the table use - 15.0
Maximun Allowable load for Copper Tube Type M, ASTM B88
.~
,
/
Nominal Size 1/2 5/8 3/4 1 1 1/4 1 1/2 2 21/2 3 4
Actual I. D. .569 0 .811 1.055 1.291 1.527 2.009 2.495 2.981 3.935
Value ofC 130 130 130 130 130 130 130 130 130 130
Velocity in ft per sec. 8 8 8 8 8 8 8 8 8 8
Maximum Gpm 4.5 0 11.5 21.5 32 45 79 121 174 303
Maximum FM WSFU 0 0 4 7 16 38 144 369 731 1833
Maximum FT WSFU 5 0 16 34 60 110 270 480 776 1833
.~