Approved:
Issued:
July 19, 2007
July 24, 2007
Wyldewood Condominiums LLC
2990 Universal St Ste C
Oshkosh, WI 54904-5903
CERTIFICATE OF OCCUPANCY
An Occupancy Permit is hereby issued for the new 5-unit condo located at 376
Wyldewood Drive, Oshkosh, Wisconsin 54904 as described in Building.Permit
Application number(s) 123610.
This building is to be used only as a multi-family residence and is located inthe R-3PD,
Multiple Dwelling District, Planned Development Overlay.
LIMITATIONS:
Maximum persons and/or living units: Five living units
CONDITIONS:
1) Final grading must be done in accordance with the approved subdivision drainage
plan. This plan is on file in the public works office, 3rd floor of City Hall.. .
2) Erosion control measures must be maintained until the lawn is established.
Note: Final grade must be a minimum of 6" below all siding.
NOTE:
1) Copies of inspection results are available upon request in room 205, City Hall.
2) Future permits may be required for additional work to your propert~~
A new Certificate' of Occupancy shall be required prior to occupancy, should additional
building(s) be erected, or should any buildings mentioned above be altered or moved.
The use of land, or buildings, shall not be changed until a Certificate of Occupancy is .
issued for that occupancy. All conditions noted above must be complied with in order
for this certificate to be valid.
AJIUJ1f~
Building Systems Inspector
Cc: Midwest General Contractors Inc.
~ Building Permit Work Card
Job Address 376 WYLDEWOOD DR Permit Number 0123610
Create Date 2/22/2007
,Owner WYLDEWOOD CONDOMINIUMS LLC
Category 130 - New Multi-Family
Contractor MIDWEST GENERAL CONTRACTORS INC
Plan W3-1917-0207
Occupany Permit Required Flood Plain Height Permit Not Required Class of Const:
Use/Nature New 5 Unit Condo - 4 units @ 1442 sf, 1 unit @ 1321 sf all with 420 sf garage.
of Work
5Bibc
I
I
HV AC Contr
Plumbing Contr
Electric Contr
Inspections:
Date 5/29/2007 Type Insulation Inspector John Zarate
Request line. Only one unit was open. I left Jay a message to call when the other units would be open.
not approved
DatelTime requested: 5/24/2007 12:58 PM Notice Type:
Access: IOpen
Requested By: MIDWEST GENERAL CONTRACTORS INC
o Reinspect Fee 0 Fee Waived 0 Reinspect Fee Paid
Ready DatelTime: 5/29/2007
Phone Number: Jay - 420-5878
Date 7/17/2007 Type Final Inspector Nicole Krahn
1) Firestop penetrations through the boxsill due to sprinkler piping
~) Seal all exterior penetrations (sump pump pipes, gas pipes)
3) Bring in fill to provide uniform rises off the rear deck steps
~) Submit HVAC and BLD compliance statements.
not approved
DatelTime requested: 7/13/2007 09:47 AM Notice Type: CC
Access: IUNITS WILL BE OPEN TUESDAY 7/17/07
Requested By: MIDWEST GENERAL CONTRACTORS INC-Jay
o Reinspect Fee 0 Fee Waived 0 Reinspect Fee Paid
Ready DatelTime: 7/17/2007 00:00
Phone Number: (920) 420-5878
Date 7/18/2007 Type Re Final Inspector Nicole Krahn approved w/cond.
Uay Hendricks signed and dated the building work card noting that the violations were corrected. Close the file per the office policy.
DatelTime requested: 7/18/2007
Access: I
Requested By:
o Reinspect Fee 0 Fee Waived
12:06 PM
Notice Type:
Ready DatelTime: 7/18/2007 12:06 PM
Phone Number:
o Reinspect Fee Paid
Page 2 of 2
Building Permit Work Card
Job Address 376 WYLDEWOOD DR Permit Number 0123610 Create Date 2/22/2007
Owner WYLDEWOOD CONDOMINIUMS LLC Contractor MIDWEST GENERAL CONTRACTORS INC
Category 130 - New Multi-Family Plan W3-1917-0207
Occupany Permit Required Flood Plain Height Permit Not Required Class of Const: 5Bibc
Use/Nature New 5 Unit Condo - 4 units @ 1442 sf, 1 unit @ 1321 sf all with 420 sf garage.
of Work
HVAC Contr Plumbing Contr
Electric Contr
Inspections:
Date 5/29/2007 Type Insulation Inspector John Zarate
'Request line. Only one unit was open. I left Jay a message to call when the other units would be open.
not approved
Date/Time requested: 5/24/2007 12:58 PM Notice Type:
Access: IOpen
Requested By: MIDWEST GENERAL CONTRACTORS INC
o Reinspect Fee 0 Fee Waived D Reinspect Fee Paid
Ready Date/Time: 5/29/2007
Phone Number: Jay - 420-5878
Date 7/17/2007 Type Final Inspector Nicole Krahn
1) Firestop penetrations through the boxsill due to sprinkler piping
:2) Seal all exterior penetrations (sump pump pipes, gas pipes)
13 Bring in fill to provide uniform rises oft the rear deck steps
) Submit HVAC and BLD compliance statements.
not approved
Date/Time requested: 7/13/2007 09:47 AM Notice Type: CC Ready Date/Time: 7/17/2007 00:00
Access: IUNITS WILL BE OPEN TUESDAY 7/17/07
Requested By: MIDWEST GENERAL CONTRACTORS INC-Jay Phone Number: (920) 420-5878
o Reinspect Fee 0 Fee Waived D Reinspect Fee Paid
A \( V ~D(~ llav\ f
J1 W~J
j c..y Hf'ldr(' c-~ f
~(t..
cor r ec:.-1 eel
7 -I C "0 7
Page 2 of 2
.. Building Permit Work Card
Job Address 376 WYLDEWOOD DR Permit Number 0123610 Create Date 2/22/2007
Owner WYLDEWOOD CONDOMINIUMS LLC Contractor MIDWEST GENERAL CONTRACTORS INC
Category 130 - New Multi-Family Plan W3-1917-0207
Occupany Permit Required Flood Plain Height Permit Not Required Class of Const: 5Bibc
Use/Nature New 5 Unit Condo - 4 units @ 1442 sf, 1 unit @ 1321 sf all with 420 sf garage.
of Work
HV AC Contr Plumbing Contr
Electric Contr
Inspections:
Date 3/22/2007 Type Footings Inspector Nicole Krahn
FAXED REQUEST / READY FOR A FOOTING INSPECTION
approved
DatelTime requested: 3/20/2007 05:14 PM Notice Type:
Access: I
Requested By: John Skotzke Concrete Construction Inc
o Reinspect Fee 0 Fee Waived D Reinspect Fee Paid
Ready DatelTime: 3/21/2007 12:00 PM
Phone Number: (920) 231-1667
Date 3/30/2007 Type Foundation Backfill Inspector Nicole Krahn
REQUEST LINE / READY FOR A FOUNDATION INSPECTION
"PLEASE CALL ANDREW LANG HE WOULD LIKE TO BE PRESENT""
approved
DatelTime requested: 3/29/2007 03:34 PM Notice Type:
Access: I
Requested By: MIDWEST GENERAL CONTRACTORS INC-Andy
o Reinspect Fee 0 Fee Waived D Reinspect Fee Paid
Ready DatelTime: 3/29/2007 03:34 PM
Phone Number: (920) 410-0864
Date 5/23/2007
Type Rough In
Inspector Nicole Krahn
approved
r"""! "",
DatelTime requested: 5/21/2007 10:57 AM Notice Type:
Access: IOpen
Requested By: MIDWEST GENERAL CONTRACTORS INC
o Reinspect Fee 0 Fee Waived D Reinspect Fee Paid
Ready DatelTime: 5/23/2007 : PM
Phone Number: Jay - 420-5878
Date 5/22/2007 Type Drain Tile Inspector John Zarate approved
Fax request / Requesting drain tile basement floor & flashing. There will be ladders in all 5 units by 10:00am. Please let Janell know
fvvhen they can pour. .
DatelTime requested: 5/22/2007 07:45 AM Notice Type:
Access: I
Requested By: JOHN SKOTZKE CONCRETE CONST - Janell
o Reinspect Fee 0 Fee Waived 0 Reinspect Fee Paid
Ready DatelTime: 5/22/2007 10:00 AM
Phone Number: 378-4380
Page 1 of 2
~ Electric Permit Work Card
'"' Job Address 376 WYLDEWOOD DR Permit Number 123679
Create Date 3/2/2007
Owner WYLDEWOOD CONDOMINIUMS LLC Contractor CUMINGS ELECTRIC INC
Service Ie New 0 Change 0 Temp 0 NIAI Type 0 Overhead . Underground 0 N/A
Volts 120/240 Circuits 132 Luminaires 60
Value
Amps 400 Switches 40 Receptacles 200
UselNature ~31 - Residential-New Multi-Family Wiring New 5-unit condo (to include temporary service). ..DEBIT ACCT...
of Work
$15,000.00
Inspections:
Date 07/17/2007 Type Final
r"""" "0. I ",II wok fo< '0.'
DatelTime requested: 07/17/2007 06:50 AM
Access:
Inspector Kevin Benner
approved
Notice Type:
Ready DatelTime: 07/17/200706:50 AM
Requested by: CUMINGS ELECTRIC INC - Jan
o Reinspect Fee 0 Fee Wavied D Reinspect Fee Paid
Phone Number:
. ~ Electric Permit Work Card
Job Address 376 WYLDEWOOD DR Permit Number 123679
Create Date 3/212007
Owner WYLDEWOOD CONDOMINIUMS LLC
Service . New 0 ChangeO Temp 0 N/A
Volts 120/240 Circuits 132
Amps
Contractor CUMINGS ELECTRIC INC
Type 0 Overhead . Underground 0 N/A
Luminaires 60
Use/Nature
of Work
400 Switches 40 Receptacles 200
631 - Residential-New Multi-Family Wiring New 5-unit condo (to include temporary service). "DEBIT ACCT".
Value
$15,000.00
Inspections:
Date 03/12/2007
Type Temporary
Inspector Adam Krause
approved
;Request line / Temporary service inspection
iFaxed to WPS 3-14-07 7:30 AM
DatelTime requested: 03/12/2007 06:02 AM
Access:
Requested by: CUMINGS ELECTRIC INC - Jan
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Notice Type:
Ready DatelTime: 03/12/200706:02 AM
Phone Number:
Date 05/15/2007 Type Service
ra'ed appro"'" to wes 5-'5-0n'O AM
DatelTime requested: 05/10/2007 01 :11 PM
Access:
Requested by: CUMINGS ELECTRIC INC - Jan Phone Number:
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
--- - - --------- - - ---- - - - ---- -- -- - ----- - - - ---- - - ----- -- ---- ------ - - ---- - - - ---- -- ----- - - - ------ ---- - - - ----- ----- ---- ----- ------- ----- - - ----- -- - ---- ------ ------
Date 05/17/2007 Type Rough In Inspector Adam Krause approved
Inspector Adam Krause
approved
Notice Type:
Ready DatelTime: 05/10/2007 01: 11 PM
DatelTime requested: 05/17/2007 08:06 AM
Access:
Requested by: CUMINGS ELECTRIC INC
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Notice Type:
Ready DatelTime: 05/17/200707:34 AM
Phone Number:
Date 07/16/2007 Type Final Inspector Kevin Benner not approved
[Request line / The inspection was not going very good so I called the E.C. and requested that he get an electrician there to review the
nstallation and correct violations and finish the work.
DatelTime requested: 07/16/2007 07:40 AM
Access:
Requested by: CUMINGS ELECTRIC INC - Jan
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Notice Type:
Ready DatelTime: 07/16/200707:40 AM
Phone Number:
Job Address 376 WYLDEWOODDR
HVAC Permit Work Card
Permit Number
123884
Create Date 03/21/2007
Owner WYLDEWOOD CONDOMINIUMS LLC Contractor BREWER HEATING
Fuel ~ Gas I U Oil I U Electric I U Solar U Solid I Value
System 0 New I 0 Replace I 0 Other
~ Forced Air U Radiant I U Steam I ~ AlC I U Vent
U Electric I U Hot Water I U Suppl. I U Con. Burner I
Chimney Type 0 Chimney A 0 Chimney B 0 Direct Vent . Not Applicable
Use/Nature COMM/ New 5 unit multifamily. -Trans ID 1372949 (See bid plan W3-1917-0207)
of Work
$22,500.00
I
I
Inspections:
Date 5/23/2007 Type Rough In
Inspector Nicole Krahn
approved
DatelTime requested: OS/23/2007 10:47 AM
Access: I
Requested By:
o Reinspect Fee 0 Fee Waived
Notice Type:
Ready DatelTime: OS/23/2007 10:47 AM
Phone Number:
o Reinspect Fee Paid
Date 7/17/2007 Type Final
Inspector Nicole Krahn
approved
DatelTime requested: 07/18/2007 07:19 AM
Access: I
Requested By:
o Reinspect Fee 0 Fee Waived
Notice Type:
Ready DatelTime: 07/18/2007 07:19 AM
Phone Number:
o Reinspect Fee Paid
This form is required to be submitted by the supervising professional (architect, engineer, HVAC designer or olectrical
designer) observing construction of projects within buildings with total areas exceeding 50,000 cubic feet and construction
$ antennas, towers, and bleachers (lLHR 50.1 O). Failure to submit this form may result in penalties as specified in
..HR 50.26 and/or local ordinances.
Generallnstructions: Prior to the initial occupancy of new buildings or additions and the final occupancy of
altered existing buildings, submit this eompJeted and signed form to:
· The municipal building inspection office and
· Safety and Buildings, P.O. Box 7162, MadiSon, WI 53707-7162
Personal Information you provide may be u.td for secondary purposes [Privacy law, s. 15.04 (1)(rn)].
1. PROJECT INFORMATION: Please fill in the following with information from your plan approval letter.
Transaction 10 Number /3 ? -<94..,
Site Number C, 757 Y . .
Site tOCltlon (number & street) iJ d 1l,I(;4.8-r; 0 JZ4-!:J '3 7 b lvt yl Je wood
tlt'City [] Village 0 Town of ~/~sl+ County of 4i~
2. PURPOSE OF THIS STATEMENT: {Check Box A, B, C, or 0 to indicate purpose and complete any other
applicable boxltSlnd information. Attach additional pages If necessary.}
Check those which apply: C Building Object ID # ' ~AC Object 10 # _ J f I 17' L
o Lighting Object 10 #
II
i
f
l
t'J$
~i~1'
c:;,.:
~'
~.
f
~
i'
~
I
~.
'~I
:~~
1:::'"
t
~y
~
i
l.
~.:t
'.1;,;'
J
w
f
l't
~
~,
~.
~
~
;.;;~.
~,
\","
~.
i,
~
l
..,
t
f
~
.,
~
l
,
i
p:,::-
f'
~'
l
~
~
1
'.
r
f
t'
Cl Partial Completion
Description of Portion Compl81td
A) ~atement of Substantial Cc;smpllanc:e
To the best of ITIy knowledge. belief, and based on Ol\site observation. construction of the following building and/or HVAC
iterris applleable to this project nllve been completed in substanlial compliance with the appreved plans and .
specifications.
C BUILDING ITEMS
,. Structural system Including submittal and erection of all building
components (tru..... precast. ~tal building, etc.)
2. Fire protedion Iystems (sprinkltrS. Ilatms, smoke detectors) de~igned.
installed, and tilled (rneluding fOlWlrd flow on back flow devices) by
appropriately registered prcfessionals
3. Shaft and Italtw8y encl08ure
4. Exit5 indudlng exit and dlredlonellights
5. Fire.miative con$truc:tlon. enclosure of hazards. fire walls, labeled
doors, class of construdicn
6. Sanitation system (toilets, sinks, drinking facilities)
7. Barrier..fre, including Comm 18 elevato", and lifts
B. ILHR 63 energy envelope
9. All condition. of building plan approval and applicable varian",
The following items are not in oomplianee and mUlt b, addressed; &IAMl',J!., /Z.r.t'A.r ~tn<.lfJ.~
o HVAC ITEMS
1. HVAC aystlWl inchJding final test
(ILHR 64.53)
2. All conaitions of HVAC ~Ian approval and
applicable variances
C UGHTING ITEMS
1. Ext~or lighting & control requirements
2. Interior lighting & control requirements
3. All conditions of lighting plan apP!'01Ial and
applicable V8riancl!S .
B) 0 Statement of Noncompliance
, Due to the following listed violation., this projed is not ready for occupancy:
C) C Supervising Professional Withdrawn From Project (Use A or 8 abolf8 to inCflcate project Slatus as of this date.)
D) 0 Project Abandoned
~. SUPERVJSING PROFESSIONAL SIG~ TURE FOf3.: ) / .
j 0 Buildin; ~AC C Ughtlng f..-Hv6 6;:(~..< ~D. 72:i;~/a7
Name (p..... print Qr type #
Phone number 7 ~-7 41 Customer 10. ~ 5' J"Ill SignatuAl: ~
.
J'f'rl
SRM720 tR.O~1I1
III d
v6vegevOe6
<< Oe598VLOe6
Cl3M3Cl8
TOTAL P.ell
OO:ee 50-CO-000e
Buildings, HV AC Compliance Statement 8BO:'9720
This form is required to be submitted by the supervising professional (arcl1itect, engineer, HVAC designer or electrical
designer) observing construction of projects within buildings with total areas exceeding 50,000 cubic feet or greater and
bleachers (Comm 50.10/Comm 61.50). Failure to submit this form may result in penaltie$ as specified in Comm
50.26/Comm 61.23 and/or local ordinances.
General Instructions: Prior to the initial occupancy of new buildings or additions and the final occupancy of
altered existing buildings, submit this completed and signed form to:
. The municipal building inspection office and
. Safety and Buildings, 10541 N Ranch Road, Hayward, WI 54843
Personal information you provide may be used for secondary purposes [Privacy Law, s. 15.04 (1)(m)].
1. PROJECT INFORMATION: Please fill in the following with information from your plan approval letter.
Transaction ID Number 1366398
Site Number 667578
Site location (number & street) 376 W1LDEWOOD 5 UNIT #9
o City 0 Village 0 Town Of OSHKOSH County of WINNEBAGO
2. PURPOSE OF THIS STATEMENT: (Check Box A, B, C, or D to indicate purpose and complete any other
applicable boxes and information. Attach additional pages if necessary).
Check those which apply: 0 Building Object 10# 1117659 0 HVAC Object ID#
o Lighting Object 10#
o Partial Completion
Description of Portion Completed
A) 0 Statement of Substantial Compliance
To the best of my knowledge, belief, and based on onsite observation, construction of the following building and/or HVAC
items applicable to this project have been completed in substantial compliance with the approved plans and specifications.
o BUILDING/LIGHTING ITEMS
1. Structural system including submittal and erection of all building
components (trusses, precast. metal building, etc.)
2. Fire protection systems (sprinklers, alarms, smoke detectors)
designed, installed, and tested (including forward flow on back flow
devices) by appropriately registered professionals.
3. Shaft and stairway enclosure
4. Exits including exit and directional lights
5. Fire-resistive construction, enclosure of hazards, fire walls, labeled
doors, class of construction, fire stopped penetrations
6. Sanitation system (toilets, sinks, drinking facilities)
7. Barrier-free including Comm 18 elevators and lifts
8. Energy envelope requirements
9. All conditions of building plan approval and applicable variances
The following items are not in compliance and must be addressed:
10. Exterior lighting & control requirements
11. Interior lighting & control requirements
12. All conditions of lighting plan approval
and applicable variances
o HVAC ITEMS
1. HVAC system including final test
2. All conditions of HVAC plan approval
and applicable variances
B) 0 Statement of Noncompliance
Due to the following listed violations, this project is not ready for occupancy:
C) 0 Supervising Professional Withdrawn From Project (Use A or B above to indicate project status as of this date.)
D) 0 Project Abandoned
3. SUPERVISING PROFESSIONAL SIGNATURE FOR:
o Building 0 HVAC 0 Lighting DONALD HAANEN 7/212007
Name (please print or type)
Phone # 920-497-5007 Customer 10# 649536 Signature