HomeMy WebLinkAbout12785-Occupancy Inspection Items
e
OSHKOSH
ON THE WATER
Issue Date 6/13/2007
Address
Sent to
Introduction
INSPECTION SERVICES DIVISION ROOM 205
DEPARTMENT OF COMMUNITY DEVELOPMENT
CORRECTION NOTICE
CITY OF OSHKOSH
215 CHURCH AVE
PO Box 1130
OSHKOSH WI 54903-1130
Compliance Date 7/13/2007 IMMEDIATELY
Compliance No
10 W 16TH AVE
~ Owner
Name
I SOPER PLUMBING INC
Address
2225 BURNWOOD DR
City
OSHKOSH
State Zip Code
WI 54902 -0000
~ Required for Occupancy Occupancy Industrial
An Occupancy Inspection on 6-11-07 revealed the following items to correct. These items must be corrected to secure the
required Occupancy Permit. Please folloW up with your HV AC contractor to ensure the required Permit is secured as
discussed.
Compliance Date 07/13/2007 IMMEDIATELY
Item # Code Comm 63.1027(3) Compliance No
Description Provide programmable thermostats for all Heating equipment.
06/13/2007
Last
Updated
Item # 2 Code Comm 64.0403 Compliance No Compliance Date 07/13/2007. IMMEDIATELY
Description Install the Office HVAC equipment as shown on the Stamped State Approved Plans to meet the ventilation requirements.
06/13/2007
Item # 3 Code Comm 62.906 Compliance No
Description ,Fire Extinguishers shall be properly sized: 2A 1 OBC.
06/13/2007 I
Last
Updated
Last
Updated
Compliance Date 07/13/2007 IMMEDIATELY
Item # 4 Code Comm 62.1101(2) Compliance No Compliance Date 07/13/2007 IMMEDIATELY
Description A.nsi A117.1-1998 section 404.2.7 All passage doors, entry and exit doors shall be provided with lever action hardware.
06/13/2007
Last
Updated
Item # 5 Code Comm 62.1101(2) Compliance No Compliance Date 07/13/2007 IMMEDIATELY
Description l\nsi A117.1-1998 section 604.5 Provide grab bars for the toilet. Make sure to install to meet the location requirements.
06/13/2007
Last
Updated
Item # 6
Description
06/13/2007
Last
Updated
Code Comm 62.1101 (2) Compliance No
["" A 117.1-1998 ",",00 604.4 The Toilet "at ,hall be 17-19" a'ovo Ihe lIo~h 1100'.
Compliance Date 07/13/2007
IMMEDIATELY
12785
Page 1 of 3
'"
~e
OSHKOSH
ON THE WATER
Issue Date 6/13/2007
INSPECTION SERVICES DIVISION ROOM 205
DEPARTMENT OF COMMUNITY DEVELOPMENT
CORRECTION NOTICE
CITY OF OSHKOSH
215 CHURCH AVE
PO Box 1130
OSHKOSH WI 54903-1130
Compliance Date 7/13/2007 IMMEDIATELY
Compliance No
Address
10 W 16TH AVE
Sent to
~ Owner
Name
I SOPER PLUMBING INC
Address
2225 BURNWOOD DR
City
OSHKOSH
State Zip Code
WI 54902 - 0000
Introduction
~n Occupancy Inspection on 6-11-07 revealed the following items to correct. These items must be corrected to secure the
required Occupancy Permit. Please follow up with your HV AC contractor to ensure the required Permit is secured as
!discussed.
~ Required for Occupancy
Occupancy Industrial
Item # 7 Code Comm 62.1003.2.10 Compliance No Compliance Date 07/13/2007 IMMEDIATELY
Description Exit lights shall be provided over the two exit doors leading to the exterior of the building for the main warehouse room.
06/13/2007
Last
Updated
Item # 8
Description
Code Comm 62.1003.2.11.2 Compliance No Compliance Date 07/13/2007 IMMEDIATELY
he main storage warehouse shall be provided with emergency illumination to illuminate a path of exit travel between the two exit doors as well
as meeting the exterior emergency illumination and emergency power source requirements. The path of travel shall be provided with the
required amount emergency illumination: average of 1 ftIcandle per sq. ft.
06/13/2007
Last
Updated
12785
Page 2 of 3
'.
OSHKOSH
ON THE WATER
Issue Date 6/13/2007
INSPECTION SERVICES DIVISION ROOM 205
DEPARTMENT OF COMMUNITY DEVELOPMENT
CORRECTION NOTICE
CITY OF OSHKOSH
215 CHURCH AVE
PO Box 1130
OSHKOSH WI 54903-1130
Compliance Date 7/13/2007 IMMEDIATELY
Compliance No
Address
10 W 16TH AVE
Sent to
l!J Owner
Name
I SOPER PLUMBING INC
Address
2225 BURNWOOD DR
City
OSHKOSH
State Zip Code
WI 54902 -0000
l!J Required for Occupancy
Occupancy Industrial
Item # 9
Description
Code Comm 61.31(4) Compliance No Compliance Date 07/13/2007 IMMEDIATELY
he State Approved Plans do not identify, nor approve this building for use as a Parking Garage or for Automotive repair. Said uses shall be
discontinued or approval for said uses shall be obtained from the Planning Division and revised Building & HVAC Plans shall be sent to the
~tate for review and approval. If the later is pursued, compliance with the approved plans shall be provided.
06/13/2007
Last
Updated
Summary ~ compliance date of 7/13/07 has been established. If additional time is needed, please contact me with information to justify
"",hat additional time is needed.
Violations must be corrected and approved within 30 days unless otherwise noted. Call for reinspections prior to concealment
and/or occupancy. Upon completing the corrections, the owner/contractor/agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 7/13/2007
Office hours for obtaining permits are Monday through Friday 7:30-8:30 a.m. and 12:30-1 :30 p.m. or by appointment. To schedule
inspections please call the Inspection Request line at 236-5128 noting the address, permit number (when applicable), and the
nature of w~ to belnspeeted. . . .
5;ono'..0 itD. Date lj, f yo 7
Inspected by: Allyn Dannhoff 236-5045 adannhoff@cLoshkosh.wLus
I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes.
Print Name
Company
Signature
Date
Also Sent to: U Bldg
U Elec
U HVAC
U Plbg
U Designer
l!J Other
U Inspector
STUART SCHROTTKY
FIRE DEPT
12785
Page 3 of 3