HomeMy WebLinkAbout0124873-Electric (V-RAD)
G
OSHKOSH
ON THE WATER
Job Address 580 GROVE ST
Contractor SHEA ELECTRIC & COMMUNICATIONS
CITY OF OSHKOSH
No
124873
ELECTRIC PERMIT - APPLICATION AND RECORD
Owner AT & T
Create Date 05/18/2007
Category 641 - Commercial-New Service
Plan
o Change 0 Temp
. N/A
Type 0 Overhead
o Underground
Service
b New
120/240
Circuits
Luminaires
Volts
100
Switches
Receptacles
Amps
Appliances
Use/Nature of COM/ Power to V-RAD cabinet. 5 Rod ground ring and 60 amp feeder from the power ped to the V-RAD cabinet.
Work
$1,000.00
Plan Approval
$0.00
Permit Fee Paid
$60.00
Fees: Valuation
Issued By: "1f &::2
Date 05/18/2007
D Permit Voided i
Parcel Id #
Signatur
Date /y!f-o 7
AgenUOwner
Address
PO BOX 946
OSHKOSH
WI 54903 - 946
Telephone Number 920-303-9380
To schedule inspections please call the Inspection Request line at 236-5128 noting the Address, Permit Number, Type of
Inspection (Le. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue if the inspection is not performed within two business days from the time the project is ready.
,~, Permit App Electrical
Page 1 of2
&
Division of Inspection Services
215 Church Avenue
P.O. Box 1130
Oshkosh, WI 54903-1130
Fax (920) 236-5084
Phone (920) 236-5050
ELECTRICAL PERMIT APPLICATION
All information after bold categories must be provided.
Incomplete applications will not be processed.
Application(s) and fee(s) can be brought to City Hall, Room 205 or mailed to
Inspection Services, PO Box 1128, Oshkosh WI 54903-1128. Commencing work
without permit(s) will result in fees being doubled or $100.00 plus the
normal permit fee, which ever is greater.
If you are a contractor participatino in the Permit Fee Account System and have
adequate funds, type YES if you want this processed throuqh your account
DATE 5-17-07
JOB ADDRESS 580 Grove St. Oshkosh
OWNER AT&T
CONTRACTOR Shea Electric & Communications LLC
CHECK ALL APPLICABLE
USE CATEGORY
Single Family
UIndustrial
Duplex
Multi-Family
Rental
~ Commercial
SERVICE
New
Temporary
TYPE LJ Overhead
LJ Not
Applicable
LJ Change
Not
Applicable
~ Underground
FILL IN THE APPROPRIATE BLANK WITH THE NUMBER
Volts 120/240
Receptacles #
Circuits #
Phase 1 phase
Amps 100
Switches #
Fixtures #
http://www.ci.oshkosh. wLus/community _ development/lnspections/Permit_ App _Electrical... 5/1712007
J' Permit App Electrical
Page 2 of2
.-
CHECK ALL APPLICABLE
Range
Dishwasher
D Garbage
Disposal
Dryer
Water Heater
Fan OR
Blower
Motors
Furnace
Ale
Electric Sign
Gas Pumps Other
DESCRIPTION OF ALL WORK BEING DONE
We will be working with AT&T and Waas Boring to install power to
their V-Rad cabinet. Installation of a ground ring and five ground
rods and a 60 amp feeder from the power ped to the V-Rad cabinet
(two feet away on the same concrete pad). $1000.00 or less
VALUE (Inc~uding labor and all materials including light fixtures) $
1000.00
MASTER ELECTRICIAN John Jacobs #689604
L,~y~,ll~~~~
http://www.cLoshkosh. wLus/community _ development/lnspections/Permit_App _Electrical... 5/17/2007
Job Address 580 GROVE ST
Owner AT & T
Service b New 0 ChangeO Temp . N/A
Volts 120/240 Circuits
Amps 100 Switches
Electric Permit Work Card
Permit Number 124873
Create Date 5/18/2007
Contractor SHEA ELECTRIC & COMMUNICATIONS
I Type 0 Overhead 0 Underground . N/A
Luminaires
Receptacles
$1,000.00
Value
641 - Commercial-New Service COM/ Power to V-RAD cabinet. 5 Rod ground ring and 60 amp feeder from the power pedl
o the V-RAD cabinet. i
I
i
I
UselNature
of Work
Inspections:
Date 05/30/2007 Type Underground Inspector Kevin Benner
Called Dan to inform him that this is approved and can be backfilled
approved
DatelTime requested: 05/30/2007 10:13AM
Access:
Requested by: SHEA ELECTRIC & COMMUNICATIONS L
o Reinspect Fee 0 Fee Wavied D Reinspect Fee Paid
Notice Type:
Ready DatelTime: 05/30/200710:13 AM
Phone Number: 216-1618 Dan
Date 06/07/2007 Type Service Inspector Kevin Benner not approved
Service Disconnects are not identified, & I question the tap rules for the breakers on the line side of the service disconnect.
DatelTime requested: 06/06/2007 10:15 AM
Access:
Notice Type:
Ready DatelTime: 06/06/2007 00:00 PM
Requested by: SHEA ELECTRIC & COMMUNICATIONS L
o Reinspect Fee 0 Fee Wavied D Reinspect Fee Paid
Phone Number: 216-1618 Dan
Date 07/0212007
Type Re Service
Inspector Kevin Benner
approved
email request
IFaxed to WPS 7/2/7
DatelTime requested: 06/29/2007 05:37 PM
Access:
Requested by: SHEA ELECTRIC & COMMUNICATIONS L
o Reinspect Fee 0 Fee Wavied D Reinspect Fee Paid
Notice Type:
Ready DatelTime: 06/29/2007 05:37 PM
Phone Number: