May 14, 2007
Glenn Dik
P AEP Architecture Engineering, PC
1811 4 Mile Road NE
Grand Rapids, MI 49525
Fred Jaques
Alliance Development
601 Oregon St Ste A
Oshkosh, VVI54902
Hank Hondorp
Progressive AE, PC
1811 4 Mile Road NE
Grand Rapids, MI49525
Site: Plan Number: Y3-1968-0407
Citifinancial
510 S Koeller St
Oshkosh WI 54902
For:
Description: Tenant space alterations
Object Type: Building and HV AC
Class of Construction: lIB - 1405 Sq Ft.; sprinklered
Occupancy: B: Business / Office
Maximum No of Occupants:
The submittal described above has been reviewed for conformance with applicable VVisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) / Conditions:
. IBC 711.3 Any penetrations of fire rated assemblies are required to be protected with a listed firestopping
system that matches the rating of the wall assembly being penetrated. Copies of the firestopping systems
are required to be provided at the time of inspection.
. IBC 901.2 Fire protection systems shall be installed, repaired, operated and maintained in accordance with
this code and the international fire code. Construction of new walls may require the addition and or
relocation of sprinkler heads to maintain required coverage, and not obstruct spray patterns offire
sprinklers.
. IBC 906.1 / IFC 906.3 The maximum travel distance allowed to a fire extinguisher is 75 feet.
. IBC 1l01.2/ANSI A117.1-308.2 & 3 - Mechanical system controls shall be located a maximum of 48"
above the finished floor if the floor space allows a forward approach by a wheel chair or if the clear space
allows a parallel approach.
. IBC 1209.1 Provide toilet room floors with smooth, hard, nonabsorbent surface extending minimum 6
inches up onto walls. SheetA] 05 shows 4 inch base, please revise to be 6 inch.
R<:vi"w\(\\mmen'j,lI Phm R<:view
96B-0407 5 ! 0 S .Ko(;;\]er S, BIdg & nVAc.doc'
Page 1 of2
IBC 2406.2 Glazing in an individual fixed or operable panel adjacent to a door where the nearest exposed
edge of the glazing is within a 24 inch arc of either vertical edge of the door in a closed position and where
the bottom exposed edge of the glazing is less than 60 inches above the walking surface is requires safety
glazing materials. The windows in the closing rooms will need to be glazed with safety glazing
materials.
. mc 2902..1 / Table 2902 Drinking water is required to be provided, since no drinking fountain is shown
on plans a bottled water cooler is required to be provided.
. Comm 2902 (4) Separate facilities shall not be required in mercantile occupancies in which the occupant
load is 50 or less. Note: if the occupancy changes in the future, the requirements for plumbing fIXtures
". will need to be reviewed for compliance.
. IMC 302.1 The building or structure shall not be weakened by the installation of mechanical systems.
Verify that existing structure is capable of supporting the additional weight of the proposed rooftop
equipment.
. Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Comm 61.31(1).
. Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
. MUN 30-35 (1)(5) All roof top and ground level mechanical equipment and utilities shall be fully screened
from view of any street or residential zoning district. Contact David Buck - Associate planner (920) 236-
5062 for additional information on screening requirements. All screening shall be properly anchored in
place to resist wind loads. Additionally mc 1608.8 Roofprojections - Drift loads due to mechanical
equipment, penthouses, parapets and other projections above the roof shall be determined in accordance
with Section 7.8 of ASCE 7.
. Comm 80 This plan review does not include plumbing. Prior to installation of plumbing, plans and
calculations are required to be submitted and approved.
. MUN 30 This review does not include review for signage. Applications for and questions regarding
signage permits should be directed to Todd Muehrer - Associate Planner (920) 236-5057
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
correspondence may be made to me at the number listed below or the address on this letterhead.
r
Building Systems Consultant