HomeMy WebLinkAbout2007-Electric
e
OSHKOSH
ON THE WATER
Job Address 3245 S WASHBURN ST
CITY OF OSHKOSH
No
124619
ELECTRIC PERMIT - APPLlCATIO~ AND RECORD
Owner
BERGSTROM FOX VALLEY INC
Create Date 04/30/2007
Service
o New
o Change 0 Temp
. NIA
Type 0 Overhead
Plan
o Underground
Contractor
TOWN & COUNTRY ELECTRIC
Category 642 - Commercial-New Building Wiring
Volts
Circuits
luminaires
Amps
Switches
Receptacles
Appliances
Use/Nature of A.uto Sales & Repair 1 New 34110 sf building. Job #524201.
Work
Fees: Valuation
$320,000.00
Plan Approval
$0.00
Permit Fee Paid
$1,173.00
Issued By:
Date 05/03/2007
o Permit Voided I
Parcelld # 1365010000
In the performance of this work I agree to perform all work pursuant to rules governing the described construction.
While the City of Oshkosh has no authority to enforce easement restrictions of which it is not ~ party, if you perform the work
described in this permit application within an easement, the City strongly urges the permit applicant to contact the easement
holder(s) and to secure any necessary approvals before starting such activity.
Signature Date
Agent/Owner
Address
PO BOX 627
APPLETON WI 54912 - 627
Telephone Number 920-225-6507
To schedule inspections please call the Inspection Request line at 236-5128 noting the Address, Permit Number, Type of
Inspection (i.e. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue if the inspection is not performed within two business days from the time the project is ready.
Job 4t 5J-L(;)-O
City of Oshkosh
Division ofInspection Services
P.O. Box 1130
Oshkosh, VVI54903-1130
Phone (920) 236~5050
Fax (920) 236-5084
ELECTRICAL PERMIT APPLICATION
. ..":!". .........
All information after bold categories must be provided.
Incomplete applications will not be processed.
. Application(s) and fee(s) can be brought to City Hall, Room 205 or mailed to Inspection Services, PO Box 1128,
Oshkosh WI 54903-1128. Commencing work without permit(s) will result in fees being doubled or $100.00 plus the
normal permit fee, which ever is greater.
OR
If vou are a contractor varticivating in the Permit Fee Account Svstem and have adequate funds, check here
if vou want this processed throu'j{h vour account D .
DATE 1--30--0(
JOB ADDRESS 3J L(S .5.
OWNER g~S-hoVV1
CONTRACTOR '. I OW \I) "J'
llUa-5 h b tA. VI/}
Td yo fq
at111 +vtl EI-fC +M' (j
/
CHECK Ii1 ALL APPLICABLE
USE CATEGORY
. o Single Family
DI)uplex
DMu!ti,-:Pamily
DRentaJ
TYPE
~om,mercial OIndustri.al'
o Overhead DNot Applicable
o Underground
SERVICE DNew
DChange
o Temporary
DNot Applicable
FILL IN THE APPROPRIATE BLANK WITH THE NUMBER
Volts
Phase
Amps
/
Receptacles #
Circuits #
Switches #
Fixtures #
CHECK Ii1 ALL APPLICABLE
ORange
OFan OR Blower
DMotors
ODishwasher
DFumace
DGas Pumps
DGarbage Disposal
DAlC
o Other
ODryer OVVater Heater
DElectric Sign
DESCRIPTION OF ALL WORK BEING DONE
W J V~ j/) t'vJ (la V dtr1 /-t v$,h/}:J
,
VALUE (Including labor and all materials including light fixtures) $, ~,+D( t1 ~O r 00
MASTER ELECTRICIAN ~oI A, ~fi-t crj~
['e e: If, 1,/73'00
tll\
~L-\La
\
3/02
,
Electric Permit Work Card
Job Address 3245 S WASHBURN ST ~ermit Number 124619
Create Date 4/30/2007
Circuits
Contractor TOWN & COUNTRY ELECTRIC
I Type 0 Overhead 0 Underground. NIA
luminaires
I
-------.J
Owner BERGSTROM FOX VALLEY INC
Service b New 0 Change 0 Temp . NIA
Volts
Amps
Use/Nature
of Work
Switches Receptacles
~42 - Commercial-New Building Wiring Auto Sales & Repair I New 34110 sf building. Job #524201.
Value
$320,000.00
.~..........l
Illspections:
Date 05/01/2007 Type Rough In
rhowroom & offire "e. parti.1. Starti" to d<yWOlI.
Date/Time requested: 04/30/2007 01 :50 PM
Access:
Requested by: TOWN & COUNTRY ELECTRIC
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Inspector Kevin Benner
I
approved
Notice Type:
Ready Date/Time: 05/01/2007 00:00 AM
Phone Number: 450-1695 Rick
---------------------------,--------------.,.---------------------------,,---.----;------:"'---:--------------------------:--------------------------------------------
Type Consultation
Inspector Kevin Benner
Date 05/01/2007
Reviewed the power ditribution system.
Need qualification of XFMR stacking. Wiring bending space is not appropriate for the MCB terminations, grounding conductor size would
not be correct. Reviewed with Rick McCann & Steve Schroed~r of T&C.
Date/Time requested: 05/01/2007 00:00 AM
Access:
Requested by: Phone Number:
I
o Reinspect Fee 0 Fee Wavied 0 Reinspect :Fee Paid
_n_ _ _ _ ____ _ _ ____ _ _ _ n__ _ _ _ __ _n _ _ _ ____ _ _ _ _n_ _ _ _ __ _ _ _ __ __ _ _ _ ____ _ _ ____ _ j_'____ _ _ n __ _. _ n__ _ _ ___ _ n___ _ _ ____ _ _ _____ ____ _ _ _ _ _ __ _ __ __ _ _ _ _ n__ - - - - - - - - - _u____
Date 05/15/2007 Type Rough In Insp~ctor Kevin Benner approved
r"" '" are. to< a d<yW01I rem". D<yWOm" 5/15/7
L I
I
Date/Time requested: 05/10/2007 03:18 PM Not~ce Type: Ready Date/Time: 05/10/200703:18 PM
:
;
Notl,ce Type:
Ready Date/Time: 05/01/200700:00 AM
Access:
Requested by:
o Reinspect Fee 0 Fee Wavied
Phone Number:
o Reinspect Fee Paid
approved w/cond.
------------------------------------------------------------------------j---------------------:------ -- -------- --
Type Service Insp~ctor Kevin Benner
I
~PProved to energize if the AIC is less than 65KAIC (MCB is 65K).--
Faxed to WPS 5/15/7 I
erry Fameree from the State of WI stated that the design of t~.. e building steel and the fashion that the grounding is installed will work even
f it may not comply with the language of the code. 5/17/7 7:40 AM
Date/Time requested: 05/10/2007 03:18 PM Notice Type:
!
Requested by: TOWN & COUNTRY ELECTRIC Ric~ McC,
- I
o Reinspect Fee 0 Fee Wavied 0 Reinspect'Fee Paid
- ---- - - ----- - - - - - - - - - -- -- - - - - - .--- - - - ---- - _.- - - - - - w__ - - - - - - - - - - -- - - - - - - -t - - - - --- - - - - -,- - - - - -- - - -- -- - - ~ - --- - - --- - - - - - - - - --- - - - - - - - - - - - - - - - -- -- - - - - - - - - - - - - - ---
!
!
Date 05/15/2007
Ready DatelTime:
05/10/200703:18 AM
Access:
Phone Number: 450-1695 Rick
Electric Permit Work Card
Job Address 3245 S WASHBURN ST Permit Number 124619
Create Date 4/30/2007
Volts
Amps
Circuits
Switches
Contractor TOWN & COUNTRY ELECTRIC
Type 0 Overhead 0 Underground . N/A
luminaires
Value
$320,000.00
Owner BERGSTROM FOX VALLEY INC
Service b New 0 ChangeO Temp . N/A
Use/Naturj;! 642 - Commercial-New Building Wiring Auto Sales & Repair 1 New 34110 sf building. Job #524201.
of Work
Receptacles
,
Inspections:
Date 05/01/2007 Type Rough In
Showroom & office area partial. Starting to drywall.
Inspector Kevin Benner
approved
DatelTime requested: 04/30/2007 01:50 PM
Access:
Requested by: TOWN & COUNTRY ELECTRIC
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Notice Type:
Ready DatelTime: 05/01/2007 00:00 AM
Phone Number: 450-1695 Rick
------------------------------------------------------------------------------------------------------------.-----------------------------------------------
Date 05/01/2007 Type Consultation Inspector Kevin Benner
Reviewed the power ditribution system.
Need qualification of XFMR stacking. Wiring bending space is not appropriate for the MCB terminations, grounding conductor size would
not be correct. Reviewed with Rick McCann & Steve Schroeder of T&C.
Date/Time requested: 05/01/2007 00:00 AM
Access:
Requested by:
o Reinspect Fee 0 Fee Wavied
Notice Type:
Ready Date/Time: 05/01/200700:00 AM
Phone Number:
o Reinspect Fee Paid
- - - - - - - - - - - - - - - - - - - - - --- - - - - -- - - - - - -- - - - - - -- - - - - - - - - - - - - - - -- - - - - - - - - - - -- - - - - - - - - - - -- - - - --- - - - - - - - - - - - - - - - - -- - - - - - -- - - - - - - - - - -- - - - - -- - - - - - - - - - - - - - - - -- - - - - ---
Date 05/15/2007 Type Rough In
A.bove an area for a drywall ceiling. Drywalling 5/15/7
Inspector Kevin Benner
approved
DatelTime requested: 05/10/2007 03:18 PM
Access:
Requested by:
o Reinspect Fee 0 Fee Wavied
Notice Type:
Ready DatelTime: 05/10/200703:18 PM
Phone Number:
o Reinspect Fee Paid
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - -- - - - - -- - ... - - - - -- - - - - --- - - - - - - - - - - - - - - - - - - - - -- - - - - --- - - - - - - - - - -- - - - - - -- - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - -- - - --
Date 05/15/2007 Type Service Inspector Kevin Benner approved w/cond.
~pproved to energize if the AIC is less than 65KAIC (MCB is 65K).
Faxed to WPS 5/15/7
~erry Fameree from the State of WI stated that the design of the building steel and the fashion that the grounding is installed will work even
if it may not comply with the language of the code. 5/17/7 7:40 AM
DatelTime requested: 05/10/2007 03:18 PM
Access:
Requested by: TOWN & COUNTRY ELECTRIC Rick McC.
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Notice Type:
Ready DatelTime: 05/10/2007 03: 18 AM
Phone Number: 450-1695 Rick
"
Electric Permit Work Card
Job Address 3245 S WASHBURN ST Permit Number 124619 Create Date 4/30/2007
Owner BERGSTROM FOX VALLEY INC Contractor TOWN & COUNTRY ELECTRIC
Service bNew o ChangeO Temp . N/A I Type 0 Overhead o Underground . N/A I
Volts Circuits luminaires
Switches Receptacles Value $320,000.00
Amps
Use/Nature 642 - Commercial-New Building Wiring Auto Sales & Repair 1 New 34110 sf building. Job #524201.
of Work
Inspections:
Date 05/31/2007 Type Abv Ceiling Inspector Kevin Benner approved
Suspended ceiling in the Showroom area only. Oiscussed the underground wiring that was installed without inspection requests and with
material that was questioned on 5/15/7 whiel conducting a service inspection. It was agreed at that time that Steve Schroeder of T&C would
provide me with product info before the installation proceeded. At that time only the pole bases were installed.
Date/Time requested: 05/30/2007 11 :27 AM
Access:
Requested by: TOWN & COUNTRY ELECTRIC
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Notice Type:
Ready Date/Time: 05/30/2007 11 :27 AM
Phone Number: 450-1695 Rick
Date 06/06/2007 Type Underground Inspector Kevin Benner approved w/cond.
f-lIyn Oannhoff stated that this office will not enforc;:e the replacement of the non-listed raceways. The undergorund installation was not
iinspected or requested to be inspected at the time of installation. This inspection is for the transition from HOPE toPVC at the pole bases
and the building. 1 Partial UG
Date/Time requested: 06/05/2007 10:38 AM
Access:
Notice Type:
Ready Date/Time: 06/06/2007 00:00 AM
Requested by: TOWN & COUNTRY ELECTRIC
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Phone Number: 470-0496 Steve
Type Underground
Inspector Kevin Benner
approved w/cond.
Date 06/06/2007
rro"
Date/Time requested: 06/06/2007 11 :30 AM
Access:
Requested by: TOWN & COUNTRY ELECTRIC
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Notice Type:
Ready Date/Time: 06/06/2007 00:00 PM
Phone Number: 450-1695 Rick
Date 06/07/2007 Type Underground Inspector Kevin Benner approved w/cond.
Final Underground inspection. Oid not see all of the corrections but the corrections that I did see were done correctly.
DatelTime requested: 06/06/2007 00:00 PM
Access:
Notice Type:
Ready Date/Time: 06/07/2007 08:30 AM
Requested by: TOWN & COUNTRY ELECTRIC
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Phone Number: 450-1695 Rick
',,'
Electric Permit Work Card
Job Address 3245 S WASHBURN ST Permit Number 124619
Create Date 4/30/2007
Circuits
Contractor TOWN & COUNTRY ELECTRIC
I Type 0 Overhead 0 Underground . NIA
luminaires
Owner BERGSTROM FOX VALLEY INC
Service b New 0 ChangeO Temp . NIA
Volts
Amps
Use/Nature
of Work
Value
$320,000.00
Switches Receptacles
~42 - Commercial-New Building Wiring Auto Sales & Repair 1 New 34110 sf building. Job #524201.
Inspections:
Date 06/07/2007 Type Abv Ceiling Inspector Kevin Benner approved
~enter office area. Need to correct CL 2 wiring violations. Will re-inspect when the remainder of the above ceiling is completed.
Date/Time requested: 06/07/2007 00:00 AM
Access:
Requested by:
Notice Type:
Ready Date/Time: 06/07/200700:00 AM
Phone Number:
o Reinspect Fee 0 Fee Wavied
o Reinspect Fee Paid
Date 06/22/2007 Type Consultation Inspector Kevin Benner
Pre-Final Inspection (substantially complete) See field notes.
Conducted the rof-top inspection which is approved.
I
not approved
Date/Time requested: 06/21/2007 06:27 AM
Access:
Notice Type:
Ready Date/Time: 06/21/2007 00:00 AM
Requested by: TOWN & COUNTRY ELECTRIC
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Phone Number: 450-1695 Rick
Date 06/29/2007 Type Final Inspector Kevin Benner not approved
o,lso to include the Portal wirng that is not compliant and the XFMR wiring from previos consultations and inspections.
Date/Time requested: 06/28/2007 08:37 AM
Access:
Requested by: TOWN & COUNTRY ELECTRIC
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Notice Type: FC Ready Date/Time: 06/29/2007 00:00 AM
Phone Number: 450-1695 Rick
Date 07105/2007 Type Re Final Inspector Kevin Benner not approved
Receptacles to be relocated for luminaires that were relocated for equipment in lube center, flexible cord installation on radiant heat vent to
be reloacted, MC cable connector in Portal, Car Wash area "Wet Location' wiring, Emergency Lights being added per F.D.
Date/Time requested: 07/05/2007 06:58 AM
Access:
Requested by: TOWN & COUNTRY ELECTRIC
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Notice Type:
Ready Date/Time: 07/05/200706:58 AM
Phone Number: 450-1695 Rick
Electric Permit Work Card
Job Address 3245 S WASHBURN ST Permit Number 124619 Create Date 4/30/2007
Owner BERGSTROM FOX VALLEY INC Contractor TOWN & COUNTRY ELECTRIC
Service b New 0 Change 0 Temp . NIA Type 0 Overhead 0 Underground . NIA
Volts
Amps
Use/Nature
of Work
Circuits
luminaires
Value
$320,000.00
Switches Receptacles
642 - Commercial-New Building Wiring Auto Sales & Repair 1 New 34110 sf building. Job #524201.
Inspections:
Date Type Re Final Inspector Kevin Benner
For violations noted on 7/5/7 Inspection. This does not include the Car Wash Area which the State INspector does not agree with the
rchitects wet location area definition.
DatelTime requested: 07105/2007 06:28 PM
Access:
Requested by: TOWN & COUNTRY ELECTRIC
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Notice Type:
Ready DatelTime: 07105/200706:28 PM
Phone Number: 450-1695 Rick
Date 08/03/2007 Type Consultation Inspector Kevin Benner approved w/cond.
Review the wash bay with Brannan of Gries Arch. & the E.C.
Nitnessed the wash process and determined that the only item to be addressed would be the Emergency Luminaire needs to be protected.
Steve Schroeder from the E.C. stated that item would be shipped8/21n
DatelTime requested: 08/01/2007 08:23 AM
Access:
Requested by: Gries Architecture
o Reinspect Fee 0 Fee Wavied
Notice Type:
Ready DatelTime: 08/03/2007 09:00 AM
Phone Number: 722-2445 Brannan
o Reinspect Fee Paid
Type Re Final
Inspector Kevin Benner
approved
Date 08/24/2007
DatelTime requested: 08/23/2007 09:06 AM
Access:
Requested by: TOWN & COUNTRY ELECTRIC Steve Sch
o Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Notice Type:
Ready DatelTime: 08/24/2007 00:00 AM
Phone Number:
::;7/Et2/Et7 EtB:4B:27
:::
y
Faith Technplogies-}
192Et2365EtB4 92Et-73B-15l5
Page EtEtl
@
SHe s.ECTRlC
Fax Transmittal
To:
Company:
FaxNumber:
From:
Fax Number:
Phone Number
Time Sent :
Pages:
Description :
Kevin Benner
19202365084
steve Schroeder
920-738-8987
920-225-6500
Monday, Jul 2, 2007 08:48AM
2
Home Office: PO Box 627, Appleton, WI 54912-0627
Home Office Phone: 920-225-6500
www.faith-technologies.com
87/82/87 88:48:56
Faith Technologies->
19282365884 928-738-1515
Page 882
'8'" 'm" "[J,.....;A.,..'...'..B........E'........""El"",..
,"' . .. .. ....
. '.. .. .-. .".. .
.. ',' ',", , " '".
, '
. , . . ..,.. .. ..
" " " .,. .... " "".. ...
. . . -. ..
>,',S::: :a'::~:E' '..::,:"
, , ' ..'h".'.',... "I" 't' '.'
"... (liel " er. " ect:lc
110 Packerland Drive, Suite C-2
Green Bay, WI 54303-4861
Phone (920) 494-3313 Fax (859)-372-1830
June 29, 2007
To: Faith Technologies
Attn: Jeff Montour
Subject:
Bergstrom Toyota, Oshkosh WI
Stacked Transformers
This is regarding the stacking of two ventilated dry type transformers; catalog
number EE75T3H. The recommendation from engineering is to provide a
minimum of 36" clearflnce between to top of the bottom transformer and the
bottom of the top transformer.
Sincerely,
SQUARE D COMPANY
~f!1J~
R. C. Batson
Executive Field Engineer
J