Site: Plan Number: X8-1948-0407
Oshkosh Truck - South Plant
333 W 29th Ave
Oshkosh VVI 54902
For:
Description: Mezzanine Alterations
Object Type: Building only
Class of Construction: lIB -1239 Sq Ft.; Sprinklered
Occupancy: F: Factory / Industrial, B: Business /Office
Maximum No of Occupants: 100
The submittal described above has been reviewed for conformance with applicable VVisconsin Administrative Codes and
VVisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01 (10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) / Conditions:
· IDC 906.1/ IFC 906.3 The maximum travel distance allowed to a fire extinguisher is 75 feet.
· Comm 5.34 No person may perform structural welding unless the person holds a registration issued by
Department of Commerce. Provide welders registration numbers for all people doing welding on this
project.
· Comm 61.30(3) / IMC 507.2 This plan review does not include heating, ventilation, or air
conditioning. HV AC plans are required to be submitted and approved prior to installation ofRV AC
equipment.
· Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Comm 61.31(1).
· Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
1:\lllspcctiol1s\Plan Rev.lcw\C\1IT1mcrcial Pian Review 2.0()7\X8.19.~.8-(H07 333 W 29th Ave Bldg Only.doc
Page I of2
."(. ,r
A copy of the approved plans, specifications, and this letter shall be on-site during construction.
be obtained prior to connnencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
Bna oe
Building Systems Consultant
(920) 236-5051 Monday- Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.
bnoe@ci.oshkosh.wi.us
cc: Property file
Fee Required $
Fee Received $
Balance Due $
320.00