HomeMy WebLinkAboutHVAC X8-1959-0407
~
OJHKOIH
ON THE WATER
City of Oshkosh
Division ofInspection Services
215 Church Avenue
PO Box 1130
Oshkosh WI 54903-1130
www.ci.oshkosh.wi.us
April 16, 2007
Doug Geyer
HV AC Design Solutions LLC
W7094 Spencer Road
Appleton WI 54914
JJ Geffers
213 S Park Ave
Oshkosh, WI 54914
Site: Plan Number: X8-1959-0407
1528 Oregon St
Oshkosh WI 54902
For:
Description: HV AC alterations
Object Type: HV AC only
Class ofConstI1tction: VB - 3241 Sq Ft.; UnsprinkIered
Occupancy: M: Mercantile / Retail
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) / Conditions:
. IMC 307.1 Liquid combustion by-products of condensing appliances shall be collected and discharged to
an approved plumbing fixture or disposal area.
. IMC 403.3 [Comm 64.0403 (6)] Ventilation rate. Janitor closets. A janitor doset that has only one
service sink may be provided with either natural ventilation via a window or louvered opening with at least
2 square feet (0.2 m2) of area openable directly to the outside or mechanical exhaust ventilation as
specified in Table 64.0403. Plans submittedfor HVAC review do not show the required service sink
Comm 62.2900 (2) requires a service sink to be located in ajanitors closet, and the [MC requires
ventilation of that space. Provide revised plans showing how required ventilation will be provided.
. IECC 803.3.3.3 Off-hour controls. Each zone shall be provided with thermostatic setback controls that
are controlled by either an automatic time clock or programmable control system. Verify that equipment is
set up to run per the control requirements included in plans.
. IECC Comm 63.1029(4) Additional duct sealing. (a) General. Except as specified in par. (b),
ductwork and plenums shall be sealed in accordance with Table 63.1029-1, and shall meet the duct seal
classes specified in Table 63.1029-2. Verify that ductwork is properly sealed for the correct duct design
static pressure classification.
1:\Inspecli').Ils\Pbn .Review\Cormnen:iaJP1;m Review 2007\X3-1959.0407 1528 Or,'gon SI INAC Only.doc
Page 1 of2
. IFGC 401 /Comm 65.0400 All gas piping and gas piping installations shall comply with NFP A 54,
National Fuel Gas Code.
. IBC 1l01.2/ANSI A1l7.1-308.2 & 3 - Mechanical system controls shall be located a maximum of 48"
above the finished floor if the floor space allows a forward approach by a wheel chair or if the clear space
allows a parallel approach.
. Comm 61.31(4) Revisions to approved plans. All proposed revisions and modificatio.ns.whichinvolve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Comm 61.31(1).
. Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
~
~~
Building Systems Consultant
(920) 236-5051 Monday - Friday 7:30 AM. to 8:30 AM and 12:30 AM to 1 :30 P.M.
bnoe@ci.oshkosh.wi.us
cc: Property file
Fee Required $
Fee Received $
Balance Due $
300.00
300.00
0.00
l:\InspeCLillHs\Plan Revie-w\CUlnmen:iaJ Plan Rl;'vil;'w 200T..x8-1959-0407 1.528 Oregon SI nVAC Only.doc