City of Oshkosh
Division of Inspection Services
215 Church Avenue
PO Box 1130
Oshkosh WI 54903-1130
www.cLoshkosh.wi.us
ON THE WATER
April 12, 2007
Mike Oxley
WD Partners
909 Lake Carolyn Pkwy Ste 600
Irving TX 75039
Fred Jacques
Alliance Developement
601 Oregon St Ste A
Oshkosh, WI 54902
Site: Plan Number: X8-1946-0407
FedEx Kinkos
530 S Koeller St
Oshkosh WI 54902
For:
Description: Tenant space alterations
Object Type: Building and HV AC
Class of Construction: lIB -1992 Sq Ft.; sprinklered
. Occupancy: M: Mercantile I Retail
Maximum No of Occupants: 19
The submittal described above has been reviewed for conformance with applicable Wisconsin AdminiStrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance withall code requirements
Key Item(s) I Conditions:
. IBC 711.3 Any penetrations of fire rated assemblies are required to be protected with a listed firestopping
system that matches the rating of the wall assembly being penetrated. Copies of the firestopping systems
are required to be provided at the time of inspection.
. IFC 901.4 Fire protection systems shall be maintained in accordance with the original installation
standards for that system. Required fire protection systems shall be extended, altered, or augmented as
necessary to maintain and continue protection whenever the building is altered, remodeled or added to.
Alterations to fire protection systems shall be done in accordance with applicable standards.
. IBC 1003.2.11 Means of egress illumination is required to be installed per this section. All paths of egress
through The Retail Display area are required to have adequate emergency lighting to me~t the performance.
requirements ofIBC 1003.2.11.3. Including the exterior side of doors out of the space. Depending on
configuration of store displays additional emergency illumination may he required to comply with these
requirements.
Flnspediulls\Pbn Revinv\Cummercial Phm Review :Z007\X8- i 946.,(\407 530 S Kodler Si Bklg 8: IIVAC.doc
Page 1 of3
. IRC 1209.1 Provide toilet room floors with smooth, hard, nonabsorbent surface extending minimum 6
inches up onto walls. Sheet A-IO indicates a 4 inch Base - please change to the required 6 inch
. NEC 600.3 All electric signs shall be listed and installed in conformance with that listing. The listing label
shall be externally visible after installation. '
. NEC 600.6 Each sign shall have a disconnecting means in conformance with NEC600~6 .
. 1M C 302.1 The building or structure shall not be weakened by the installation of mechap.ical systems.
Verify that existing structure is capable of supporting the additional weight of the proposed roof top
equipment. Verify that the existing structure is capable of supporting the weight of the proposed rooftop
equipment.
. IMC 403.3 [Comm 64.0403 (6)] Ventilation rate. Janitor closets. A janitor closet that has only one
service sink may be provided with either natural ventilation via a window or louvered opening with at least
2 square feet (0.2 rn2) of area openable directly to the outside or mechanical exhaust vel}tilation as
specified in Table 64.0403. Plans submittedfor HVAC review do not show the required exhaustfor the
service sink included in building plans. Comm 62.2900 (2) requires a service sinkto be located in a
janitors closet, and the lMC requires ventilation of that space. Provide information /details showing
how required ventilation will be provided.
. IMC 606.2.1 Smoke detectors shall be installed in return air systems with a design capacity greater than
2000 cfm. . .. Verify that duct detectors are installed.
. IMC 606.4.1 The duct smoke detectors shall be connected to a fire alarm system. The actuation of a
smoke detector shall activate a visible and audible supervisory signal at a constantly attended location.
. IFGC 401/Comm 65.0400 All gas piping and gas piping installations shall comply with NFP A 54,
National Fuel Gas Code.
. IRC 1l01.2/ANSI A1l7.1-308.2 & 3 - Mechanical system controls shall be located a maximum of48"
above the finished floor if the floor space allows a forward approach by a wheel chair or if the clear space
allows a parallel approach.
. Comm 61.30(3) This review does not include lighting. Comm 63.0001 Prior to instalJation, lighting
plans and calculations shall be prepared in compliance with the code. The plans shall be available upon
request.
. Comm 61.31(4) Revisions to approved plans. All proposed revisions and modificatio)1swhich involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the of:qce that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Comm 61.31(1).
. Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
T:\Insp<:ctions\PlanReview\Commereial PhlJ'l Review 2007\X8.! 946.0407 530 S Kodltr SI Bkl!? & IIVAC.due
Page 2 00
· Comm 80 This plan review does not include plumbing. Prior to installation of plumbing, plans and
calculations are required to be submitted and approved.
· MUN 30 This review does not include review for sign age. Applications for and questions regarding
signage permits should be directed to Todd Muehrer - Associate Planner (920) 236-5057.
· MUN 30-35 (1)(5) All roof top and ground level mechanical equipment and utilities shall be fully screened
from view of any street or residential zoning district. Contact Todd Muehrer - Associate planner (920)
236-5057 for additional information on screening requirements. All screening shall be properly anchored
in place to resist wind loads. Additionally mc 1608.8 Roofprojections - Drift loads due to mechanical
equipment, penthouses, parapets and other projections above the roof shall be determined in accordance
with Section 7.8 of ASCE 7. No HVAC permit will be issued until screening plan has been approved.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to connnencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
B. rNoe
Building Systems Consultant
(920) 236-5051 Monday- Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.
bnoe@ci.oshkosh.wi.us
cc: Property file
Fee Required $
Fee Received $
Balance Due $
450.00
450.00
0.00
1:\.Inspedlol1s',Plan l'(eview\Commen:ial P].ll1
1007\X8-T 946-0407 :'530 S Koeller SI Bklg & IIVAC.doc