Site: Plan Number: X2-1884-0107
Shooters Bar & Nightclub
1014 Ohio St
Oshkosh WI 54902
For:
Description: HV AC System
Object Type: HVAC only
Class of Construction: IIIB - 6220 Sq Ft.; Sprinklered
Occupancy: A2: Assembly,
Maximum No of Occupants: 256
The submittal described above has beenreviewed for conformance with applicable Wisconsin Administr tive Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
. NOTE: This approval is limited to the space that is being finished at this time. It does not include e unoccupied
basement or the "future lease space" which will not be used. Future use of these spaces will require e-submittal of plans
for further review.
NOTE: Additionally the occupancy is limited to the 256 occupants as agreed to by the Owner due to the
resfuced amount of outside air being provided.
Key Item(s) I Conditions:
. City of Oshkosh Municipal Ordinance Section 14-1.2 "Smoking prohibited inside estarants"
Note: This plan has not been reviewed for complete compliance with this ordinance, as t does not include
information that addresses all the requirements for review. If there isa desire to create a separately
ventilated smoking room, additional plans are required to be submitted for review.
. IMC 606.2.1 Smoke detectors shall be installed in return air systems with a design cap city greater than
2000 cfm......
. IMC 606.4.1 The duct smoke detectors shall be connected to a fire alarm system. The ctuation of a
smoke detector shall activate avisible and audible supervisory signal at a constantly atte ded location.
IMC 606.4.1 Exception 2. In occupancies not required to be equipped with a fire ala system, actuation
of a smoke detector shall activate a visible and an audible signal in an approved locatio . Smoke detector
trouble conditions shall activate a visible or audible signal in an approved location and all be identifies
as air duct detector trouble. As no fire alarm system is being installed, verify complian e with both the
trouble and alarm notification requirements.
1:\"!nspedjolls\Pbn Review\('i)mmen:iaJ Pl:;n Review:2007\X2-1 :<'8...-0 i 07-H 101.+ Ohio 5t IIVAC Only.doc
P ge 1 of2
. NEC 110.26 Spaces About Electrical Equipment. Sufficient access and working spa e shall be
provided and maintained about all electric equipment to permit ready and safe operation and maintenance
of such equipment. Plans do not indicate location of electrical service or equipment - erify that the
appropriate clearances required by this section are being maintained
. IECC 803.2.8 [Comm 63.0803 (2) (f)] Duct and plenum insulation and sealing.
1. Supply and return air ducts and plenums. Except as specified in subd. 2., all supply, ucts and return,
air ducts and plenums shall be insulated with a minimum ofR-4 insulation when loc ted in
unconditioned spaces and with a minimum of R-7.5 insulation when located outs'de the buildin
envelope. When located within a building envelope assembly, the duct or plenum s all be separated
from the building exterior or unconditioned or exempt spaces by a minimum ofR-7. insulation. All
supply ducts located in plenums within the building envelope shall be insulated to R 4.
2. Exceptions:
a. When located within equipment.
b. When the design temperature difference between the interior and exterior ofthe.d ct or plenum does
not exceed 150P (-8C).
3. Joints, longitudinal and transverse seams, and connections. Joints, longitudinal and t ansverse seams,
and connections in ductwork shall be sealed in accordance with s. Comm 63.1029 (4).
. Plans do not show any details for duct work located on the exterior - verify that this i installed in
compliance with code requirements.
. Comm 61.31(4) Revisions to approved plans. All proposed revisions and modificatio s which involve
rules under this code and which are made to construction documents that have previousl been granted
approval by the department or its authorized representative, shall be submitted to the offi e that granted the
approval. All revisions and modifications to plans shall be approved in writing by the d partment or its
authorized representative prior to the work involved in the revision or modification bein carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in ccordance with
Comm 61.31(1).
. Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervi ing professional
shall file a compliance statement form SBD-9720 with this office.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All pe 'ts are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 10 1.12( , nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or compone t.
)
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
~Respe,.. . ~
- k:.
-~
BnallNoe
Building Systems Consultant
(920) 236-5051 Monday- Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.