HomeMy WebLinkAboutHVAC U4-70-0706-H2 Revised
~
OJHKOfH
City of Oshkosh
Division of Inspection Services
215 Church Avenue
PO Box 1 130
Oshkosh WI 54903-1 130
www.ci.oshkosh.wi.us
ON THE WArER
February 26, 2007
Joel Clary
Summit Design LLC
W6744 Rogersville Rd
Fond du Lac, WI 54937
Ryan Meyers
Oshkosh Truck
2307 Oregon St
Oshkosh, WI 54903
Site: Plan Number: U4-70-0706-H2
Oshkosh Truck
2737 Harrison St
Oshkosh WI 54901
For:
Description: Revised HV ACfor 2nd floor remodel of office bldg
Object Type: HV AC only
Class of Construction: lIB - 8200 Sq Ft.; sprinklered
Occupancy: B: Business I Office
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) I Conditions:
· NEC 110.26 Spaces About Electrical Equipment. Sufficient access and working space shall be
provided and maintained about all electric equipment to permit ready and safe operation and maintenance
of such equipment. Caution -on clearances around VA V 's installed above ceiling.
· IMC 606.4.1 The duct smoke detectors shall be connected to a fire alarm system. The actuation of a
smoke detector shall activate a visible and audible supervisory signal at a constantly attended location.
· IECC 803.2.9 Piping insulation. All piping serving as part of a heating or cooling system shall be
thermally insulated in accordance with Section 803.3.7/ Comm 63.1029.
· Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification toa plan, drawing or specification shall be signed and sealed in accordance with
Comm 61.31(1).
hlm;pc:diol1s\Pbn Review\Cnmmerl'ial Plan Revi",w ::007\U4-70-0706-H2 2737Uarrison St H,'vi,ed HVAC Only.d()c
Page 1 of2
· Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
~
B=n Noe
Building Systems Consultant
(920) 236-5051 Monday- Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.
bnoe@ci.oshkosh.wLus
cc: Property file
Pee Required $
Fee Received $
Balance Due $
150.00
150.00
0.00
l:\hbpectiUr!s\Plan Hevinv\Cornrnerc.ial nom Review 2(107\U4-7(l-(l706-H2 2737 IIarrison St l<kvi:::ed IIVAC Only.do<;
Page 2 of2