February 21,2007
Richard Fisher
Fisher & Associates, LLC
642 Tholsen Dr
Kimberly, WI 54136
Ron Detj en
Landmark LTD III
PO Box 2366
Oshkosh, WI 54903
Site: Plan Number: X4-1908-0207
Martial Arts America
300 S Koeller St Suite C-2
Oshkosh WI 54902
For:
Description: Tenant space alterations
Object Type: Building only
Class of Construction: lIB - 1653 Sq Ft.; Sprinklered
Occupancy: M: Mercantile I Retail
Maximum No of Occupants: 100
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
NOTE: The unoccupied space that is being provided with a set of doors as per fax received on 2/21/07 is not to be used
as an occupied space unless additional plans are submitted for review and approval.
Key Item(s) I Conditions:
. IBC901.2 Fire protection systems shall be installed, repaired, operated and maintained in accordance with
this code and the international fire code. Construction of new walls may require the addition and or
relocation of sprinkler heads to maintain required coverage, and not obstruct spray patterns of fire
sprinklers.
. IBC 906.1 / IFC 906.3 The maximum travel distance allowed to a fire extinguisher is 75 feet.
. IBC 1003.2.2.5 Posting of occupant load. Every room or space that is an assembly occupancy shall have
the occupant load of the room or space posted in a conspicuous place, near the main exit access doorway
from the room or space. Posted signs shall meet the requirement of municipal code section 13-5. Min 12
inches in length, min 4 inches in height with min Yz inch lettering and the numbers being minimum 3
inches in height. The sign shall state "Limit (number) Persons".
. IBC 1003.2.10 Exit signs are required to be installed per this section
.Re'vje\\'\Co~Dmercial Pltli1
2(i07\X4-190S-{)207 300 5 Kocj)er 51 13kl" Only.do<:
Page 1 00
. IBC 1003.2.11 Means of egress illumination is required to be installed per this section. All paths of egress
are required to have adequate emergency lighting to meet the performance requirements of IBC
1003.2.11.3. Provide complete emergency lighting plan showing compliance with these requirements
prior to installation of emergency lighting system. Additionally emergency lighting is required to be
provided for the new egress path in the unoccupied storage space.
. 1004.2.3 Egress through intervening spaces. Egress from a room or space shall not pass through
adjoining or intervening rooms or areas, except where such adjoining rooms or areas are accessory to the
area served; are not a high-hazard occupancy; and provide a discernible path of egress travel to an exit.
Egress shall not pass through kitchens, store rooms, closets or spaces used for similar purposes. An exit
access shall not pass though a room that can be locked to prevent egress. Means of egress from dwelling
units or sleeping areas shall not lead through other sleeping areas, toilet rooms or bathrooms. Verify that
egress path is maintained through the "Preparation Area"
. IBC 1004.3.2.1 Construction Corridors (the rear egress path is considered a corridor.) shall be fire-
resistance rated in accordance with Table 1004.3.2.1. The corridor walls required to be fire-resistance-rated
shall comply with Section 708 for fire partitions.
Table 1004.3.2.1 Exception c. Buildings equipped throughout with an automatic sprinkler system in
accordance with Section 903.3.1.1 or 903.3.1.2. This will require the monitorin!! and alarms per
Section 903.4 this includes ALL valves controllin!! water supplv. .
. IBC 2406.2 Glazing in an individual fixed or operable panel adjacent to a door where the nearest exposed
edge of the glazing is within a 24 inch arc of either vertical edge of the door in a closed position and where
the bottom exposed edge of the glazing is less than 60 inches above the walking surface is requires safety
glazing materials.
. Comm 61.30(3) This review does not include lighting. Corom 63.0001 Prior to installation, lighting
plans and calculations shall be prepared in compliance with the code. The plans shall be available upon
request.
. Comm 61.30(3) / IMC 507.2 This plan review does not include heating, ventilation, or air
conditioning. HVAC plans are required to be submitted and approved prior to installation ofHV AC
equipment.
. Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Cornm 61.31(1).
]:'.!nspediuDs\Pbn .Revil:'w\Commen:ial I'1;m Ro:vit:w 2007\X4-1903-0207 300 S Rodier StBldg Only.do,-
Page 2 of3
SUBMIT:
. Cornm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
. IBC 1003.2.11 Means of egress illumination is required to be installed per this section. All paths of egress
are required to have adequate emergency lighting to meet the performance requirements of IBC
1003.2.11.3. Provide complete emergency lighting plan showing compliance with these requirements
prior to installation of emergency lighting system.
. NFP A 72 4.5.2 Provide a copy of the fire alarm system record or completion for the required monitoring
and alarms of the automatic fire sprinkler system
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
e
Building Systems Consultant