Loading...
HomeMy WebLinkAbout2006-Emergency Power Page 1 of 2 Noe, Brian From: Noe, Brian Sent: Friday, October 13, 2006 11:42 AM To: 'Kari @me pe.com' Cc: Benner, Kevin Subject: RE: Renaissance Emergency Power Kari, As long as no electrical life support equipment is required, then a Type 3 system is acceptable. If any electrical life support equipment is required you would need to provide a Type 1 system per NFPA 99 14.3.4.2.1. If in fact it is determined that all that is required is the Type 3 system, then NFPA 99 4.6.1.1 requires that generators conform to requirements of 4.4.1.1 NFPA 99 and NFPA 101 do not specify fuel capacity or run time for generators. NFPA 70 Section 700.12(B)(2) does require a minimum fuel supply of 2 hours for legally required standby emergency generators. You may also want to contact HFS as they may have additional licensing requirements that may apply. Please call me to discuss the type of system you are proposing to install. Based on the plans we have on file it appears that a Type 1 system had been planned. Brion Noe City of Oshkosh Building Systems Consultant (920) 236 -5051 Original Message From: Benner, Kevin Sent: Thursday, October 12, 2006 1:49 PM To: Noe, Brian Subject: FW: Renaissance Emergency Power Original Message From: Kari Gehde [mailto:Kari @me- pe.com] Sent: Thursday, October 12, 2006 1:47 PM To: kbenner @ci.oshkosh.wi.us Subject: FW: Renaissance Emergency Power Kari Gehde Electrical Designer Muermann Engineering 0/13/2006 Page 2 of 2 116 Fremont St. Box 235 Kiel, Wi 53042 -0235 Phone (920) 894 -7800 ext 111 Fax (920) 894 -7916 From: Kari Gehde Sent: Thursday, October 12, 2006 1:45 PM To: 'kbenner @cioshkosh.wi.us' Cc: Fred Muermann mrobbins @hoffman.net Subject: FW: Renaissance Emergency Power Good afternoon Kevin, We have a project in Oshkosh called The Renaissance Center. It has 11,700 square of Practice /Clinic space and 12,500 square feet of Ambulatory Surgery Center space. The projects address is 2400 Witzel Ave. The specified Generator is 250 KW diesel with a sub base fuel tank We would like to verify our assumption regarding required run -time for the generator i.e. this determines the size of the fuel tank). We would like to confirm that we had interpreted the codes correctly. This facility is an Ambulatory Heath Care under NFPA 101 Chapter 3.3.134.1. Under 20.2.9.2, an essential electrical system was provided in accordance with NFPA 99 (Standard for Health Care Facilities). From NFPA 99 Chapter 14 Other Health Care Facilities 14.3.4.2 The essential electrical distribution system shall conform to type 3 system as described in chapter 4 From Chapter 4 (4.4.1.72) Type 3 essential electrical system power sources shall be classified as Type 10, Class X, generator sets per NFPA 110, Standard for emergency and Standby power systems. Class X defines the required run time for this generator NPPA 110 Chapter 4 Classifications of emergency power supply systems (EPSSs). Table 4.1(a) Classifications of EPSSs Class X Other time, in hours as required by the application code, or user. We have assumed that the life safety code for emergency lighting of 1 1/2 hours is the required run time, the owner has indicated that no procedure preformed at the facility would last longer than one hour. Would it be your opinion that if the generator ran for at least 1 1/2 hours that the code is satisfied? Kind regards, Kari Gehde Electrical Designer Muermann Engineering 116 Fremont St. Box 235 Kiel, Wi 53042 -0235 Phone (920) 894 -7800 ext 111 Fax (920) 894 -7916 10/13/2006 Page 1 of 2 Noe, Brian From: Benner, Kevin Sent: Thursday, October 12, 2006 1:49 PM To: Noe, Brian Subject: FW: Renaissance Emergency Power Original Message From: Kari Gehde [mailto:Kari @me- pe.com] Sent: Thursday, October 12, 2006 1:47 PM To: kbenner @ci.oshkosh.wi.us Subject: FW: Renaissance Emergency Power Kari Gehde Electrical Designer Muermann Engineering 116 Fremont St. Box 235 Kiel, Wi 53042 -0235 Phone (920) 894 -7800 ext 111 Fax (920) 894 -7916 From: Kari Gehde Sent: Thursday, October 12, 2006 1:45 PM To: 'kbenner @cioshkosh.wi.us' Cc: Fred Muermann mrobbins @hoffman.net Subject: FW: Renaissance Emergency Power Good aftemoon Kevin, We have a project in Oshkosh called The Renaissance Center. It has 11,700 square of Practice /Clinic space and 12,500 square feet of Ambulatory Surgery Center space. The projects address is 2400 Witzel Ave. The specified Generator is 250 KW diesel with a sub base fuel tank We would like to verify our assumption regarding required run -time for the generator i.e. this determines the size of the fuel tank). We would like to confirm that we had interpreted the codes correctly. This facility is an Ambulatory Heath Care under NFPA 101 Chapter 3.3.134.1. Under 20.2.9.2, an essential electrical system was provided in accordance with NFPA 99 (Standard for Health Care Facilities). From NFPA 99 Chapter 14 Other Health Care Facilities 14.3.4.2 The essential electrical distribution system shall conform to type 3 system as described in chapter 4 From Chapter 4 (4.4.1.72) Type 3 essential electrical system power sources shall be classified as Type 10, Class X, generator sets per NFPA 110, Standard for emergency and Standby power systems. Class X defines the required run time for this generator NPPA 110 Chapter 4 Classifications of emergency power supply systems (EPSSs). Table 4.1(a) Classifications of EPSSs Class X Other time, in hours as required by the application code, or user. We have assumed that the life safety code for emergency lighting of 1 1/2 hours is the required run time, the owner has indicated that no 10/12/2006 Page 2 of 2 procedure preformed at the facility would last longer than one hour. Would it be your opinion that if the generator ran for at least 1 1/2 hours that the code is satisfied? Kind regards, Kari Gehde Electrical Designer Muermann Engineering 116 Fremont St. Box 235 Kiel, Wi 53042 -0235 Phone (920) 894 -7800 ext 111 Fax (920) 894 -7916 10/12/2006 1 Article 700 Emergency Systems 700.12 '..,'8) Be a cable listed to maintain circuit integrity for not tems include electrical circuit protective systems (FHIT), less than 1 hour when installed in accordance with the electrical circuit protective materials (FHIY), and fire-re- 4, listing requirements sistive cables (FHJR). Feeder- Circuit Equipment Equipment for feeder cir- (2) Listed Thermal Barrier Systems. These systems c''ts (including transfer switches, transformers, and pan- are described in the UL Building Materials Directory as ,oards) shall be located either in spaces fully protected thermal barrier systems (XCLF). Examples of the thermal roved automatic fire suppression systems (including barrier protection technique include batts and blankets ay app PP y C g P q n- ,rin1ders, carbon dioxide systems) or in spaces with a (XCLR), packing material (XCMD), and preformed mineral i i hour fire resistance rating. and fiber units (XCMK) wrapped or otherwise formed over III the conduit to achieve a predetermined fire rating. FY N: For the definition of occupancy classification, see Section 6.1 of NFPA 101 -2003, Life Safety Code. (3) Fire -Rated Assembly. These systems are de- scribed in the UL Fire Resistance Directory, Volumes 1 and e proper operation of emergency electrical systems is 2. The assemblies found in Volume 1 include hourly ratings t ical for densely populated occupancies and for high -rise for beams, floors, roofs, columns, and walls and partitions. pupancies. Therefore, fire protection requirements for both Volume 2 of the directory includes hourly ratings for joint x ergency system feeder circuits and equipment ensure the systems and through penetration firestop systems. All fire ,itegrity as well as the performance of the emergency electri- ratings and fire resistance ratings are based on the assump- system. If feeders and equipment are located in buildings tion that the structural supports for the assembly are not ,,ttt are fully protected by an approved fire suppression impaired by the fire. 725 .'stem, then no further fire protection techniques are gener- SIGNi required. (4) Embedded in Concrete. Embedding a conduit in CIRCI S rinkler s stems are the most common fire su ression concrete is most effective when implemented during original P y PP construction. This method has been successful for many 760 and they are covered in NFPA 13, Standard for the FIRE years in protecting premises from service conductors. Ac- 'i "stallation of Sprinkler Systems. Buildings that are full cording to 230.6, conductors embedded in not less than 2 arotected by automatic sprinkler systems meet the require in. of concrete are considered to be outside the building. 77 11ents of 700.9(D). Additional fire suppression systems are OF FII ;�3 luded in the following standards: (5) Cables Listed to Maintain Circuit Integrity. Cir- cuit integrity cables are classified by the UL Building Materi- NFPA 11, Standard for Low-, Medium and High- 8 als Directory under the existing product category of fire- C ;Ex Foam resistive cables (FHJR). C NFPA 12, Standard on Carbon Dioxide Extinguishing Systems NFPA 12A, Standard on Halon 1301 Fire Extinguishing It is important to understand the difference between a 1 i Systems hour fire rating of an electrical cable and a 1 -hour fire resis it4, NFPA 15, Standard for Water Spray Fixed Systems for tance rating of a structural member, such as a wall. Simply Fire Protection stated, at the end of a 1 -hour fire rating test on an electrical NFPA 17, Standard for Dry Chemical Extinguishing cable, the circuit and its insulation must be intact and electri- 1/ S y s tems tally functioning. (No short circuits, grounds, or opens are 6. NFPA 2001, Standard on Clean Agent Fire Extinguish permitted.) However, a wall subjected to a 1 -hour fire resis- I itag Systems tance test must only prevent a fire from passing through or past the wall, without regard to damage to the wall. If feeders and equipment are not located in buildings hat are fully protected by an approved fire suppression III. Sources of Power t: ystem, other methods and protection techniques are avail- 01e to comply with the fire protection requirements of 700.12 General Requirements k ,00.9(D)(2). These additional fire protection methods and Current supply shall be such that, in the event of failure of ii echniques include the following. the normal supply to, or within, the building or group of (1) buildings concerned, emergency lighting, emergency OListed Electrical Circuit Protective Sy stems g g Y g g� ower, P These systems are described in the UL Building Materials or both shall be available within the time required for the rectory. The four letter code (shown in parentheses) fol- application but not to exceed 10 seconds. The supply system lowing each category heading in the directory is the UL for emergency purposes, in addition to the normal services t tip., category guide designation. Examples of these sys- to the building and meeting the general requirements of this section, shall be one or more of the types of systems de- 17 National Electrical Code Handbook 2005 1059 Article 700 Emergency Systems 700.12 (:l) Battery Power and Dampers Where a storage battery ensure operation when the engine -driven generator operates. i used for control or signal power or as the means of starting These additional loads require the system designer to ensure the prime mover, it shall be suitable for the purpose and that the engine -driven generator is of adequate capacity in shall be equipped with an automatic charging means inde- accordance with 700.5(A). pendent of the generator set. Where the battery charger is required for the operation of the generator set, it shall be connected to the emergency system. Where power is required (5) Auxiliary Power Supply Generator sets that require for the operation of dampers used to ventilate the generator more than 10 seconds to develop power shall be permitted set, the dampers shall be connected to the emergency system. if an auxiliary power supply energizes the emergency system until the generator can pick up the load. Engine -driven generators that are not equipped with an al- ternator to provide battery charging require a separate bat- Exhibit 700.3 illustrates a typical generator installation sup- t system. Failure of the power supply to a plying standby power. battery- charging system or failure of the battery- charging system itself could render the engine -driven generator inop- erable. The second sentence of 700.12(B )(4) ensures that (6) Outdoor Generator Sets Where an outdoor housed the charging system always has power. generator set is equipped with a readily accessible discon- Ventilation dampers may require electrical power in necting means located within sight of the building or struc- order to operate. If this is the case, 700.12(B)(4) also requires ture supplied, an additional disconnecting means shall not them to be powered by the emergency power source to be required where ungrounded conductors serve or pass through the building or structure. 725 SIGNAL CIRCer n 760 FIRE Al SYSTEI ac feed from dc feed to 770 normal utility battery Silencer OPT engine ,--To load ft 1 \i FIBS start Emergency feed Inlet air control ��r� ®a- 80( opening r�'�,' Wall thimble COI Automatic i t ransfer switch CIR I im —1 Flexible conduits I Supports Drain 8', '1 ®o I Flexible Flexible duct 90 I coupling �1 i u� I g, „„I Outlet air TA opening Engine .P t/ C I Battery o charg generator Z��. i� T control t O il R T "---y 'I Day tank so' Main fuel 8 '1 i M I' o' L�"�e/ s Normal utility feed Generator- 1 fuel lines gauge T mounted R eturn line C circuit L I breaker X11 4 P II ac Jacket 1 Main Vibration isolators water heater fuel tank Batteries 1 Suction line Typical Generator Installation Exhibit 700.3 A typical generator installation supplying standby power in ratings from 55 kW to 930 kW, 60 Hz. (Courtesy of Caterpillar) National Electrical Code Handbook 2005 1061 700.12 Article 700 Emergency Systems scribed in 700.12(A) through 700.12(E). Unit equipment careful evaluation of the variables at each particular in- (4) B in accordance with 700.12(F) shall satisfy the applicable stallation. is use requirements of this article. the p] In selecting an emergency source of power, consider- (A) Storage Battery Storage batteries used as a source of shall ation shall be given to the occupancy and the type of service power for emergency systems shall be of suitable rating and pende to be rendered, whether of minimum duration, as for evacua- capacity to supply and maintain the total load for a minimum requit period of 1'/2 hours, without the volts tion of a theater, or longer duration, as for supplying emer- P voltage applied to the load conne gency power and lighting due to an indefinite period of current falling below 87'h percent of normal. for th ail from trouble either inside or outside the building. Batteries, whether of the acid or alkali type, shall be set, th Equipment shall be designed and located so as to mini- designed and constructed to meet the requirements of emer- Ili the hazards that might cause complete failure due to gency service and shall be compatible with the charger for flooding, fires, icing, and vandalism. that particular installation. Engin For a sealed battery, the container shall not be required ternat to be transparent. However, for the lead acid battery that tery -c An alternate source of power must be designed and located batter such that it is not exposed to hazards that could impair its requires water additions, transparent or translucent jars shall be furnished. Automotive -type batteries shall not be used. sy stet reliability. Such hazards include fire, flooding, icing, and enable vandalism. See Exhibit 700.2. An automatic battery charging means shall be provided. the ch (B) Generator Set order s f$ (1) Prime Mover Driven For a generator set driven by a them prime mover acceptable to the authority having jurisdiction and sized in accordance with 700.5, means shall be provided for automatically starting the prime mover on failure of the p normal service and for automatic transfer and operation of all i Z' required electrical circuits. A time -delay feature permitting a I 15- minute setting shall be provided to avoid retransfer in case of short-time reestablishment of the normal source. a nc j y (2) Internal Combustion as Prime Movers Where inter- nal combustion engines are used as the prime mover, an on- I ,,r site fuel supply shall be provided with an on- premise fuel P' supply sufficient for not less than 2 hours' full- demand I "L operation of the system. Where power is needed for the operation of the fuel transfer pumps to deliver fuel to a T,''''',-y. generator set day tank, this pump shall be connected to the Exhibit 700.2 Alternate source of power in a heated and secure emergency power system. building that is located in an area not subject to flooding. Engine -driven generators that require a fuel pump may not start or continue operating if the fuel pump is not operating_ Equipment for sources of power as described in The last sentence of 700.12(B)(2) ensures that fuel transfe 700.12(A) through 700.12(E) where located within assembly pumps have power when needed. occupancies for greater than 1000 persons or in buildings above 23 m (75 ft) in height with any of the following occupancy classes assembly, educational, residential, de- (3) Dual Supplies Prime movers shall not be solely depen- tention and correctional, business, and mercantile shall dent on a public utility gas system for their fuel supply or be installed either in spaces fully protected by approved municipal water supply for their cooling systems. Mean' automatic fire suppression systems (sprinklers, carbon diox- shall be provided for automatically transferring from one ide systems, and so forth) or in spaces with a 1 -hour fire fuel supply to another where dual fuel supplies are used. rating. Exception: Where acceptable to the authority having lli FPN No. 1: For the definition of occupancy classifica- diction, the use of other than on -site fuels shall be permitted tion, see Section 6.1 of NFPA 101 2003, Life Safety Code. where there is a low probability of a simultaneous fail iul` FPN No. 2: Assignment of degree of reliability of the of both the off -site fuel delivery system and power from tlu 1 recognized emergency supply system depends on the outside electrical utility company. 1060 2005 National Electrical Code Han' Emergency Generator Requirements, Ambulatory Surgical Centers Page 1 of 2 Department of Health Family Services Topics A -Z I Programs Services I Partners Providers I Reference Center I Search If You Have Complaints Emergency Generator Requirements about Wisconsin Health Care PDF Version of 99 -030. (PDF, 6 KB) Information Introduction Providers Contacts 1 What's_ Happening 1 Publications 1 about Bureau of Quality Related Sites Assurance (BQA) (608) 266 -8481 BQA web DATE: May 21, 1999 DSL- BQA -99 -030 Pages TO: Ambulatory Surgical Centers ASC 3 BQA Facility Directories FROM: Rita Prigioni, Interim Director, Bureau of Quality Assurance BQA Provider Training Enclosed is a copy of Life Safety Code Regional Program Letter No. 99 -01 [not available via the Internet] which is intended to clarify the BQA Numbered requirements of an emergency generator in ambulatory surgical Memos centers (ASCs). DHFS Forms This Regional Program Letter indicates that each facility currently Wisconsin participating in the Medicare program as an ASC is required [42 CFR Nurse Aide 416.44 (exit DHFS)] to meet the Life Safety Code (LSC) of the National Training and Fire Protection Association (NFPA). The 1985 LSC and 1991 LSC Registry Info require compliance with NFPA 99; hence, a generator is required for Caregiver those facilities admitting patients requiring electrical life support or Program/ where inhalation anesthetics are administered. Background Checks The Health Care Financing Administration (HCFA) is considering Wisconsin adoption of the 1997 LSC. Once adopted, all new and existing ASCs in Adult Programs the program will be required to meet NFPA 99, which requires a Caregiver generator in all facilities with critical care areas (i.e. operating rooms). Misconduct Registry One exception exists; see the attachment. Wisconsin Please reference NFPA 110 for emergency generator inspection and Medicaid monthly testing requirements and NFPA 72 for emergency generator Provider Information fuel supply capacity and sources. If you have any questions, please contact your Bureau of Quality Assurance engineer. Romaine Western Regional Office (Eau (715) 836 -6751 Anderson Claire) http: /dhfs. wisconsin. gov /rl_DSL /AmbSgyCtr /ASC99030.htm 10/13/2006 Emergency Generator Requirements, Ambulatory Surgical Centers Page 2 of 2 Ganesh Southeastern Regional Office (414) 227 -2004 Shrestha (Milwaukee) Keith Weitner Southeastern Regional Office (414) 227 -2003 (Milwaukee) George Southern Regional Office (608) 243 -2376 Gunderson (Madison) Kevin Joyce Northeastern Regional Office (920) 448 -5256 (Green Bay) John Rutt Northern Regional Office (715) 365 -2803 (Rhinelander) Tom Ankeny Central Office (Madison) (608) 243 -2029 Jon Cechvala Central Office (Madison) (608) 243 -2037 Ron Hoffiand [replaced by Richard Central Office (Madison) (608) 266 -7474 Batchelder, (414) 220- 5306] David Soens Central Office (Madison) (608) 261 -5993 Lynn Wallace Central Office (Madison) (608) 243 -2069 PDF: The free Acrobat Reader® software is needed to view and print portable document format (PDF) files. Learn more. It Back to top 1 About I Contact I Disclaimer 1 Privacy Notice 1 Feedback Wisconsin Department of Health and Family Services Protecting and promoting the health and safety of the people of Wisconsin http: dhfs. wisconsin.gov /rl_DSL /AmbSgyCtr/ASC99030.htm 10/13/2006 DATE: May 21, 1999 DSL- BQA -99 -030 TO: Ambulatory Surgical Centers ASC 3 FROM: Rita Prigioni, Interim Director Bureau of Quality Assurance Emergency Generator Requirements Enclosed is a copy of Life Safety Code Regional Program Letter No. 99 -01 which is intended to clarify the requirements of an emergency generator in ambulatory surgical centers (ASCs). This Regional Program Letter indicates that each facility currently participating in the Medicare program as an ASC is required [42 CFR 416.44] to meet the Life Safety Code (LSC) of the National Fire Protection Association (NFPA). The 1985 LSC and 1991 LSC require compliance with NFPA 99; hence, a generator is required for those facilities admitting patients requiring electrical life support or where inhalation anesthetics are administered. The Health Care Financing Administration (HCFA) is considering adoption of the 1997 LSC. Once adopted, all new and existing ASCs in the program will be required to meet NFPA 99, which requires a generator in all facilities with critical care areas (i.e. operating rooms). One exception exists; see the attachment. Please reference NFPA 110 for emergency generator inspection and monthly testing requirements and NFPA 72 for emergency generator fuel supply capacity and sources. If you have any questions, please contact your Bureau of Quality Assurance engineer. Romaine Anderson Western Regional Office (Eau Claire) (715) 836 -6751 Ganesh Shrestha Southeastern Regional Office (Milwaukee) (414) 227 -2004 Keith Weitner Southeastern Regional Office (Milwaukee) (414) 227 -2003 George Gunderson Southern Regional Office (Madison) (608) 243 -2376 Kevin Joyce Northeastern Regional Office (Green Bay) (920) 448 -5256 John Rutt Northern Regional Office (Rhinelander) (715) 365 -2803 Tom Ankeny Central Office (Madison) (608) 266 -7577 Jon Cechvala Central Office (Madison) (608) 266 -1758 Ron Hoffland Central Office (Madison) (608) 266 -7474 David Soens Central Office (Madison) (608) 261 -5993 Lynn Wallace Central Office (Madison) (608) 267 -0468 Attachment Page 1 of3 Noe, Brian From: Fred Muermann [Fred@me-pe.com] Sent: Monday, October 16, 2006 2:16 PM To: bnoe@cLoshkosh.wLus Cc: Kari Gehde Subject: FW: Renaissance - Emergency Power - 2..~t:D ~,,'2..~ ~6' Brian You are correct the generator will be a type 1, we did not originally indicate the the Emergency stop button which is required for a type one it will now be shown Kind regards Fred Muermann President Muermann Engineering 116 Fremont St. Kiel, WI 53042 Phone 920.894.7800 Fax 920.894.7916 From: Noe, Brian [mailto:bnoe@ci.oshkosh.wi.us] Sent: Friday, October 13, 2006 11:42 AM To: Kari Gehde Cc: Benner, Kevin Subject: RE: Renaissance - Emergency Power Kari, As long as no electrical life support equipment is required, then a Type 3 system is acceptable. If any electrical life support equipment is required you would need to provide a Type 1 system per NFPA 99 - 14.3.4.2.1. If in fact it is determined that all that is required is the Type 3 system, then NFPA 99 -4.6.1.1 requires that generators conform to requirements of 4.4.1.1 NFPA 99 and NFPA 101 do not specify fuel capacity or run time for generators. NFPA 70 Section 700.12(B)(2) does require a minimum fuel supply of 2 hours for legally required standby emergency generators. You may also want to contact HFS as they may have additional licensing requirements that may apply. Please call me to discuss the type of system you are proposing to install. Based on the plans we have on file it appears that a Type 1 system had been planned. 11/2/2006 Page 2 of3 Brian Noe City of Oshkosh Building Systems Consultant (920) 236-5051 -----Origina I Message----- From: Benner, Kevin Sent: Thursday, October 12, 2006 1:49 PM To: Noe, Brian Subject: FW: Renaissance - Emergency Power -----Original Message----- From: Kari Gehde [mailto:Kari@me-pe.com] Sent: Thursday, October 12, 2006 1:47 PM To: kbenner@ci.oshkosh.wi.us Subject: FW: Renaissance - Emergency Power Kari Gehde Electrical Designer Muermann Engineering 116 Fremont St. Box 235 Kiel, Wi 53042-0235 Phone (920) 894-7800 ext 111 Fax (920) 894-7916 From: Kari Gehde Sent: Thursday, October 12, 2006 1:45 PM To: 'kbenner@cioshkosh.wi.us' Cc: Fred Muermann ; mrobbins@hoffman.net Subject: FW: Renaissance - Emergency Power Good aftemoon Kevin, We have a project in Oshkosh called The Renaissance Center. It has 11,700 square of Practice/Clinic space and 12,500 square feet of Ambulatory Surgery Center space. The projects address is 2400 Witzel Ave. The specified Generator is 250 KW diesel with a sub base fuel tank We would like to verify our assumption regarding required run-time for the generator ( i.e. this determines the size of the fuel tank). We would like to confirm that we had interpreted the codes correctly. This facility is an Ambulatory Heath Care under NFPA 101 - Chapter 3.3.134.1. Under 20.2.9.2, an essential electrical system was provided in accordance with NFPA 99 (Standard for Health Care Facilities). From NFPA 99 - Chapter 14 Other Health Care Facilities 14.3.4.2 - "The essential electrical distribution system shall conform to type 3 system as described in chapter 4 " . From Chapter 4 (4.4.1.72) .. Type 3 essential electrical system power sources shall be classified as Type 10, Class X, generator sets per NFPA 110, Standard for emergency and Standby power systems. " 11/2/2006 , Page 3 of3 Class X defines the required run time for this generator NPPA 110 - Chapter 4 - Classifications of emergency power supply systems (EPSSs). Table 4.1 (a) Classifications of EPSSs - Class X = Other time, in hours as required by the application code, or user. We have assumed that the life safety code for emergency lighting of 1 1/2 hours is the required run time, the owner has indicated that no procedure preformed at the facility would last longer than one hour. Would it be your opinion that if the generator r~n for at least 1 1/2 hours that the code is satisfied? Kind regards, Kari Gehde Electrical Designer Muermann Engineering 116 Fremont St. Box 235 Kiel, Wi 53042-0235 Phone (920) 894-7800 ext 111 Fax (920) 894-7916 11/2/2006