OJHKOfH
City of Oshkosh
Division ofInspection Services
215 Church Avenue
PO Box 1130
Oshkosh WI 54903-1130
www.cLoshkosh.wi.us
ON THE WATER
February 16,2007
Thomas Karrels
Thomas R. Karrels P.E. S.C
1934 Algoma Blvd.
Oshkosh, VVI5490l
Pete Zwirchitz
Oshkosh Truck
2307 Oregon St
Oshkosh, VVI 54903
Site: Plan Number: U4-70-0706-R
Oshkosh Truck
2737 Harrison St
Oshkosh VVI 54901
For:
Description: 2nd floor remodel of office bldg
Object Type: Building Revisions only
Class of Construction: lIB - 8200 Sq Ft.; sprinklered
Occupancy: B: Business / Office
Maximum No of Occupants: 81
The submittal described above has been reviewed for conformance with applicable VVisconsin Administrative Codes and
VVisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), VVisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) / Conditions:
· IBC 901.2 Fire protection systems shall be installed, repaired, operated and maintained in accordance with
this code and the international fire code. Construction ofnew walls may require the addition and or
relocation of sprinkler heads to maintain required coverage, and not obstruct spray patterns offire
sprinklers
· IFC 901.4 Fire protection systems shall be maintained in accordance with the original installation
standards for that system. Required fire protection systems shall be extended, altered, or augmented as
necessary to maintain and continue protection whenever the building is altered, remodeled or added to.
Alterations to fire protection systems shall be done in accordance with applicable standards. Submit plans
for fire sprinkler modifications.
· IBC 906.1/ IFC 906.3 The maximum travel distance allowed to a fire extinguisher is 75 feet.
· IBC 1003.2.11 Means of egress illumination is required to be installed per this section. All paths of egress
are required tp have adequate emergency lighting to meet the performance requirements of IDC
1003.2.11.3. Provide complete emergency lighting plan showing compliance with these requirements
prior to installation of emergency lighting system.
~ J:\JllspedioHs\I'lan Heview\Commen:ial P!,m Rt:'v.iew :!007\U4-70-070{) 2737-R Halyison StRevised Ridg Oniy.dor.:
Page 1 of2
. Comm 61.30(3) This review does not include lighting. Comm 63.0001 Prior to installation, lighting
plans and calculations shall be prepared in compliance with the code. The plans shall be available upon
request.
. Comm 63.1050 Lighting Controls that must be installed Provide are controls, controls to reduce
lighting, controls for daylit areas, and shutoff controls as required by this section.
. Comm 61.30(3) 1 IMC 507.2 This plan review does not include heating, ventilation, or air
conditioning. HV AC plans are required to be submitted and approved prior to installation ofHV AC
equipment. If HVA Cplans have been modified from those approved August 3, 2006 then revised plans
are required to be submitted.
. Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Comm 61.31(1).
. Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
.~
~
Building Systems Consultant
(920) 236-5051 Monday-Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.
bnoe@ci.oshkosh.wi.us
cc: Property file
Fee Required $
Fee Received $
Balance Due $
150.00
150.00
0.00
I:\IIlspediolls\Plan Revit'l,v\Cnmmen:ial Pi;m Review 2007\U4-70-0706 2737-R Ihtrrison St Reyised Jl1dg Only.do;;
Page 2 of2