HomeMy WebLinkAboutW7-1869-1206-H ~ .~ OJHKOIH City of Oshkosh Division of Inspection Services 215 Church Avenue PO Box 1130 Oshkosh WI 54903-1130 www.ci.oshkosh.wi.us ON THE WATER February 9,2007 r D. Phillip Corbin J.F. Ahem Co. 855 Morris St. Fond du Lac, WI 54935 Jeff Pauly City Center 246 City Center Oshkosh, WI 54903 Site: Plan Number: W7-1869-1206-H Mile Kimball 250 City Center Oshkosh WI 54901 For: Description: Tenant space alterations Object Type: HV AC only Class of Construction: IA - 21,211 Sq Ft.; SprinkIered Occupancy: B: Business / Office Maximum No of Occupants: 260 The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defmed in Chapter 101.01(10), Wisconsin Statutes, is responsiblefor compliance with all code requirements Key Item(s) / Conditions: · IBC 711.3 Any penetrations of fire rated assemblies are required to be protected with a listed firestopping system that matches the rating of the wall assembly being penetrated. Copies of the firestopping systems are required to he provided at the time of inspection. If an assembly that meets ASTM E 119 can not be found for the exhaust ducts penetrating the rated wall- fire dampers are required to be installed per section 715. · IBC 1101.2/ANSI A117.1-308.2 & 3 - Mechanical system controls shall be located a maximum of 48" above the finished floor if the floor space allows a forward approach by a wheel chair or if the clear space allows a parallel approach. . NEC 110.26 Spaces About Electrical Equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment. Verify that the appropriate clearances required by this section are being maintained around any equipment located above ceiling. · IMC 403.3.3 Variable air volume air distribution systems, other than those designed to supply only 100% outdoor air shall be provided with controls to regulate the flow of outdoor air. Such controls shall be designed to maintain the flow of outdoor air at a rate not less than required by Section 403 over the entire range of supply air operating rates. Additional information dated February f1' indicates that all RTU's are controlled by the building automation system having J{FD 's for air capacity control. Verify that minimum required outside air is provided over entire range of supply air operating rates. I:'Jns,x:dions\Plan .Rt:vil'w\Cnmmercial 2007\W7-1869-1206-H 250 CilY Page 1 00 · IMC 403.3.4 Balancing Ventilation systems shall be balanced by an approved method. Such balancing shall verify that the ventilation system is capable of supplying the airflow rates required by Section 403. · IMC 602.2.1 Materials exposed within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.4, materials exposed within plenums shall be noncombustible or shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E 84. · IMC 606.2.1 Smoke detectors shall be installed in return air systems with a design capacity greater than 2000 cfm...... · IMC 606.4.1 The duct smoke detectors shall be connected to a fire alarm system. The actuation of a smoke detector shall activate a visible and audible supervisory signal at a constantly attended location. · IMC 606.4.1 Exception 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identifies as air duct detector trouble. · IECC ComID 63.1029 (2) Piping insulation. Except as provided in pars. (a) to (c), recirculating plumbing system piping, plumbing piping in the first 8 feet from storage tanks for noncirculating systems, any piping served by a self-regulating electric heating cable, HV AC system piping, and related HV AC fluid conveying conduit, such as heat exchanger bodies, shall be thermally insulated in accordance with Table 63.1029 or equivalent. · IECC Comm 63.1029(4) Additional duct sealing. (a) General. Except as specified in par. (b), ductwork and plenums shall be sealed in accordance with Table 63.1029-1, and shall meet the duct seal classes specified in Table 63.1029-2. Verify that ductwork is properly sealed for the correct duct design static pressure classification, as plans submitted do not provided any information as to duct sealing or pressure classification. · COIDm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve rules under this code and which are made to construction documents that have previously been granted approval by the department or its authorized representative, shall be submitted to the office that granted the approval. All revisions and modifications to plans shall be approved in writing by the department or its authorized representative prior to the work involved iil the revision or modification being carried out. A revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with Comm 61.31(1). SUBMIT: · IECC 503.3.3.7 [Comm 63.0503(2)(f)] Balancing and documentation of the HV AC system shall conform to the IMe. Balancing report required to be submitted prior to final occupancy being allowed. · Comm61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional shall file a compliance statement form SBD-9720 with this office. 1:\InspcedlllJ1s\PlanRevil;>v\(\)l1]men:i<!J l'!;iIl RI;Vll;IV 2007\W7-1869-1206-II 250 Cily Cenkr Page 2 00 A copy of the approved plans, specifications, and this letter shall be on-site during construction. All pemrits are required to be obtained prior to commencement of work. In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or additions should conditions arise making them necessaryfor code compliance. As per state stats 101.12(2), nothing in this review shaH relieve the designer of the responsibility for designing a safe building, structure, or component. Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead. ~ Brian N oe Building Systems Consultant (920) 236-5051 Monday- Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M. bnoe@ci.oshkosh.wi.us cc: Property file Fee Required $ Fee Received $ Balance Due $ f:\Illsped.iuns\Pbn Rt:view'<Cnmmercia! Plan Rt'vitw :lQOT,iN7 -1869-! 250 C'iLy Centef nVAC On!y.doc Page 3 00 580.00 580.00 0.00