HomeMy WebLinkAboutBuilding & HVAC W5-113-1106
~
OJHKOfH
City of Oshkosh
Division of Inspection Services
215 Church Avenue
PO Box 1130
Oshkosh WI 54903-1130
www.cLoshkosh.wi.us
ON THE WATER
November 28, 2006
Patrick G Bless
219 North Second St Suite 301
Minneapolis, MN 55401-1454
Leland Franke
Gries Architectural Group
500 North Commercial St
Neenah, WI 54656
Andy Dumke
Dumke Property
601 Oregon St. Suite A
Oshkosh, WI 54901
Buffalo Wild Wings Corporate
1600 Utica Ave. Suite 700
Minneapolis, MN 55416
Site:
Buffalo Wild Wings
500 S Koeller St
Oshkosh WI 54902
For:
Description: Tenant space alterations
Object Type: Building and HV AC
Class of Construction: lIB -5683 Sq Ft.;
Occupancy: A2: Assembly
MaXimum No of Occupants: 239
Plan Number: W5-113-1106
Sprinklered
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defmed in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) I Conditions:
. ICC/ANSI A1l7.1 404.2.4 Maneuvering Clearance at Doors. Minimum maneuvering clearances at
door shall comply with Sections 404.2.4.1 through 404.2.4.7; It would appear that the door # 117
between the Bar storage area, and Bar area is being provided with a closer and would then require 12
inch minimum clearance on latch side of door projecting 48 inches in front of the door. It would
appear that the audio / video equipment rack will infringe into this required space. Provide details as to
how this issue will be resolved.
. IBC 903.4 Sprinkler system monitoring and alarms. All valves controlling the water supply for
automatic sprinkler systems and water-flow switches on all sprinkler systems shall be electrically
supervised.
. IRC 903.4.1 Signals. Alarm, supervisory and trouble signals shall be distinctly different and shan be
automatically transmitted to an approved central station, remote supervising station or proprietary
supervising station as defined in NFPA 72. NFPA 72 4.5.2 Provide a copy ofthefire alarm system
record or completion for the required monitoring and alarms of the automatic fire sprinkler system
. IRC 903.4.2 Alarms. Approved audible devices shall be connected to every automatic sprinkler system.
Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single
sprinkler of the smallest orifice size installed in the system. Alarm devices shall be provided on the exterior
ofthe building in an approved location. Where a fire alarm system is installed, actuation of the automatic
sprinkler system shall actuate the building fire alarm svstem.
H:'bri"",,,':'fHh (omm Pkin Review\W5-113-i 106 50\! S K(dw" Sf BUg & nv.'\c.t10(;
Page 1 of4
· IRC 906.1 /IFC 906.3 The maximum travel distance allowed to a fire extinguisher is 75 feet. Additionally
a class K fire extinguisher is required to be located within 30 feet of commercial cooking equipment.
· IBC 1003.2.2.5 Posting of occupant load. Every room or space that is an assembly occupancy shall have
the occupant load of the room or space posted in a conspicuous place, near the main exit access doorway
from the room or space. Posted signs shall meet the requirement of municipal code section 13-5. Min 12
inches in length, min 4 inches in height with min Yz inch lettering and the numbers being minimum 3
inches in height. The sign shall state "Limit (number) Persons".
· IBC 1003.2~10 Exit signs are required to be installed per this section
· . IBC 1003.2.11 Means of egress illumination is required to be installed per this section. All paths of egress
are required to have adequate emergency lighting to meet the performance requirements ofIBC
1003.2.11.3. Provide complete emergency lighting plan showing compliance with these requirements
prior to installation of emergency lighting system. Current plans showing emergency lighting appear to
be inadequate - additional emergency lights are required in the dinning area, and the patio area to
comply with code required light levels.
· IBC 2406.2 Glazing in an individual fixed or operable panel adjacent to a door where the nearest exposed
edge of the glazing is within a 24 inch arc of either vertical edge of the door in a closed position and where
the bottom exposed edge of the glazing is less than 60 inches above the walking surface is requires safety
glazing materials.
. IRC 2603 This .chapter governs the use of foam plastic insulation within buildings and structures. No
construction details were provided for the walk in cooler. Verify that cooler construction will comply
with the provisions of this chapter.
· IMC 302.1 The building or structure shall not be weakened by the installation of mechanical systems.
Verify that existing structure is capable of supporting the additional weight of the proposed roof top
equipment. Original Building shell plans indicate maximum RTU weight of 1500#, while this plan set
indicates 2800#, 2000#, and 1600# RTU loads. Provide structural calculations, and details on how roof
joists will be reinforced for increased loads.
. IMC 304.9 Guards. Guards shall be provided where appliances, equipment, fans or other components that
require service are located within 10 feet (3048 mm) of a roof edge or open side of a walking surface and
such edge or open side is located more than 30 inches (762 mm) above the floor, roof or grade below. The
guard shall extend not less than 30 inches (762 mm) beyond each end of such appliance, equipment, fan or
component and the top of the guard shall be located not less than 42 inches (1067 mm) above the elevated
surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21-inch-
diameter (533 mm) sphere and shall comply with the loading requirements for guards specified in the
International Building Code. IT would appear that mechanical equipment is being located closer than 10
feet from the roofs edge, where parapet walls do not extend 42 inches high. Provide detailed information
showing compliance with this section.
. NEC 110.26 Spaces About Electrical Equipment. Sufficient access and working space shall be
provided and maintained about all electric equipment to permit ready and safe operation and maintenance
of such equipment. Verify that the appropriate clearances required by this section are being maintained
rt'll,,,,,.',,, :'iH\ \ "inm Phm Review\W5-113- ii()6 50!) [((,dler SiBldg &; nv!\c.do(;
Page 2 of 4
· IMC 401.5.1 Mechanical and gravity outside air intake openings shall be located a minimum of 10 feet
from any hazardous or noxious contaminant such as vents, chimneys, plumbing vents, streets, alleys,
parking lots and loading docks.
· IMC 401.3 [Comm 64.0401 (2)] When required. (a) Outside air. Mechanical ventilation systems shall be
operated to provide a continuous source of outside air to all areas while people are present. (b )Operation.
1. Except as provided in subd. 2., the required building exhaust ventilating systems shall operate
continuously when people are in the building to provide the amount of exhaust specified in Table 64.0403.
Plans indicate that outside air is being controlled by C02 sensors. State of Wisconsin mechanical code
requires that the minimum required outside air be continuously provided while people are present.
Using a C02 sensor to reduce the amount of outside air below minimum levels is not permitted, and
outside air is required to be provided anytime the space is occupied.
· IMC 509.1 An approved automatic fire suppression system complying with the mc and !FC is required
for this kitchen exhaust hood installation.
· IBC 904.11.2 System Interconnection The Interconnection of the fire suppression system shall
automatically shut down the fuel or electrical power supply to the cooking equipment. The fuel and
electrical supply reset shall be manual.
· IECC 503.3.3.7 [Comm 63.0503(2)(1)] Balancing and documentation of the HV AC system shall conform
to the !MC. Balancing report required to be submitted prior to final occupancy being allowed.
· IECC 803.3.3.3 Off-hour controls. Each zone shall be provided with thermostatic setback controls that
are controlled by either an automatic time clock or programmable control system.
· IMC 606.2.1 Smoke detectors shall be installed in return air systems with a design capacity greater than
2000 cfm......
· IMC 606.4.1 The duct smoke detectors shall be connected to a fire alarm system. The actuation of a
smoke detector shall activate a visible and audible supervisory signal at a constantly attended location.
· IMC 606.4.1 Exception 2. In occupancies not required to be equipped with a fire alarm system, actuation
of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector
trouble conditions shall activate a visible or audible signal in an approved location and shall be identifies
as air duct detector trouble.
· Comm 5.34 No person may perform structural welding unless the person holds a registration issued by
Department of Commerce. Provide welders registration numbers for all people doing welding on this
project.
· Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Comm 61.31(1).
· Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
II:'J:rri(.Lnr('.2tHY~~. q:-~'~rn P1;.lr1 Ht~\'ie\\",,\V5-1 1 h)6 50(J S v.c>~.n~.~:' \~ fVdU. ct JTVAC.doG
Page 3 of 4
4
· MUN 30 This review does not include review for signage. Applications for and questions regarding
signage permits should be directed to David Buck - Associate Planner (920) 236-5062.
· MUN 15 NOTE: Contact Sandy Knutson - Health Services (920) 236-5027 for additional information as
to Health code requirements. Preliminary review indicates the need for an additional sink.
· MUN 30-35 (1)(5) All rooftop and ground level mechanical equipment and utilities shall be fully screened
from view of any street or residential zoning district. Contact David Buck - Associate planner (920) 236-
5062 for additional information on screening requirements. All screening shall be properly anchpred in
place to resist wind loads. Additionally IDe 1608.8 Roofprojections - Drift loads due to mechanical
equipment, penthouses, parapets and other projections above the roof shall be determined in accordance
with Section 7.8 of ASCE 7. Provide screening plan for all equipment that will be visible from a street
or residential property. NOTE: No mechanical permits will be issued until a screening plan has been
approved.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
R~
~~
Building Systems Consultant
(920) 236-5051 Monday-Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.
bnoe@ci.oshkosh.wi.us
cc: Property file
Fee Required $
Fee Received $
Balance Due $
800.00
800.00
0.00
n :\bri;Lm,'20U6
Phm Re\'ie\\'\\V5-1. 13-1 5('i1J :' K('>1~"i!~:.
&; liY"\Cdo(;
Page 4 of 4