HomeMy WebLinkAbout2007-Building X1-1879-0107
~
OJHKOfH
City of Oshkosh
Division of Inspection Services
215 Church Avenue
PO Box 1130
Oshkosh WI 54903-1130
www.ci.oshkosh.wi.us
ON THE WATER
February 2, 2007
James Groff
. HGMArchitecture Inc.
805 North Main St
Oshkos~ VVI54901
Dave Hanson
D.M. Rentals LLC
55 Knapp St
Oshkosh, VVI 54902
Site: Plan Number: XI-1879-0107
420 N Main St.
Oshkosh VVI 54901
For:
Description: Conversion of 2nd floor into apartments
Object Type: Building only
Class of Construction: VB -1600 Sq Ft.; Unsprinklered
Occupancy: R3 Residential
The submittal described above has been reviewed for conformance with applicable VVisconsin Administrative Codes and
VVisconsin Statutes. The submittal has been CONDITIONALI" Y APPROVED. The owner, as defmed in Chapter
101.01(10), VVisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) / Conditions:
This plan approval is contingent on the approval of the Variance applied for on 1/19/07 and any of the conditions
included in the application or required as a condition to granting that variance..
. IRC 711.3 Any penetrations of fire rated assemblies are required to be protected with a listed firestopping
system that matches the rating of the wall assembly being penetrated. Copies of the firestopping ~ystems
are required to be provided at the time of inspection. Caution on laundry hook-ups, and dryer vent in a
rated wall.
. IRC 714.2.3 Doors in corridors and smoke barriers. Fire doors required to have a minimum fire-
protection rating of 20 minutes where located in corridor walls or smoke barrier walls having a fire-
resistance rating in accordance with Table 714.2 shall be tested in accordance with NFP A 252 or UL 10C
without the hose stream test. If a 20-minute fire door or fire door <l;ssembly contains glazing material, the
glazing material in the door itself shall have a minimum fire-protection rating of 20 minutes and be exempt
from the hose stream test. Glazingmaterial in any other part ofthe door assembly, including transom lites
and sidelites, shall be tested in accordance withNFP A 257, including the hose stream test, in accordance
with Section 714.3. Fire doors shall also meet the reQuirements for a smoke- and draft-control door
assemblv tested in accordance with VI. 1784 with an artificial bottom seal installed across the full
width of the bottom of the door assemblv. The air leakage rate of the door assembly shall not exceed 3.0
cfm per square foot (0.01524 m3/s1m2) of door opening at 0.10 inch (24.9 Pa) of water for both the
ambient temperature and elevated temperature tests. Louvers shall be prohibited.
FTn,p~di,.ms\Plan Review\CommerdalPlan Revi>:w 200TXI-I 879-0 I 07 .+20 NMail1 Sll3ldg On!:v.doc'
Page 1 of 4
. mc 714.2.7 Fire doors shall be self closing or automatic closing. The door schedule included in the plans
does not show closers for the addedfire doors. All hardware installed on rated doors is required to
comply with NFP A 80 requirements for hardware on rated doors.
. mc 803 Interior finish based on group. Interior wall and ceiling finish shall have a flame spread index
not greater than that specified in table 803.4 for the group and location designated. The corridor requires
a class "c" finish
. me 906.1 / IFC 906.3 The maximum travel distance allowed to a fire extinguisher is 75 feet..Fire .
extinguisher is required to be provided in common area, as well as within each unit - verifY location
acceptable to fire department.
. 907.2.10.1.2 Groups R-2, R-3, R-4 and 1-1. Single- or multiple-station smoke alarms shall be installed
and maintained in Groups R-2, R-3, R-4 and I-I, regardless of occupant load at all of the following
locations: LOn the ceiling or wall outside of each separate sleeping area in the immediate vicinity of
bedrooms.
2. In each room used for sleeping purposes.
3. In each story within a dwelling unit, including basements and cellars but not including
crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and
without an intervening door between the adjacent levels, a smoke alarm installed on the
upper level shall suffice for the adjacent lower level provided that the lower level is less
than one full story below the upper level.
. IRC 1003.2.10 Exit signs are required to be installed per this section Exit signs are required to be
installed at each exit stair
. IRC 1003.2.11 Means of egress illumination is required to be installed per this sectionA minimum 1 foot-
cmidle at the floor level is required to be provided for the entire path of egress at all times. This would
include the exterior porch and stairs.
. IRC 1003.2.11 Means of egress illumination is required to be installed per this section. All paths iof egress
are required to have adequate emergency lighting to meet the performance requirements of mc
1003.2.11.3. . The entire path of egress including the porch and exterior stair to grade is required to be
provided with emergency illumination. Provide complete emergency lighting plan showing compliance
with these requirements prior to installation of emergency lighting system.
. IRC 1005.3.2.2 Enclosures under stairways. The walls and soffits within enclosed usable spaces under
enclosed and unenclosed stairways shall be protected by I-hour fire-resistance-rated construction, or the
fire-resistance rating of the stairway enclosure, whichever is greater. Access to the enclosed usable space
shall not be directly from within the stair enclosure. Plans submitted do not included information on this
issue - verifY that required fire rated construction is provided.
. IRC 1009.1/ Comm 62.1009 In Group R occupancies and Group I-I occupancies. Provide emergency
escape and rescue opening in accordance with this section Openings shall be a minimum of 5.7 sq ft in
actual clear opening (5 sq ft on grade floor(s)) and minimum of24" high and 20" wide with a maximum
sill height of 44".
Exceptions:
2. In other than Group R-3 occupancies as applicable in Section 101.2, (twofamily detached), sleeping
rooms provided with a door to a fire-resistance-rated corridor having access to two remote exits in opposite
directions. Doors from bedrooms to corridor are required exits. The bedroom without the 2nd exit is
required to have rescue opening windows that comply with this section
l:\Inspectiuns'.Plan Review'..CulJ1men:ial Pbn R.t',,)t'w
879-0! 07
Bk!g
Page 2 of 4
. IBC 1202.1 General. Buildings shall be provided with natural ventilation in accordance with Section
1202.4 or shall be provided with mechanical ventilation in accordance with the International Mechanical
Code. Provide details for how ventilation is being provided for bedrooms without windows, or include
this information in HVAC plan submittal ifbeing accomplished with mechanical ventilation.
. IRC 1206.2 Air-borne sound. Walls, partitions and floor/ceiling assemblies separating dwelling units
. from each other or from public or service areas shall have a sound transmission qlass (STC) of not less than
50 (45 if field tested) for air-borne noise when tested in accordance with ASTM E 90. This requirement
shall not apply to dwelling unit entrance doors; however, such doors shall be tight fitting to the frame and
sill.
. IMC 504.5 Makeup air. Installations exhausting more than 200 cfm (0.09 m3/s) shall be provided with
makeup air. Where a closet is designed for the installation of a clothes dryer, an opening having an area of
not less than 100 square inches (0.0645 m2) shall be provided in the closet enclosure.
. IMC 504.6.1 Maximum length. The maximum length of a clothes dryer exhaust duct shall not exceed 25
feet (7620 rom) from the dryer location to the outlet terminal. The maximum length of the duct shall be
reduced 2.5 feet (762 rom) for each 45-degree (0.79 rad) bend and 5 feet (1524 rom) for each 90-degree
(1.6 rad) bend. Exception: Where the make and model of the clothes dryer to be installed is known and
the manufacturer's installation instructions for such dryer are provided to the code official, the maximum
length of the exhaust duct, including any transition duct, shall be permitted to be in accordance with the
dryer manufacturer's installation instructions.
. IFC 304.3 Containers. Combustible rubbish and waste material kept within a structure shall be stored in
accordance with Sections 304.3.1 through 304.3.3.
. IFC 304.3.3 Capacity exceeding 1.5 cubic yards. Dumpsters and containers with an individual capacity
of 1.5 cubic yards or more shall not be stored in buildings or placed within 5 feet of combustible walls,
openings, or combustible roof eve lines. Provide details on where garbage will be stored .
. Comm 61.30(3) / IMC 507.2 This plan review does not incIud~ heating, ventilation, or air
conditioning. BV AC plans are required to be submitted and approved prior to installation ofHV AC
equipment. Be aware that mc 1004.3 .2.4 contains additional resmction for air movement in conidors
. Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Corom 61.31(1).
. Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
. Contact Susan Kepplinger (920) 236-5058 in the planning services division for additional requirements
that apply to interior finishes, and materials.
1:\Inspedions\Pbn Revlew\Cnmmerdal Pi"n Rt'vit'w 2007\XI-1879-0 I (}7 .+20 N Main 31 Bldg Only. dot:
Page 3 of 4
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work. '
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe bui1dmg, structure, or component.
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
Brian oe
Building Systems Consultant
(920) 236-5051 Monday - Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1 :30 P.M.
bnoe@ci.oshkosh.wi.us
cc: Property file
Susan Kepp1inger
Fee Required $
Fee Received $
Balance Due $
430.00
430.00
0.00
Flnsp"diOlJs\Pbn Rt:view\Comme.n:ial Plan Rc-vi!;w 2007\X 1-1879-0 I 07.+20 N BUg
Page 4 of 4