Issue Date 1/11/2007
Address 315 ALGOMA BLVD
INSPECTION SERVICES DIVISION ROOM 205
DEPARTMENT OF COMMUNITY DEVELOPMENT
CORRECTION NOTICE
CITY OF OSHKOSH
215 CHURCH AVE
PO Box 1130
OSHKOSH WI 54903-1130
Compliance Date 2/1 0/2007 IMMEDIATELY
Compliance No
Sent to
~ Owner
Name
! WIS BELL INC
Address
722 N BROADWAY ST
City
MILWAUKEE
State Zip Code
WI 53202 -4396
Introduction
U Required for Occupancy Occupancy Commercial
hile conducting Final Inspection with Glen from Eland Electric the following violation was noted that a Correction Notice was
requested for. Other violations will be corrected when the final installations are completed.
Item # 1
Description
Code NEC 250.30(A)(3) Compliance No Compliance Date 02/10/2007 IMMEDIATELY
grounding electrode conductor for a separately derived system shall be sized in accordance with 250.66 for the derived phase conductors
nd shall be used to connect the grounded conductor to the grounding electrode. Note: See the atached document which describes the NEC's
nterpretation of a separately derived system. This is a copy from the commentary of NFPA 70 / NEC.
01/11/2007
Last
Updated
Summary TO avoid any further inconvenience please correct the above noted violation immediately. Any questionsorconcerns please
eel free to contact me @ 920-236-5046 or email @ kbenner@cLoshkosh.wLus
Violations must be corrected and approved within 30 days unless otherwise noted. Call for r~inspections prior to concealment
and/or occupancy. Upon completing the corrections, the owner/contractor/agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 2/10/2007
Office hours for obtaining permits are Monday through Friday 7:30-8:30 a.m. and 12:30-1 :30 p.m. or by appointment. To schedule
inspections please call the Inspection Request line at 236-5128 noting the address, permit number (when applicable), and the
nature of what needs to be inspected.
S'gnatu", ~t:3 B<l4'1~ D""'~
Inspecte Y: Kevin Benner 236-5046 kbenner@ci.oshkosh.wi.us
I hereby certify the violations listed on this report have been corrected In compliance with the applicable codes.
Print Name
Company
Signature
Date
Also Sent to:
U Bldg
~ Elec
U HVAC
U Plbg
U Designer
U Other
U Inspector
I
j ELAND ELECTRIC CORP
I
i
i
-l
I
3154 HOLMGREN WAY
GREEN BAY
WI 54304 -0
12154
Page 1 of 1
'.'
..
Section 250.30(A) provides the requirements for bonding and
grounding the separately derived systems described in 250.20(D).
A separately derived system is defined in Article 100 as a premises
wiring system in which power is derived from a battery, a solar
photovoltaic system, a generator, a transformer, or converter
windings. It has no direct electrical connection, including a solidly
connected grounded circuit conductor, to supply conductors
originating in another system.
The requirements of 250.30 are commonly applied to 480-volt
transformers that transform a 480-volt supply to a 208Y1120-volt
system for lighting and appliance loads. These requirements
provide for a low-impedance path to ground so that line-to-ground
faults on circuits supplied by the transformer result in a sufficient
amount of current to operate the overcurrent devices. These
requirements also apply to generators or systems that are derived.
from converter windings, although these systems do not have the
same wide use as separately derived systems that are derived from
transformers.