HomeMy WebLinkAbout2007-HVAC Plan W7-1872-1206-H
~
OJHKOJH
city of Oshkosh
Division of Inspection Services
215 Church Avenue
PO Box 1130
Oshkosh WI 54903-1130
www.cLoshkosh.wLus
ON THE WATER
January 10, 2007
Thomas J Harper
Auer Steel
707 N Perkins St
Appleton, WI 54914
James Roberts
Roberts Homes
255 S Main St
Fond du Lac, WI 54935
Site: Plan Number: W7-1872-1206-H
Roberts Homes
1423 S Washburn
Oshkosh WI 54904
For:
Description: HV AC for tenant space Build Out
Object Type: HV AC only
Class of Construction: VB - 1145 Sq Ft.; Unsprinklered
Occupancy: B: Business / Office
. The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
. 101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) / Conditions:.
. IMC 304.1 Equipment and appliances shall be installed as required by the terms of their approval, in
accordance with the conditions of the listing, the manufactures instructions and this code. Maintain
required clearances to equipment.
. IMC 401.3 [Comm 64.0401 (2)] When required.
(a) Outside mr. Mechanical ventilation systems shall be operatedto provide a continuous source of outside
air to all areas while people are present.
(b) Operation.
l.Except as provided in subd. 2., the required building exhaust ventilating systems shall operate
continuously when people are in the building to provide the amount of exhaust specified in Table
64.0403.
2.Subdivision 1. does not apply to all of the following:
a.Toilet rooms with two or fewer total water closets or urinals, if the required ventilation is
provided when the room is occupied. This exception is not applicable, as the toilet room.has
been provided with supply air, the exhaust system for the toilet room is required to run
simultaneously.
. IBC 1l01.2/ANSI A1l7.1-308.2 & 3.- Mechanical system controls shall be located a maximum of 48"
above the finished floor if the floor space allows a forward approach by a wheel chair or if the clear space
allows a parallel approach.
l:\lnspcctions\Pliln Revlcw\Cill1UllCrcial Plan RL'vicw 2007\ Wi. j ~72.12\l6.H 1423 S Washburn H V/\C Only.doc
Page 1 of2
. Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Corum 61.31(1).
. MUN 30-35 (1)(5) All roof top and ground level mechanical equipment and utilitie.s shall be fully screened
from view of any street or residential zoning district. Contact David Buck- Associate planner (920) 236-
5062 for additional information on screening requirements. All screening shall be properly anchored in
place to resist wind loads. Additionally mc 1608.8 Roofprojections - Drift loads due to mechanical
equipment, penthouses, parapets and other projections above the roof shall be determined in accordance
with Section 7.8 of ASCE 7.
SUBMIT:
. Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteraticm the supervising professional shall
file a compliance statement form SBD-9720 with this office.
. IECC 503.3.3.7 [Comm 63.0503(2)(f)] Balancing and documentation of the HV AC system shall conform to
the IMe. Balancing report required to be submitted prior to final occupancy being allowed.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting tlps approval the City of Oshkosh Inspection Services Department re~erves the right to reqUire changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence may be made to me at the numberlisted below or the address on this letterhead.
oe
Building Systems Consultant
(920) 236-5051 Monday-Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.
bnoe@ci.oshkosh.wi.us
cc: Property file
Fee Required $
Fee Received $
Balance Due $
230.00
230.00
0.00
1:\lnspcctiol1s\Plall Revlcw\Commcrelal Plan Review 20()7\,:V7.] 872-12()6.H 1423 S ,:VaB1ibum HV/\C Only.doc
Page 2 of2