HomeMy WebLinkAbout0122897-HVAC
e
OSHKOSH
ON THE WATER
Job Address 3596 STEARNS DR
CITY OF OSHKOSH
No
122897
HVAC PERMIT -APPLICATION AND RECORD
Owner DANIEL E DOWLING
Create Date 12/14/2006
Contractor GARTMAN MECHANICAL SERVICES
Fuel ~ Gas UOil
System ~ New
l!:J Forced Air U Radiant
U Electric U Hot Water
Chimney Type U Chimney A . Chimney B
Heat Loss . As Approved o Existing
BTU Rate . As Per Plan () Variable
Category 510 - Ind. & Comm-Heating & Ventilating
U Solar
Plan Q5-85-0905-R2H
U Solid
U Electric
D Replace
U Steam
U Suppl.
() Direct Vent
U AlC
U Con. Burner l
() Not Applicable
o Not Applicable
() Other
Value
Value
Use/Nature IND/ Installation of 5 unit heaters as per plans.
of Work
Fees: Valuation
$10,900.00
Plan Approval
$0.00
Permit Fee Paid
$169.00
Issued By:
Date 12/14/2006
D Permit Voided I
Parcel Id # 1278800000
In the performance of this work, I agree to perform all work pursuant to rules governing the described construction.
While the City of Oshkosh has no authority to enforce easement restrictions of which it is not a party, if you perform the work
described in this permit application within an easement, the City strongly urges the permit applicant to contact the easement
holder(s) and to secure any necessary approvals before starting such activity.
Signature
Date
AgenUOwner
Address
PO BOX 2264
OSHKOSH
WI 54903 - 2264 Telephone Number (920) 231-5530
To schedule inspections please call the Inspection Request line at 236-5128 noting the Address, Permit Number, Type of
Inspection (i.e. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue if the inspection is not performed within two business days from the time the project is ready.
Oct OS 04 09:52a
.Oshkosh Inspections
920-236-5084
p. 1
'f
,.
r
City of Oshkosh
Division ofInspection Services
P.O. Box 1130
Oshkosh, WI 54903-1130
Phone (920) 236-5050
Fax (920) 236-5084
HVAC PERMIT APPLICATION
All information after bold categories must be provided.
Incomplete applications will not be processed.
~
OfHKOfH
ON THE WATER
· Application(s) and fee(s) can be brought to City Hall, Room 205 or mailed to Inspection Services, PO Box 1128,
Oshkosh WI 54903-1128. Commencing work without permit(s) win result in fees being doubled or $100.00 plus the
normal pennit fee, which ever is greater.
OR
I au are a contractor artici otin in the Permit ee Account S stem and have ade uate
:~~~~::?;;;o;;:~: X /~;;j~. ~dj
OWNER ~~ ?d.cif_ jpMd-'l'
'CONTRAcrOR ,~~~ C- ..
CHECK It!' ALL APPLICABLE
r\i
USE CATEGORY
OSingle Family DDuplex OMulti-Family
FUEL ~s
ORental ~mmercial
o Industrial
DElectric DSolid
o Solar
SYSTEM
DNew
o Other
OReplace
~~ed Air DRadiant DSteam DAlC OVent DElectric OHot Water OSuppL Oeon. Burner
IS CHIMNEY BEING LINED~o DYes - LINER SIZE & MANUFACTURER
Note: All chimneys shall be sized ~th~'BTU's being vented.
CHIMNEY TYPE ~'mneY A DChinmey B
BEAT LOSS . Approved OExisting
BTU RATE s Per Plan DVariable
DESCRIPTION OF AI.. WORK BEING DO
~.'O
ODirect Vent OOther
DNot Applicable
DOther Value
\0,
cPy
$ /L?.J 90a
VALUE
ELECTRICAL CONTRACTOR
o For applicable projects, an Electric Installation Verification fonn, signed by the Electrical Contractor, must be
attached. If not attached or not applicable, a separate Electrical Permit is required.
----
{\
t
9(02
Job Address 3596 STEARNS DR
HVAC Permit Work Card
Permit Number
:
122897
Create Date 12/14/2006
Contractor GARTMAN MECHANICAL SERVICES
Owner
DANIEL E DOWLING
Fuel [~Gas I U Oil U Electric 1 U Solar
System 0 New I 0 Replace
~ Forced Air U Radiant I U Steam
U Electric U Hot Water I U Suppl.
Chimney Type 0 Chimney A . Chimney B
Use/Nature IND/. Installation of 5 unit heaters as per plans.
of Work
I ~n Value
I 0 Other
~ U AlC ~ U Vent
I ~Con. Burner I .
o Direct Vent . 0 Not Applicable
$10,900.00
I
I
Inspections:
Date 11/7/2007 Type Final Inspector Allyn Dannhoff not approved
Need properly located thermostats and provide thermostats with automatic setback controls. Need HVAC Compliance Statement.
.
Date/Time requested:
Access: I
Requested By:
o Reinspect Fee 0 Fee Waived
Notice Type:
R~ady DatefTime:
Phone Number:
o Reinspect Fee Paid
- - - - - - - - - - - - -- - - - - - - --- - - - - - - - - - - - - - - - - - - - - - - --- - - - - - -- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - --
Date 12/31/2007 Type Final Inspector Allyn Dannhoff
hermostats corrected per e-mail from Tim Weitz (Gartman).
approved w/cond.
Date/Time requested:
Access: I
Requested By:
o Reinspect Fee 0 Fee Waived
Notice Type:
R~ady DatefTime:
Phone Number:
o Reinspect Fee Paid
- - - -_.- - -- - ------ - - --- _.-- - - -- -_.- -- - ----- - - --- ---- - -- - .------ - - ---- ------ - - - ---- -- - ---- -. - - - - - - - - - .--- - -- ---- - - - - ---- -------- ------ - - ----- ---- --- ------- - - ---- ------ -- - -----
~'~,""- :,~.?io-:.;:~.;.;~~~~~,...."_. ".,..:::;;:..;;.:....~...,-
~
OJHKOfH
City of Oshkosh
Division of Inspection Services
215 Church Avenue
PO Box 1130
Oshkosh WI 54903-1130
www.cLoshkosh.wi.us
ON THE WATER
December 14, 2006
Keith Paul
OMS Inc
520 W South Park Ave
Oshkosh, WI 54902
Dan Dowling'
3596 Sterns Dr.
Oshkosh WI 54903
Site: Plan Number: Q5-85-0905-R2 -H
3596 Sterns Dr
Oshkosh WI 54901
For:
Description: HV AC for Sunset School Conversion
Object Type: HV AC Only
Building Type: VB - 5422 Sq. Ft. Unsprinklered
Occupancy:Sl,S2,:Storage
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPR,OVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) I Conditions:
. IBC 1101.21ANSI A117.1-308.2 & 3 -Mechanical system controls shall be located a maximum of 48" above
the finished floor if the floor space allows a forward approach by a wheel chair or if the clear space allows a
parallel approach.
. 304.4 Public garages. Appliances located in public garages, service stations, repair garages or other areas
frequented by motor vehicles, shall be installed a minimum of 8 feet (2438 mm) above the floor. Where
motor vehicles exceed 6 feet (1829 rom) in height and are capable of passing under an appliance, appliances
shall be installed a minimum of2 feet (610 rom) higher above the floor than the height of the tallest vehicle.
. IFGC 401 /Comm 65.0400 All gas piping and gas piping installations shall comply with NFP A 54, National
Fuel Gas Code.
. IFGC 619.2 Support. Suspended-type unit heaters shall be supported by elements that are designed and
constructed to accommodate the weight and dynamic loads. Hangers and brackets shall be of noncombustible
material.
. 619.4 Clearance. Suspended-type unit heaters shall be installed with clearances to combustible materials of
not less than 18 inches (457 rom) at the sides, 12 inches (305 rom) at the bottom and 6 inches (152 mm) above
the top where the unit heater has an internal draft hood or 1 inch (25 rom) above the top of the sloping side of
the vertical draft hood. Exception: Unit heaters listed for reduced clearance shall be permitted to be installed
with such clearances in accordance with their listing and the manufacturer's instructions.
f:\fn"fI,,\,;ions\Plan Pevit'w'-C\llTlrne:','i,!i I'bn i<e,"'\'w::n\)6'Q5-85-o905-1n~1l 3596 Sfe,.,,, 'f)r I IV AC (lniy,d,,\'
Page 1 of2
.....~~.-....-- ~
. .Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve rules.
under this code and which are made to construction documents that have previously been granted approval by
the department or its authorized representative, shall be submitted to the office that granted the approval. All
revisions and modifications to plans shall be approved in writing by the department or its authorized
representative prior to the work involved in the revision or modification being carried out. A revision or
modification to a plan, drawing or specification shall be signed and sealed in accordance with Corom 61.31(1).
A copy of the approved plans, specifications, and this letter shall be on-she during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
a
Building Systems Consultant
(920) 236-5045 Monday- Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.
adannhoff@ci.oshkosh.wi.us
cc: Property file
Fee Required $
Fee Received $
Balance Due $
320.00
320.00
0.00
"
Rcvi!:w\('O!Hmer'-';11
!(;C'\">'\' "I)!jli"Q5-85-0905-RI-Il 35% SW'1';' I), IIVAC Only,deK'
Page 2 of2
~. "-~,...~,..~"_..,,,.. ~ ~."."..-..
~~~_ n"_~"
~
CORRECTION NOTICE / FIELD INSPECTION REPORT
JOB LOCATION: .3S'"?(P ~eo t- i'\.:'S:
CONTRACTOR: OW)l^-€r- / c;.,:n-f-i4A-a let
./
PROJECT TO BE INSPECTED: #'?h~f'~ .Q..- s: Lob
TYPE OF INSPECTION: ;:=r'A-CL r /
~
City of Oshkosh
Inspection Services Division
215 Church Avenue, PO Box 1130
Oshkosh, WI 54903-1130
Phone: (920) 236-5050
Fax (920) 236-5084
a.r-€.A-
Violations must be corrected and approved within 30 days unless otherwise noted. Call for re-inspections prior to concealment
and/or occupancy. Upon completing the corrections, the owner/contractor/agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 1 ~ l
.ct'lll'Mf#. ""OODE INSPECnONRESULTS
~l1ed/Faxed
Z~-~~d----
Phone #
Print Name
Company
Date
Signature:
Page 1 of 1
Dannhoff, Allyn J.
From: Tim Weitz [tweitz@gartmanmechanical.com]
Sent: Friday, December 14, 20078:00 AM
To: Dannhoff, Allyn J.
Subject: Dowling's
Allyn,
We have completed the services required in the correction notice for Dowling's building however I am waiting on
the signature from Dan that you requested. He was not present upon completion of the services, I will send
through the paperwork when he returns the signed copy to us. Thank you for the extension on these services, if
you have any questions or concerns please give me a call.
Tim Weitz
GMS, Inc.
12/14/2007