HomeMy WebLinkAboutHVAC Plan Approval
,."~"";
~
OJHKOfH
City of Oshkosh
Division of Inspection Services
215 Church Avenue
PO Box 1130
Oshkosh WI 54903-1130
www.ci.oshkosh.wi.us
ON THE WATER
December 14,2006
Keith Paul
GMS Inc
520 W South Park Ave
Oshkosh, WI 54902
Dan Dowling
3596 Sterns Dr.
Oshkosh WI 54903
Site: Plan Number: Q5-85-0905-R2-H
3596 Sterns Dr
Oshkosh WI 54901
For:'
Description: HV AC for Sunset School Conversion
Object Type: HV AC Only
Building Type: VB - 5422 Sq. Ft. Unsprinklered
Occupancy: SI, S2, :Storage
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) I Conditions:
. IBC 1l01.2/ANSI A1l7.1-308.2 & 3 - Mechanical system controls shall be located a maximum of 48" above
the finished floor if the floor space allows a forward approach by a wheel chair or if the clear space allows a
parallel approach.
. 304.4 Public garages. Appliances located in public garages, service stations, repair garages or other areas
frequented bv motor vehicles, shall be installed a minimum of 8 feet (2438 mm) above the floor. Where
motor vehicles exceed 6 feet (1829 mm) in height and are capable ofpassirig under an appliance, appliances
shall be installed a minimum of2 feet (610 mm) higher above the floor than the height of the tallest vehicle.
. IFGC 401/Comm 65.0400 All gas piping and gas piping installations shall comply with NFP A 54, National
Fuel Gas Code.
. IFGC 619.2 Support. Suspended-type unit heaters shall be supported by elements that are designed and
constructed to accommodate the weight and dynamic loads. Hangers and brackets shall be of noncombustible
material.
. 619.4 Clearance. Suspended-type unit heaters shall be installed with clearances to combustible materials of
not less than 18 inches (457 mm) at the sides, 12 inches (305 mm) at the bottom and 6 inches (152 rom) above
the top where the unit heater has an internal draft hood or 1 inch (25 mm) above the top of the sloping side of
the vertical draft hood. Exception: Unit heaters listed for reduced clearance shall be permitted to be installed
with such clearances in accordance with their listing and the manufacturer's instructions.
r:'.Jn,pe<:l;,m,'.P!an FeVleW\('OrlHnt:,.,,'ni Pi,lll 1<,:",<"," i'.f\)6\Q5-85~9(l5-R2~[J 3:'96 Stern, Dr IIV (lniy,dn<:
Page 1 of2
. Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve rules
under this code, and which are made to construction documents that have previously been granted approval by
the department or its authorized representative, shall be submitted to the office that granted the approval. All
revisions and modifications to plans shall be approved in writing by the department or its authorized
representative prior to the work involved in the revision or modification being carried out; A revision or
modification to a plan, drawing or specification shall be signed and sealed in accordance with Comm 61.31(1).
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence maybe made to me at the number listed below or the address on this letterhead.
Building Systems Consultant
(920) 236-5045 Monday-Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M,
adannhoff@ci.oshkosh.wi.us
cc: Property file
Fee Required $
Fee Received $
Balance Due $
320.00
320.00
0.00
i!n,pedi',lHs\Phm Review\Commerc'i,,: I'Lm (<C" ','W ~,(;()Ii'{)5-85-()9(l5-R2-H 35% Sle"''' Dr IIV!\C Oniy,do<:
Page 2 of 2