HomeMy WebLinkAbout2006-HVAC
~
.
OSHKOSH
ON THE WATER
Job Address 3110 PROGRESS DR
CITY OF OSHKOSH
No
122806
HV AC PERMIT - APPLICATION AND RECORD
Owner FOX CITIES CONSTRUCTION CO INC
Create Date 12/06/2006
Plan U6-75-0706-H
U Solar U Solid
Category 512 - Ind. & Comm-Both
U Electric
o Replace
U Steam
U Suppl.
() Direct Vent
o Other
~ AlC ~ Vent
U Con. Burner
Contractor SURE-FIRE INC
Fuel ~ Gas UOil
System ~ New
~ Forced Air U Radiant
U Electric U Hot Water
Chimney Type ~) Chimney A () Chimney B
Heat Loss . As Approved () Existing
BTU Rate . As Per Plan () Variable
. Not Applicable
() Not Applicable
C) Other
Value
Value
Use/Nature IND/ HVAC system as per plans for new building
of Work
Fees: Valuation
$149,117.00
Plan Approval
$0.00
Permit Fee Paid
$931.00
Issued By:
Date 12/06/2006
o Permit Voided I
Parcelld #
In. the performance of this work, I agree to perform all work pursuant to rules governing the described construction.
. While the City of Oshkosh has no authority to enforce easement restrictions of which it is not a party, if you perform the work
described in this permit application within an easement, the City strongly urges the permit applicant to contact the easement
holder(s) and to secure any necessary approvals before starting such activity.
Signature
Date
Agent/Owner
Address
POBOX 191
HORICON
WI 53032 -191 Telephone Number 920-485-4883
To schedule inspections please call the Inspection Request line at 236-5128 noting the Address, Permit Number, Type of
Inspection (i.e. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue if the inspection is not performed within two business days from the time the project is ready.
Sep.29. 2006 11:29AM inspection
Post-It" Fax. Note
To
No. 9064 P. 1
r-\
City of Oshkosh
Division oflDspection Serv
P.O. Box 1130
Oshkosh, WI 54903-1130 .
Phone (920) 23(i.SOSO Fax r,r;<() - 'f,; 5- (/"75" Fax # .
.Fu (920) 236-5084 U)u)(.,0. C-I . (X?h\<PSh. ~I . u..'S /commUJ\(h.l-d-e.\J~\apment J
\ nspeCllcY\S J ~rV)'\\~ _O-..pp- n\lClC_ '2.GQ;Lf
. 1~t\6 \, HVAC PERMIT APPLICATION
Ot.C \\~~ AU information after bold categories umst be promed.
t.f:::J \ ' Incomplete applications will not be processed.
Phone /I
~
QftKOfH
ON THE WAT1!R "~
0"10
. s-~
\J 10- l
· Application(s) and fee(s) can be brought to City Hall, Room 205 or mailed to Inspection Services. PO Box 1128,
Oshkosh WI 54903-1128. Commencing work without pennit(s) wilt result in fees being doub'ed or 5100.00 plus the
nonnal pennit fee, which ever is greater.
OR
[(YOU ~,.e a contractor lIarticipaU", in the Permit fee Account SYstem and haV.e adequate funds. check here
if vou want this 'processed tlrrouvh "Our account n
lOB ADDRESS 1~ i; PA~
'OWNER 3~
CONTR.AC'fOR_. . Su..u- - j-Lh.Q..; ~::... ...
DATE S-r.rt. r9q d.DO(o
- .
CHECK Ii( ALL APPLICABLE
USE CATEGORY
r\ DSingle Family DDuplex OMulti-Family
[JRental
RE Ei E':
. .d" j ..
OCT 0 2 2006
DEPARTMENT OF
COMMUNITY DEVELOPMENT
~mmercial DIndustrial .
FUEL
DGas
OOiI
DElectric DSolid
JJSolar
SYSTEM 14New
'CQther
DReplace
TYPE
ptForced Air DRadiant DSteam ~C ~Vent DElectric
IS CHIMNEY BEING LINED"tiNo DYes - LINER SIZE
Note; All chimneys shall be 'sized ~ BTU's being vented.
~B
DExisting
OVariable
OHot Water OSuppl. oCon. Burner
& MANUFACTURER.
CHIMNEY TYPE
JlEAT LOSS
BTU RATE
DChimney A
fJAs Approved
TfI.^s Per Plan
ODirect Vent
DNot Applicable
OOther Value
[]Other
DESCR1PTIONOFALLWORKBElNGDONE ~ll Q~L(lflYl~
VALUE
L\q ,117;g.Q
Q3/.02-
ELECTRICAL CONTRACTOR
{\ 0 For applicable projects, an Electric Installation Verification f~ signed by the Electrical Contractor, must be
attached. If not attached or not applicab~e. a separate Electrical Pennit is required.
9/02
09/29/2006 FRI 14:07 FAX 9204854075 SURE-FIRE, INC.
.
141 004/007
;
>
0/.
May $, 2006
Fox Cities Construction
4614 Red Fox Road
Oshkosh, WI 54904
Attn: Keith
Re: New Factory - Revised Bid
We propose to furnish and Install the following.
Weldinq Area
3 - Gas-fired unit heaters
1 - Gas-fired make-up air unit, rated @ 3000 CFM, with starter and disconnect, controlled by
discharge air controller
2 -12' wide air curtains for 14' high doors
1 - Wall exhaust fan, 3000 CFM's, to be interlocked with above make-up air unit, by electrical
contractor
1 - Relocation and installation of (6) air cleaners from existing plant (by others)
Wash Bay
1 - Ceiling recirculation fan above prep/wash area
1 - Wall exhaust fan, rated @ 800 CFM, with ductwork to near the floor
Paint Booth
Relocation and Installation of existing booth, including relocation and support for (2) rooftop
make-up air units, relocation of (4) exhaust fans with minimum discharge Ductwork by others
2 - Curbs for supply air ductwork, including connection of ductwork from make-up air unit to inlet
of spray booth
4 - New roof flashings for extension of spiral pipe through roof, and install existing roof cap and
storm collars for a watertight installation
Office Area
1 - 20-Ton rooftop unit
Insulated supply & return ductwork with all required grilles & registers
System will be zoned with seven zones, as follows:
#1 - Reception area
#2 - Conference room
#3 - Three of five offices on exterior wall
#4 - Remaining two of five office on exterior wall
#5 - Private office behind elevator
#6 - Open general office area
#7 - Break room
2 - Roof-mounted exhaust fans (1 for restroom, 1 for break room)
1 - Ceiling exhaust fan and line voltage thermostat for elevator equipment room
3 - Electric wall heaters (1 for vestibule, 2 for restrooms)
Paint Storage Area
1 - Wall-exhaust fan with ductwork to floor; fan to run continuously
1 - Transfer duct with fire damper in wall
Plant Area
1 - Air turnover unit, located in middle of plant, with starters and pisconnects
2 - Wall exhaust fans in truck unloading bay
Relocation and installation of ductwork for compressor, including additional ductwork, if required
General
Gas, vent, intake, and condensate piping
09/29/2006 FRI 14:07 FAX 9204854075 SURE-FIRE, INC.
..
141 005/007
.,.
. .'.If
;.i)c."
Temperature controls with low voltage wiring
16 - Ceiling fans with (4) speed controls per (4) fans.
$3200 Allowance for ductwork. spiral pipe, & materials for final connection to paint booth
Air balancing
Local permit and state-approved plans
Start-up and one year warranty
Extended 5-year warranties for compressor and heat exchanger on rooftop unit for office
For the sum of $ 143,800.00
Alternate Bid #1 - In lieu of air turnover heating unit:
1 - Cambridge heating unit with starters and disconnects (see enclosed literature)
Deduct $ 8,100.00
** Note - This will not apply if Alternate Bid #2 is accepted.
Alternate Bid_#2 - Add A/C to plant
Remove air turnover unit and install (3) 25-ton, gas-fired rooftop units with combination supply
and return grilles, curb for standing high heat option, economizers, & gravity relief
Add $ 14,600.00
Alternate Bid #3
Remove the powered air curtains from Base Bid
Deduct $ 6,800.00
We do not include:
Line voltage wiring, starters, or disconnects, unless noted
Gas meter or service charges by local utility
Removal and relocation of equipment unless noted above
Contract amount is subject to revision after 30 days.
Terms - Payment due upon receipt of monthly progress billings. Past due amounts are subject to
a late charge of 1 % per month.
Please contact me if you have any questions or comments.
Sincerely,
Terrance R. Zimmerlee, P.E.
Sure-Fire, Inc.