CONDITIONAL APPROVAL
PLAN APPROVAL EXPIRES: 02/08/2007
SITE:
Orion Flight Services
3418 Park Drive
City of Oshkosh
FOR:
Object Type: HV AC ICC System
12,000 sq ft Area Heated
Transaction ID No. 1230687
Site In No. 705529
'Please refer to both' identificationn1imb~rs,
.above~ iriall <::orresbi1dence with the'a enc .
Regulated Object ID No.: 1058011
The submittal described above has beeQrevie'fed for conformance with applicable Wisconsin Administrative Codes
<indWisconsin Statutes. The, submittalha.s been CONDITIONALLY APPROVED; Th.e,owner, as defined in .
chapter 101,0 i (10), Wisconsin Statutes, is responsible for compliance with all coder~quirements.
The (ollowiIiitcondi1ibns' shairbg%'et'dufirigicdn'sirllciion ot installationancl pi-bite) !8ctupancy()r'u~e:'
. IBC412.2.6 No hazardous operations shall take placein this building.
. IBC 412.2.4 Boiler to be wall mounted a min. 18" above the floor.
Reminders
. This review does not include approval or registration for the installation of Boilers and Pressure Vessels
indicated on this plan. The installation of any Boiler or Pressure Vessel shall be registered with the Department
by the installer before the system is placed in operation as prescribed by COMM 41.41. Registration shall be in
writing on Form SBD-6314. This form, and additional information, may be obtained via telephone at 608-266-
1818 or via the Internet at http://www.commerce.state.wLus/SB/SB-DivForms.html#Boilers
. IMC 10011Comm 64.1001 Provide boilers and pressure vessels that are constructed and installed in
compliance with the standards of the American Society of Mechanical Engineers, as adopted under Comm 41.
. IECC 503.3.3.1, 504.5, 803.2.9, 803.3.7 & 804.5/IECC 804/Comm 63.1029(2) Provide piping carrying fluids
less than 55 deg. F or more than 105 deg. F with insulation to the R-value shown in Comm Table 63.1029,
except where it can be shown that the heat gain to or heat loss from the piping without insulation will not
increase building energy use.
',' " "c." ;'_",,':> I', '''',''',' ,,-,_:--- _-; ,-:; ".' ",' " ',',"" .. '-' ,'" ",", " -' ": " '" ' , - ,', ." ," . '-:
A copy of theapprdved plans, specifications and this letter shall be on-site during construction and open to
iqsp~.ctio.qby authorized rept:es~ntativ~s of the Department, which may in9lude local inspectors. If plan index sheets
were ~ubmitted in. lieu of additional full plansets, a copy of this approval letter and index sheet shall be attached to
plans' that correspond with the copy on file with th.e Department. All permits required by the state or the loc~i
municipality shall be obtained prior to commencement of construction/installation/operation. If this construction
project will disturb one or more acres of land, an Erosion Control Notice of Intent (NO!) shall be filed with the
department 14 days prior to any earth disturbing activities.
..
Page 2
"
PAUL SOBIECK
2/812006
In granting this approval the Division of Safety & Buildings reserves the right to require changes or additions should
conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this review
shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence may be made to me at the telephone number listed below, or at the address
on this letterhead.
Fee Required $
Fee Received $
Balance Due $
SiTfjiP
tilL Dien,ic'f-d
Plan Reviewer, Integrated Services
(920)492-5606, M-TH 6:30 am - 4:00 pm, Fri a.m. Only
ddiedrick@commerce.state.wi.us
cc: Peter R Ochs, State Building Inspector, (920) 948-3500 , Friday, 7:45 A.M. - 4:30 P.M.
Jeff Wanke, Orion Flight Services
Jon P Wolf, Boiler Inspector, (920) 723-0032
440.00
440.00
0.00
Designer CUST ill No. 266062
Responsible Party
PAUL SOBIECK
2442 HUTSON RD
GREEN BAY WI 54303
PAUL SOBIECK
MILWAUKEE STOVE & FURNACE
2442 HUTSON RD
GREEN BAY WI 54303
ADDITIONAL INFORMATION PHONE CALL
SITE:
Orion Flight Services
3418 Park Drive
City of Oshkosh
FOR:
Object Type: HV AC ICC System Regulated Object ill No.: 1058011
12,000 sq ft Area Heated
The submittal described above has been placed on HOLD and the review and approval is pending subject to receipt
of the ADDITIONAL INFORMATION and accompany the resubmittal:
· mc 412.2.4/Comm 62.0412 Heating equipment in an aircraft hangar shall be placed in a room separated by 2-
hour fIre-resistive rated construction, or meet a listed exception. The entrance to this room shall be from the
outside or by means of a vestibule providing a two doorway separation.