October 27, 2005
CUST ID No. 259120
ARTHUR WARREN
CONDON TOTAL COMFORT INC
11 BLACKBURN ST
PO BOX 184
RIPON WI 54971
A TTN: Buildings & Structures Inspector
BUILDING INSPECTION
CITY OF OSHKOSH
POB 1130
OSHKOSH WI 54902
CONDITIONAL APPROVAL
PLAN APPROVAL EXPIRES: 10/27/2006
SITE:
Jay Manufacturing
2045 W 20TH St
City of Oshkosh, 54901
FOR:
Object Type: HV AC ICC System
38,980 sq ft Area Heated
Identification Numbers
Transaction ID No. 1203483
Site ID No. 702703
Please refer to both identification numbers,
above, in all corres ondence with the a enc .
Regulated Object ID No.: 1045372
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes
and Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in
chapter 101.01 (10), Wisconsin Statutes, is responsible for compliance with all code requirements.
The following conditions shall be met during construction or installation and prior to occupancy or use:
Key Item(s)
. IMC 304.4/IFGC 305.3/IBC 1607.7.3 Provide suspended heating appliances for public garages, service
stations, repair garages or other motor vehicle areas at least8 feet above the floor, or a minimum of2 ft higher
above the floor than the height of the tallest vehicle based on door opening height, whichever is greater; or
provide protection from motor vehicle impact. All suspended equipment shall be protected per this code
section.
. IMC 403/Comm 64.0403 Provide minimum mechanical exhaust ventilation in the amount of 75 cfm per fixture
for the public toilet rooms. See Comm Table 64.0403. Toilet room 06, located adjacent to the lobby shall be
provided exhaust. Plans indicate no fan in, this toilet room.
. IMC 306.5/IFGC 306.5 Provide a permanent access for appliances installed on roofs or elevated structures
with equipment located at a height exceeding 16 ft. Access shall not require climbing over obstructions greater
than 30 inches, or walking on roofs having a slope greater than 4/12. Permanent access shall be provided,to
RTU-1 and RTU-2 on the roof of the addition building.
A copy of the approved plans, specifications and this letter shall be on-site during construction and open to
inspection by authorized representatives of the Department, which may include local inspectors. If plan index sheets
were submitted in lieu of additional full plansets, a copy of this approval letter and index sheet shall be attached to
plans that correspond with the copy on file with the Department. All permits required by the state or the local
municipality shall be obtained prior to commencement of construction/installation/operation.
In granting this approval the Division of Safety & Buildings reserves the right to require changes or additions should
conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this review
shall relieve the designer of the responsibility for designing a safe building, structure, or component.