HomeMy WebLinkAbout2006-Electric
e
OSHKOSH
ON THE WATER
Job Address 3110 PROGRESS DR
CITY OF OSHKOSH
No
120636
ELECTRIC PERMIT - APPLICATION AND RECORD
Owner
FOX CITIES CONSTRUCTION CO INC
Create Date 07/20/2006
Contractor
WITZKE ELECTRIC INC
Category 652 - Industrial-New Building Wiring
Plan
Service
o Change 0 Temp
ON/A
Volts
~
480/277
Circuits
Type 0 Overhead
50
40
. Underground
Luminaires
100
100
Amps
1200
Switches
Receptacles
Appliances
otors, AlC, water heater
Use/Nature of INDUSTRIAL / WIRE NEW BUILDING AND TEMP SERVICE* 100A 120/240V
Work
Fees: Valuation
$1?LQ.QO.00
Plan Approval
$0.00
Permit Fee Paid ~~~.OO
Issued By:
Date 07/20/2006
o Permit Voided I
Parcelld #
In the performance of this work I agree to perform all work pursuant to rules goveming the described construction.
While the City of Oshkosh has no authority to enforce easement restrictions of which it is not a party, if you perform the work
described in this permit application within an easement, the City strongly urges the permit applicant to contact the easement
holder(s) and to secure any necessary approvals before starting such activity.
Signature Date
Agent/Owner
Address
PO BOX 102
OSHKOSH
WI 54903 - 102
Telephone Number 920-235-6572
To schedule inspections please call the Inspection Request line at 236-5128 noting the Address, Permit Number, Type of
Inspection (Le. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue if the inspection is not performed within two business days from the time the project is ready.
(04 CITY OF OSHKOSH No 120636
OSHKOSH ELECTRIC PERMIT - APPLICATION AND RECORD . ''
ON THE WATER
Job Address 3111 PROGRESS ST Owner FOX CITIES CONSTRUCTION CO INC Create Date 07/20/2006 `
Contractor WITZKE ELECTRIC INC Category 652 - Industrial -New Building Wiring Plan
Service 0 New 0 Change 0 Temp 0 N/A Type 0 Overhead • Underground
Volts 480/277 Circuits 50 Luminaires 100
Amps 1200 Switches 40 Receptacles 100
Appliances motors, NC, water heater
Use /Nature of INDUSTRIAL / WIRE NEW BUILDING AND TEMP SERVICE* 100A 120/240V
Work
- _ I
Fees: Valuatio $127,000.00 Plan Approval $0.00 Permit Fee Paid $594.00
Issued By: Date 07/20/2006
Permit Voided I Parcel Id #
In the performance of this work I agree to perform all work pursuant to rules goveming the described construction.
While the City of Oshkosh has no authority to enforce easement restrictions of which it is not a party, if you perform the work
described in this permit application within an easement, the City strongly urges the permit applicant to contact the easement
holder(s) and to secure any necessary approvals before starting such activity.
Signature Date
Agent/Owner
Address PO BOX 102 OSHKOSH WI 54903 - 102 Telephone Number 920 - 235 -6572
To schedule inspections please call the Inspection Request line at 236 -5128 noting the Address, Permit Number, Type of
Inspection (i.e. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue if the inspection is not performed within two business days from the time the project is ready.
Electric Permit Work Card
Job Address 3110 PROGRESS DR Permit Number 120636 Create Date 7/20/2006
Owner FOX CITIES CONSTRUCTION CO INC Contractor WITZKE ELECTRIC INC
Category 652 - Industrial -New Building Wiring
Service • New 0 Change() Temp 0 N/A Type 0 Overhead • Underground 0 N/A
Volts 480/277 Circuits 50 Luminaires 100
Amps 1200 Switches 40 Receptacles 100
Fee $594.00 ❑ Value $127,000.00
Appliances motors, A/C, water heater
Use /Nature INDUSTRIAL / WIRE NEW BUILDING AND TEMP SERVICE* 100A 120/240V
of Work
Inspections:
Date 10/25/2006 Type Re Service Inspector Adam Krause approved
Eric Strangeway from WPS stated that the AIC is 35.5KAIC. 10/24/06 8:45AM
Dan Cook from Witzke stated that the GFP test is to be conducted today.
Fax received from Witzke /Square D -GFP test completed & passed. Approval faxed to WPS 12:45 PM
Date/Time requested: 10/24/2006 08:52 AM Notice Type: Phone Number: 379 -4967 Dan
Access:
Ready Date/Time: 10/25/2006 00:00 AM Requested by: WITZKE ELECTRIC INC
0 Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
Date 10/26/2006 Type Rough In Inspector Adam Krause approved
Request line /For office area - Discussed access for VAV in ceiling with Dan
Date/Time requested: 10/25/2006 04:36 PM Notice Type: Phone Number: 920 - 379 -4967
Access:
Ready Date/Time: 10/25/2006 04:36 PM Requested by: WITZKE ELECTRIC INC - Dan
0 Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
Electric Permit Work Card
Job Address 3110 PROGRESS DR Permit Number 120636 Create Date 7/20/2006
Owner FOX CITIES CONSTRUCTION CO INC Contractor WITZKE ELECTRIC INC
Category 652 - Industrial -New Building Wiring
Service • New 0 Change() Temp 0 N/A Type 0 Overhead • Underground 0 N/A
Volts 480/277 Circuits 50 Luminaires 100
Amps 1200 Switches 40 Receptacles 100
Fee $594.00 ❑ Value $127,000.00
Appliances motors, A/C, water heater
Use /Nature INDUSTRIAL / WIRE NEW BUILDING AND TEMP SERVICE* 100A 120/240V
of Work
Inspections:
Date 08/28/2006 Type Underground Inspector Kevin Benner approved w /cond.
Grounding/ Dan stated that the re -bar that he is attached to is tied to the footing re -bar throught the foundation
wall. This will be the supplemental grounding
Date/Time requested: 08/28/2006 07:35 AM Notice Type: Phone Number: 379 -4967
Access:
Meet Dan on site
Ready Date/Time: 08/28/2006 02:30 PM Requested by: WITZKE ELECTRIC INC Dan
0 Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
Date 10/19/2006 Type Service Inspector Kevin Benner not approved
Request Line / Ready for a service inspection/ GFP Test was not conducted & the AIC of the MCB is in
question because the tables & charts provided by WPS in the Service Manual states the AIC is in excess of the
equipment that is installed. Reviewed with Dan Cook on site from the E.C.
Date/Time requested: 10/19/2006 07:23 AM Notice Type: Phone Number: (920) 379 -4967
Access:
Ready Date/Time: 10/19/2006 07:23 AM Requested by: WITZKE ELECTRIC INC - Dan Koch
0 Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
Electric Permit Work Card
Job Address 3111 'PROGRESS ST Permit Number 120636 Create Date 7/20/2006
Owner FOX CITIES CONSTRUCTION CO INC Contractor WITZKE ELECTRIC INC {'
Category 652 - Industrial -New Building Wiring
Service New 0 Change Q Temp 0 N/A Type 0 Overhead • Underground Q N/A
Volts 480/277 Circuits 50 Luminaires 100
Amps 1200 Switches 40 Receptacles 100
Fee $594.00 ❑ Value $127,000.00
Appliances motors, A/C, water heater
Use /Nature INDUSTRIAL / WIRE NEW BUILDING AND TEMP SERVICE" 100A 120/240V
of Work
Inspections:
Date 07/21/2006 Type Temporary Inspector Kevin Benne approved
Request line
TEMPORARY SERVICE ONLY
Faxed to WPS 7/21/6
Datemme requested: 07/20/2006 10:05 AM Notice Type: Phone Number:
Access:
Ready Date/Time: 07/20/2006 10:05 AM Requested by: WITZKE ELECTRIC INC
Q Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
Date 07/21/2006 Type Underground Inspector Kevin Benner
approved w /cond.
Field Request
Ony the trenches were dug, reviewed the remainder of the installation with the field electrician
Date/Time requested: 07/21/2006 10:00 AM Notice Type: Phone Number:
Access:
Ready Date/Time: 07/21/2006 10:00 AM Requested by: WITZKE ELECTRIC INC
0 Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
OCT.25.2006 10 :05AM WITZKE ELECTRIC NO.802 P.1
Witihe eII c/ ic, Inc.
Residential, Industrial and Commercial Installations
155 E. Packer Avenue Poet Office Box 102
Oshkosh, Wisconsin 54903.0102
Phone (920) 235 -6572 FAX (920) 2354582
FAX COVER SHEET
DATE: 10 -25 -06 TIME: 10:05
COMPANY: City of Oshkosh Inspections
PHONE:
ATTENTION: Kevin Benner
FAX:
FROM: John Haaelberg
PHONE (920) 235 -6572
REFERENCE : Shallbetter 3111 Progress
FAX (920) 235 -6582
NUMBER OF PAGES INCLUDING COVER SHEET : 2
•
OCT. 25.2006 10:05AM WITZKE ELECTRIC NO.802 P.2
INALIARE
Srhnoider. Eiectric
APPLETON FACILITY
N1051B Tows View Dr.
Greenville, WI 54942
920 -70-1057
Fax: 920-157 -
October 24, 2006
Witzke Electric
155 E, Packer Avenue
Oshkosh, WI 54901
Dear Sir,
Enclosed is the test reports for the ground fault testing that was performed on the new Square D switchboard
recently installed at the Shallbetter facility located in Oshkosh, WI, The following is a summary of the field
tests perfbrmed and findings.
Low Voltage Circuit Breakers:
Ground Fault System Test: This test is used to verify the proper operation of the ground fault
system. It was performed using the primary current injection test on the low voltage service
disconnect circuit breaker.
All of the equipment tested passed both the visual/mechanical inspections and the electrical tests performed. The
equipment was found to be operational and within applicable standards and manufacturer's tolerances,
Thank you for allowing Square D Services to meet the electrical needs of Witzke Electric and Shallbetter. If you
have any questions or concerns regarding the enclosed test reports or work performed please feel free to contact
me anytime at 920 - 585 -0362.
Regards,
Terry Michels
Square D Senior Field Service Representative
Email: Terry. Michels @US.Schneider- Electric.com