July 24, 2006
Charles King
The office of Charles King AlA
2017 Spring Garden St
Philadelphia, PA 19130
Felice Arredondo
Prime Retail
217 E Redwing, 20th Floor
Baltimore MD 2l202Name
Site: Plan Number: U5-73-0706
Stride Rite
3001 S Washburn S1. Suite AlOO
Oshkosh WI 54904
For:
Description: Tenant space alterations
Object Type: Building only
Class of Construction: lIB - 2523 Sq Ft.; Sprinklered
Occupancy: M: Mercantile I Retail
Maximum No of Occupants: 66
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) I Conditions:
. ANSI 404.2.4 Maneuvering Clearance at Doors. Minimum maneuvering clearance at doors shall
comply with Sections 404.2.4.1 through 404.2.4.7. Table 404.2.4,1 required min 18 inches on latch side
of front approach on pull side of door. Door into existing toilet room does not appear to have the
required clearance. Provide details on how this issue will be resolved.
. IBC 711.3 Any penetrations of fire rated assemblies are required to be protected with a listed firestopping
system that m;ltches the rating of the wall assembly being penetrated. Copies of the firestopping systems
are required to be provided at the time of inspection.
. IBC 901.2 Fire protection systems shall be installed, repaired, operated and maintained in accordance with
this code and the international fire code. Construction of new walls may require the addition and or
relocation of sprinkler heads to maintain required coverage, and not obstruct spray patterns of fire
sprinklers
. IFC 901.4 Fire protection systems shall be maintained in accordance with the original installation
standards for that system. Required fire protection systems shall be extended, altered, or augmented as
necessary to maintain and continue protection whenever the building is altered, remodeled or added to.
Alterations to fire protection systems shall be done in accordance with applicable standards. Submit plans
for fire sprinkler modifications.
\\OSIIKOSIIMISFS\1}SF.RS\br!i.lnn\20(16 (:omrn Plan Review\C5-"! 3-0706 3001 S Washburn St Bldg Only.doG
Page I 00
. IBC 906.1/ IFC 906.3 The maximum travel distance allowed to a fire extinguisher is 75 feet.
. IBC 1003.2.10 Exit signs are required to be installed per this section
. IBC 1003.2.11 Means of egress illumination is required to be installed per this section. All paths of egress
through The Retail Display area are required to have adequate emergency lighting to meet the performance
requirements ofIBC 1003.2.11.3. Provide complete emergency lighting plan showing compliance with
these requirements prior to installation of emergency lighting system.
. IBC 1004.3.2 Corridors - Corridors shall comply with sections 1004.3.2.1 through 1004.3.2.5.
IBC 1004.3.2.1 Construction Corridors (the rear egress path through the "Egress Corridor" is
considered a corridor.) shall be fire-resistance rated in accordance with Table 1004.3.2.1. The corridor
walls required to be fire-resistance-rated shall comply with Section 708 for fire partitions.
Table 1004.3.2.1 Exception c. Buildings equipped throughout with an automatic sprinkler system in
accordance with Section 903.3.1.1 or 903.3.1.2. This will require the monitorinf! and alarms per
Section 903.4 this includes ALL valves controllinf! water supplv.
. NFP A 72 4.5.2 Provide a copy of the fire alarm system record or completion for the required monitoring
and alarms of the automatic fire sprinkler system
. IBC 1101.2/ANSI A117.1-308.2 & 3 - Mechanical system controls shall be located a maximum of 48"
above the finished floor if the floor space allows a forward approach by a wheel chair or if the clear space
allows a parallel approach.
. IBC 1209.1 Provide toilet room floors with smooth, hard, nonabsorbent surface extending minimum 6
inches up onto walls.
. COMM 62.1109 (12) Where counters are provided for sales or distribution of goods or services, at least
one of each type provided shall be accessible. Per ANSI AI17.1-1998 the minimum length of an accessible
service counter is 36 inches, to be maximum 36 inches above the floor.
. IBC 2902..1 / Table 2902 Drinking water is required to be provided, since no drinking fountain is shown
on plans a bottled water cooler is required to be provided.
. Comm 61.30(3) This review does not include lighting. Comm 63.0001 Prior to installation, lighting
plans and calculations shall be prepared in compliance with the code. The plans shall be available upon
request.
. Comm 61.30(3) / IMC 507.2 This plan review does not include heating, ventilation, or air
conditioning. HV AC plans are required to be submitted and approved prior to installation ofHV AC
equipment. Be aware that mc 1004.3.2.4 contains additional restriction for air movement in corridors
. Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Comm 61.31(1).
\\OSHKOSmVnSFSJ}SFRS'J"",,.,,,';'O(;6 Comm Plan Review'.U5-73-0706 3001 S WashburnSt BJdg OnJy.d(l~
Page 2 of3
. Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
. MUN 30 This review does not include review for signage. Applications for and questions regarding
signage permits should be directed to David Buck - Associate Planner (920) 236-5062.
. MUN 30-35 (1)(5) All rooftop and ground level mechanical equipment and utilities shall be fully screened
from view of any street or residential zoning district. Contact David Buck - Associate planner (920) 236-
5062 for additional information on screening requirements. All screening shall be properly anchored in
place to resist wind loads. Additionally IDC 1608.8 Roofprojections - Drift loads due to mechanical
equipment, penthouses, parapets and other projections above the roof shall be determined in accordance
with Section 7.8 of ASCE 7.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
's correspondence may be made to me at the munber listed below or the address on this letterhead.
oe
Building Systems Consultant