Job Address 2307 OREGON ST
CITY OF OSHKOSH
No
120237
HVAC PERMIT -APPLICATION AND RECORD
Owner OSHKOSH TRUCK CORP
Create Date 05/12/2006
Plan T1-39-0506
Contractor GARTMAN MECHANICAL SERVICES
Fuel U_Gas UOil
System o New
U Forced Air U Radiant
o Electric U Hot Water
Chimney Type Q Chimney A () Chimney B
Heat Loss K:) As Approved () Existing
BTU Rate O_~ Per Plan () Variable
Category 510 -Ind. & Comm-Heating & Ventilating
U Solar U Solid
D Other
U AlC U Vent
U Con. Bumer
. Not Applicable
U Electric
D Replace
U Steam
U Suppl.
() Direct Vent
. Not Applicable ~ Value
. Other ---.J Value
Use/Nature Factory/Interior alterations to front office - both floors. Remove and install various partition walls./ DUCTINGNENTILATION CHANGES
of Work pNL Y
Fees: Valuation $35,000.00
Issued By: full0
Plan Approval
$0.00
Permit Fee Paid
$355.00
Date 06/26/2006
D Permit Voided I
Parcelld # 1413800000
In the performance of this work, I agree to perform all work pursuant to rules governing the described construction.
While the City of Oshkosh has no authority to enforce easement restrictions of which it is not a party, if you perform the work
described in this permit application within an easement, the City strongly urges the permit applicant to contact the easement
holder(s) and to secure any necessary approvals before starting such activity.
Signature
Date
Agent/Owner
Address
PO BOX 2264
OSHKOSH
WI 54903 - 2264 Telephone Number (920) 231-5530
To schedule inspections please call the Inspection Request line at 236-5128 noting the Address, Permit Number, Type of
Inspection (i.e. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue if the inspection is not performed within two business days from the time the project is ready.
"-'" ..t
~
OJHKQfH
City of Oshkosh
Division of Inspection Services
215 Church Avenue
POBox 1130
Oshkosh WI 54903-1130
www.ci.oshkosh.wi.us
ON THE WATER
June 12, 2006
Larry Grosser
CMG & Associates
266 Corporate Dr
Madison, WI 53714
Oshkosh Truck Corp
2307 Oregon St
Oshkosh, WI 54902
Site: Plan Number: Tl-39-0506-H
Oshkosh Truck Corp North Plant
2307 Oregon St
Oshkosh WI 54902
For:
Description: Tenant space alterations
Object Type: HV AC only
Class of Construction: lIB - 8440 Sq Ft.; sprinklered
Occupancy: B: Business I Office
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defmed in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) I Conditions:
· IMC 403.3.3 Variable air volume air distribution systems, other than those designed to supply only 100%
outdoor air shall he provided with controls to regulate the flow of outdoor air. Such controls shall be
designed to maintain the flow of outdoor air at a rate not less than required by Section 403 over the entire
range of supply air operating rates.
· IBC 1l01.2/ANSI A117.1-308.2 & 3 - Mechanical system controls shall be located a maximum of 48"
above the finished floor if the floor space allows a forward approach by a wheel chair or if the clear space
allows a parallel approach.
· IECC 803.3.3.3 Off-hour controls. Each zone shall be provided with thermostatic setback controls that
are controlled by either an automatic time clock or programmable control system.
· IMC 606.2~1 Smoke detectors shall be installed in return air systems with a design capacity greater than
2000 c:fin.. . Verify that smoke detection is installed in systems exceeding the 2000 cfm. Plans do not
show a smoke detector to exist in Air Handler # 5.
· IMC 606.4.1 The duct smoke detectors shall be connected to a fire alarm system. The actuation of a
smoke detector shall activate a visible and audible supervisory signal at a constantly attended location.
.H:\briann\2006 Comm Plan Review'TI-39-0506-H 2307 Oregon Si, HVAC' Only.dol:
Page lof2
t.,.'ib
. Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Corom 61.31(1).
SUBMIT:
. IECC 503.3.3.7 [Comm 63.0503(2)(f)] Balancing and documentation of the HV AC system shall conform
to the !MC. Balancing report required to be submitted prior to fmal occupancy being allowed.
. Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
. s correspondence may be made to me at the number listed below or the address on this letterhead.
oe
Building Systems Consultant
(920) 236-5051 Monday- Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.
bnoe@cLoshkosh.wi.us. .
cc: Property file
Fee Required $
Fee Received $
Balance Due $
320.00
320.00
0.00
II:\briann"2006 Comm Plan Revje\V\Tl.~9.05()6.H 2307 Oregon St, HVAC Only. doc