HomeMy WebLinkAbout2006-Letter Building & HVAC Plans
~
OJHKQ/H
City of Oshkosh
Division of Inspection Services
215 Church Avenue
PO Box 1130
Oshkosh WI 54903-1130
www.cLoshkosh.wi.us
ON THE WATER
June 20, 2006
Timothy G Pleger
AAD:fitch
15425 N Greenway-Hayden Loop Suite 100
Scottsdale AZ 85260
Prime Retail
217 Redwood S1. 20th Floor
Baltimore, MD 21202
Louie C Panopio
NP Mechanical Inc
1717 W NorthemAve. Suite 116
Phonix, AZ 85021
Matt Hardesty
500 E Balboa Blvd.
Newport Beach, CA 92661
Site:
Pac Sun
3001 S Washburn St - Space C20
Oshkosh WI 54904
For:
Description: Tenant space alterations
Object Type: Building and HV AC
Class of Construction: lIB - 3460 sq ft.;
Occupancy: M: Mercantile / Retail
Maximum No of Occupants: 91
Plan Number: T7-56-0606
sprinklered
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defmed in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) / Conditions:
· IBC 901.2 Fire protection systems shall be installed, repaired, operated and maintained in accordance with
this code and the international fire code. {Construction of new walls may require the addition and or
relocation of sprinkler heads to maintain required coverage, and not obstruct spray patterns offire
sprinklers}
· IFC 901.4 Fire protection systems shall be maintained in accordance with the original installation
standards for that system. Required fire protection systems shall be extended, altered, or augmented as
necessary to maintain and continue protection whenever the building is altered, remodeled or added to.
Alterations to fire protection systems shall be done in accordance with applicable standards. Submit plans
for fire sprinkler modifications.
· IBC 906.1 /IFC 906.3 The maximum travel distance allowed to a fire extinguisher is 75 feet.
· IBC 1003.2.10 Exit signs are required to be installed per this section
\\OSHKOSHMISFS\USERS\briann\200(i ComITl Plan Revicw\T7-56-0606 3001 S Washbum Space 20 Bldg and HVAC.doc
Page I of3
-1....-.-... .-.---1-.-..
. IBC 1003.2.11 Means of egress illumination is required to be installed per this section. All paths of egress
through The Retail Display area are required to have adequate emergency lighting to meet the performance
requirements ofIRC 1003.2.11.3. It does not appear that unit equipment shown on sheetA3 will provide
the required levels of emergency illumination. Provide manufactures cut sheetfor emergency light
fixtures being installed.
. 1004.2.3 Egress through intervening spaces. Egress from a room or space shall not pass through
adjoining or intervening rooms or areas, except where such adjoining rooms or areas are accessory to the
area served; are not a high-hazard occupancy: andorovide a discernible oath of e1!ress travel to an exit.
Egress shall not pass through kitchens, store rooms, closets or spaces used for similar purposes. An exit
access shall not pass though a room that can be locked to prevent egress. Means of egress from dwelling
units or sleeping areas shall not lead through other sleeping areas, toilet rooms or bathrooms. The path of
egress through the rear exit shall he kept clear.
· IRC 1209.1 Provide toilet room floors with smooth, hard, nonabsorbent surface extending minimum 6
inches up onto walls.
. COMM 62.1109 (12) Where counters are provided for sales or distribution of goods or services, at least
one of each type provided shall be accessible.
· IMC 302.1 The building or structure shall not be weakened by the installation of mechanical systems.
Verify that existing structure is capahle of supporting the additional weight of the proposed rooftop
equipment.
· IMC 304.9 Guards. Guards shall be provided where appliances, equipment, fans or other components that
require service are located within 10 feet (3048 mm) of a roof edge or open side of a walking surface and
such edge or open side is located more than 30 inches (762 mm) above the floor, roof or grade below. The
guard shall extend not less than 30 inches (762 mm) beyond each end of such appliance, equipment, fan or
component and the top of the guard shall be located not kss than 42 inches (1067 mm) above the elevated
surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21-inch-
diameter (533 mm) sphere and shall comply with the loading requirements for guards specified in the
mtemational Building Code. .
· IMC 405.1 Mechanical ventilation systems shall be provided with manual or automatic controls that will
operate such systems whenever the spaces are occupied. Air conditioning systems that supply required
ventilation air shall be provided with controls designed to automatically maintain the required outdoor air
supply rate during occupancy.
· IECC 503.3.3.7 [Comm 63.0503(2)(f)] Balancing and documentation of the HV AC system shall conform
to the IMC. Balancing report required to be submitted prior to final occupancy being allowed.
· IMC 606.4.1 The duct smoke detectors shall be connected to a fire alarm system. The actuation of a
smoke detector shall activate a visible and audible supervisory signal at a constantly attended location.
· IMC 606.4.1 Exception 2. m occupancies not required to be equipped with a fire alarm system, actuation
of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector
trouble conditions shall activate a visible or audible signal in an approved location and shall be identifies
as air duct detector trouble.
\\OSHKOSHMISFS\USERS\briann\1006 Comm Plan Redew\T7-56-0606 :JOO] S Washhurn Spaee 10 BJdg and HVJ\Cdoc
Page 2 of3
_ I________....J.--_,~__-~"--'~~"_--~__------~-'-' --"-'----"-- ,---,
. Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Corom 61.31(1).
SUBMIT:
. IECC 503.3.3.7 [Comm 63.0503(2)(1)] Balancing and documentation of the HV AC system shall conform
to the IMC. Balancing report required to be submitted prior to final occupancy being allowed.
. IBC 1003.2.11 Means of egress illumination is required to be installed per this section. All paths of egress
through The Retail Display area are required to have adequate emergency lighting to meet the performance
requirements ofIBC 1003.2.11.3. Provide complete emergency lighting plan showing compliance with
these requirements prior to installation of emergency lighting system.
. IBC 2902 Table 2902.1 Minimum Number of Plumbing Facilities. A minimum of one service sink is
required to be provided. IMC 403.3 [Comm 64.0403 (6)] Ventilation rate. Janitor closets. A janitor
closet that has only one service sink may be provided with either natural ventilation via a window or
louvered opening with at least 2 square feet (0.2 m2) of area openable directly to the outside or mechanical
exhaust ventilation as specified in Table 64.0403. Plans submitted do not show the required service sink
included in building plans. Comm 62.2900 (2) requires a service sink to be located in a janitors closet,
and the IMC requires ventilation of that space. Provide additional details / floor plan showing where
the required service sink will be located and how required ventilation will be provided.
. Comm 61.30(3) This review does not include lighting. Corom 63.0001 Prior to installation, lighting
plans and calculations shall be prepared in compliance with the code. Please submit lighting work sheets.
. Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to connnencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning th. s correspondence may be made to me at the number listed below or the address on this letterhead.
~,~etfull
~, e
Building Systems Consultant
(920) 236-5051 Monday-Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.
bnoe@cLoshkosh.wi.us
cc: Property file
Fee Required $
Fee Received $
Balance Due $
590.00
590.00
0.00
\\OSHKOSHMISFS\USERS\briann\2006 ComTll Plan Review\T7-56-0606 3001 S \Vashburn Space 20 Bldg and HVACdoc
Page 3 on