HomeMy WebLinkAbout06/2/06-Fire Code Violation Fire Rated Furnace / Mechanical Room Date: June 2, 2006 Address: 300 Division St Issue: Current condition is there is an 11' x 16' ftre rated furnace, mechanical room, in which a great deal of combustible material (paper fIles) are being stored. This has placed the property in violation of fITe code. Building info: Year Built: 1969 No of stories: 1 wi basement Total Area: 1204 - Use Group: B - Office Equipment in furnace room: 120,000 Btu natural gas open combustion furnace 40,000 Btu natural gas water heater 18" x 9" combustion air intake from the exterior Applicable codes: Old Code - in effect at time of construction IND 54.13 Isolation of Hazards: (1) All heating boilers and furnaces, power boilers, fuel rooms, storage vaults for paints, oils and similar combustibles and other similar hazards in a building shall be isolated from the rest of the building by at least a 2-hour fITe-resistive enclosure as specifted in Ind. 5 1.05 and Ind. 51.06; except that in buildings not more than 2 stories in height and having a floor area of not more than 3000 sq. feet per floor, a one-hour ftre-resistive enclosure as specifted in Ind. 51.05 and Ind.51.06, or better shall be provided Current Code - in effect if the building were built today IBC Table 302.1.1 Incidental areas: Furnace room where largest piece of equipment is over 400,000 Btu per hour input requires a one-hour separation, or automatic fITe-extinguishing system. IFC 315.2.3 Equipment Rooms: Combustible material shall not be stored in boiler rooms, mechanical rooms, or electrical equipment rooms. Conclusion: We do not typically apply the provisions of the new code to an existing building without evaluating the entire structure to review for compliance with all of the new code requirements. However, in this speciftc case the limited size of the building, and the fact that is stands on its own (not attached to any other building) would allow for us to apply the new code provisions without requiring a full code review of the building. In this case it will result in a no rating being required for the furnace I mechanical room. This will allow for tlte construction of a smaller uon-mted furnace room to separate tlte equipment from the area being used for storage. All required clearance, aud combustion air requirements are required to be maintained. Cc: Property File Inspections Fire Department File