HomeMy WebLinkAboutStairway Addition & Wrestling Room #S4-38-0406 (05/01/2006)
(t)
OfHKOfH
City of Oshkosh
Division of Inspection Services
215 Church Avenue
PO Box 1130
Oshkosh WI 54903-1130
www.cLoshkosh.wLus
ON THE WATER
May I, 2006
Thomas Karre!s
Thomas R. Karre!s P.E.S.c.
1984 A!goma Blvd
Oshkosh, WI 54901
JobnHirte
Unified Catholic Schools - Lourdes I Neuman
lION Sawyer St
Oshkosh, WI 5492
Site:
Unified Catholic Schools Lourdes I Neumau
110 N Sawyer St
Oshkosh WI 54902
For:
Description: Stairway Addition - Wrestling room
Object Type: Bnilding only
Class of Construction: IIIB - ISO Sq Ft.; Unsprinkiered
Occupancy: E: Educational, A3 Assembly, B Business I Office
Maximum No of Occupants: 24
Plan Number: S4-38-0406
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statates. The submittal has been CONDITIONALLY APPROVED. The owner, as deemed in Chapter
101.01(10), Wisconsin Statotes, is responsible for compliance with all code requirements
Key Item(s) / Conditions:
IBC 803 Interior finish based on group. Interior wall and ceiling finish shall have a flame spread index
not greater than that specified in table 803.4 for the group and location designated. Caution on plywood
covered walls in Wrestling room -not aU plywood meets the class C flame spread limitation of200.
IFC 901.4 Fire protection systems shall be maintained in accordance with the original installation
standards for that system. Required fire protection systems shall be extended, altered, or augmented as
necessary to maintain and continue protection whenever the building is altered, remodeled or added to.
Alterations to fire protection systems shall be done in accordance with applicable standards. Comm 61.30
(3) requires plans to be submitted for fire protection systems in education Group E Occupancy.
- Submit plansfor fire sprinkler modifications.
IBC 906.1 / IFC 906.3 The maximum travel distance allowed to a fire extinguisher is 75 feet.
IBC 1003.2.11 Means of egress illumination is required to be installed per this section
IBC 1003.2.11.2 Means of egress illumination is required to be installed per this section. All paths of
egress are required to have adequate emergency lighting to meet the performance requirements ofIBC
1003.2.11.3. Provide complete emergency lighting plan showing compliance with these requirements
prior to instaUation of emergency lighting system.
W.l>ri:um'2006 Comm Phm R.vi.w\S4-38-0406 ¡ION Scowyer Bldg Only.doc
Page 1 of2
Comm 5.34 No person may perform structoral welding unless the person holds a registration issued by
Department of Commerce. Provide welders registration numbers for all people doing welding on this
project.
Comm 61.30(3) / IMC 507.2 This plan review does not include heating, ventilation, or air
conditioning. HV AC plans are required to be submitted and approved prior to installation ofHV AC
equipment. Be aware that mc 1004.3.2.4 contains additional restriction for air movement in corridors
Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Comm61.3I(l).
Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. AIl pennits are required to
be obtained prior to conunencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structote, or component.
Inquiries concerning this correspòndence may be made to me at the number listed below or the address on this letterhead.
~Y
~
Building Systems Consultant
(920) 236-5051 Monday- Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.
bnoe@ci.oshkosh.wi.us
ce: Property file
Fee Required $
Fee Received $
Balance Due $
320.00
0.00
320.00
Ihbrillim\2006 Comm Plan R.,i.w\S4-38-04Q6 1 ION Sawy" Bldg Only.doc
Page2of2