HomeMy WebLinkAbout0000000 B
',.
~
OJHKOJH
City of Oshkosh
Division of Inspection Services
215 Church Avenue
POBox 1130
Oshkosh WI54903-1130
www.cioshkosh.wius
0"'"' WATER
February 27,2006
Thomas R Karrels
Thomas R Karrels P .E.S.C
1934 Algoma Blvd
Oshkosh, WI 54901
Pete Zwirchitz
Oshkosh Truck Corporation
2307 Oregon St
Oshkosh WI 54901
Joel Clary
Snmmit Design LLC
W6744 Rogersville Road
Fond dn Lac WI 54937
Site:
Oshkosh Trnck Print Center
2225 Minnesota St
Oshkosh WI 54901
For:
Description: Tenant space alterations
Object Type: Bnilding and HV AC
Class of Construction: lIB - 8257.5 Sq Ft.; 1 Story Unsprinklered
Occupancy: B: Business / Office S: Storage
MaximumNo of Occupants: 55
Plan Number: R5-13-0206
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as derIDed in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key ltem(s) / Conditions:
IBC 711.3 Any penetrations of fire rated assemblies are required to be protected with a listed firestopping
system that matches the rating of the wall assembly being penetrated. Copies of the firestopping systems
are required to be provided at the time of inspection.
IBC 1003.2.10 Exit signs are required to be installed per this section
IBC 2902..1/ Table 2902 Drinking water is required to be provided, since no drinking fountain is shown
on plans a bottled water cooler is required to be provided.
IFC 304.3 Containers. Combustible rubbish and waste material kept within a structure shall be stored in
accordance with Sections 304.3.1 through 304.3.3.
IFC 304.3.3 Capacity exceeding 1.5 cubic yards. Dumpsters and containers with an individual capacity
of 1.5 cubic yards or more shall not be stored in buildings or placed within 5 feet of combustible walls,
openings, or combustible roof eve lines.
IMC 304.1 Equipment and appliances shall be installed as required by the terms of their approval, in
accordance with the conditions of the listing, the manufactures instructions and this code.
Rcvkw\I<5-13-<i2116 2225 Mincsot; St Bidg and
Page lof3
304.8 Clearances from grade. Equipment and appliances installed at grade level shall be supported on a
level concrete slab or other approved material extending above adjoining grade or shall be suspended a
minimum of 6 inches (152 mm) above adjoining grade.
.
IMC 307.1 Liquid combustion by-products of condensing appliances shall be collected and discharged to
an approved plumbing fIXture or disposal area. Plans indicate" Drain to Outside" this is not permitted.
IFGC 307.2.1/ IMC 307.2.1 Provide a means to convey condensate from cooling coils and evaporators
from a drain pan outlet to an approved place of disposal. Discharge into a street, alley or other areas of
nuisance are not allowed. Plans indicate" Drain to Outside" this is not permitted.
IMC 401.5 Opening Location Outside air exhaust and intake openings shall be located a minimum of 10
feet (3048 rom) from lot lines or buildings on the same lot. Where openings front on a street or public way,
the distance shall be measured to the centerline of the street or public way.
IMC 401.5.1 Mechanical and gravity outside air intake openings shall be located a minimum of 10 feet
from any hazardous or noxious contaminant such as vents, chinmeys, plumbing vents, streets, alleys,
parking lots and loading docks.
401.5.2 Exhaust openings. Outside exhaust openings shall be located so as not to create a nuisance.
Exhaust air shall not be directed onto walkways.
403.2 Outdoor air required. The minimum ventilation rate of required outdoor air shall be determined in
accordance with Section 403.3.
IMC 405.1 Mechanical ventilation systems shall be provided with manual or automatic controls that will
operate such systems whenever the spaces are occupied. Air conditioning systems that supply required
ventilation air shall be provided with controls designed to automatically maintain the required outdoor air
supply rate during occupancy.
IECC 803.3.3.3 Off-hour controls. Each zone shall be provided with thermostatic setback conttols that
are controlled by either an automatic time clock or programmable control system.
IFGC 619.2 Support. Suspended-type unit heaters shall be supported by elements that are designed and
constructed to accommodate the weight and dynamic loads. Hangers and brackets shall be of
noncombustible material.
Comm 61.30(3) This review does not include lighting. Comm 63.0001 Prior to installation, lighting
plans and calculations shall be prepared in compliance with the code. The plans shall be available upon
request.
Comm 80 This plan review does not include plumbing. Prior to installation of plumbing, plans and
calculations are required to be submitted and approved if required by plumbing code. While no formal
plumbing plan review has been conducted, be aware that the quantity of clearwater discharge appears
to exceed the 50 gallons per day allowed per Table 82.38-1, due to the volume of water being
discharged from the humidification equipment being installed. A storm water drain appears to be
needed to serve as a point of discharge for clear water waste from this site.
Rcvkw\R5-13-112iJ(' 2225 Mincsota St Bídg.nd HVAc.do,
Page2of3
Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Comm 61.31(1).
MUN 30-35 (1)(5) All rooftop and ground level mechanical equipment and utilities shall be fully screened
from view of any street or residential zoning district. Contact David Buck - Associate planner (920) 236-
5062 for additional information on screening requirements. All screening shall be properly anchored in
place to resist wind loads. Additionally mc 1608.8 Roofprojections - Drift loads due to mechanical
equipment, penthouses, parapets and other projections above the roof shall be determined in accordance
with Section 7.8 of ASCE 7. No HVAC permit can be issued until an approved screening plan has been
submitted
SUBMIT:
IECC 503.3.3.7 [Comm 63.0503(2)(f)] Balancing and documentation of the HV AC system shall conform
to the !MC. Balancing report required to be submitted prior to final occupancy being allowed.
IBC 1003.2.11 Means of egress illumination is required to be installed per this section. All paths of egress
are required to have adequate emergency lighting to meet the performance requirements of IBC
1003.2.11.3. Existing means of egress emergency lighting is permitted to be maintained in compliance
with the code in effect at the time of construction. Any altered path of egress, or new path of egress,
and any new emergency lighting being installed is required to comply with current code requirements.
Provide complete emergency lighting plan-showing compliance with these requirements prior to
installation of emergency lighting system.
. Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structute, or component.
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
~
~
Building Systems Consultant
(920) 236-5051 Monday - Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.
bnoe@ci.oshkosh.wi.us
cc: Property file
Fee Required $
Fee Received $
Balance Due $
800.00
800.00
0.00
';'OSHKOSHMJSFS\LSERS\hriann\10<J6 Comm Plan Rcvkw\R5-130)2116 2225 Minesota sr rHdg and HVACdoc
Page 3 00
~.