HomeMy WebLinkAbout2006-Electric
~
OSHKOSH
ON THE WATER
Job Address 3001 S WASHBURN ST
CITY OF OSHKOSH
No
118286
ELECTRIC PERMIT - APPLICATION AND RECORD
Owner
FIRST HORIZON GROUP LIMITED PTNSHI Create Date 02/20/2006
Contractor
ROYAL ELECTRIC INC
0 Change
Category 643 - Commercial-Addition/Remodels
Plan
Service . New
Volts 120/208
Amps ~
Circuits
Type
52
0 Overhead
. Underground
0 Temp
0 NIA
Fixtures
~
Switches 20
Receptacles --~
Appliances
l
UselNature of Suite A60 Oshkosh B Gosh I Interior alterations per plans
Work
Fees: Valuation
$31,390.00
Plan Approval
$0.00
Penmit Fee Paid
$280.00
Issued By:
Date 02/23/2006
D Permit Voided I
Parcelld # 1329420000
In the performance of this work i agree to perform all work pursuant to rules govemlng the described construction.
While the City of Oshkosh has no authority to enforce easement restrictions of which It is not a party, if you perform the work
described in this permit application within an easement, the City strongly urges the penmit applicant to contact the easement
holder(s) and to secure any necessary approvals before starting such activity.
Signature
Date
Address
640 MOASIS DR
AgenUOwner
LITTLE CHUTE WI 64140 -0
Telephone Number 920-788-8800
To schedule inspections please call the Inspection Request line at 236-5128 noting the Address, Permit Number, Type of
Inspection (i.e. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue ifthe inspection is not performed within two business days from the time the project is ready.
Electric Permit Work Card
Job Address 3001 S WASHBURN ST Permit Number 118286
Create Date 02/20/2006
Owner FIRST HORIZON GROUP LIMITED PTNSHP
Contractor ROYAL ELECTRIC INC
Category 643 - Commercial-Addition/Remodeis
Service b New
Volts 120/208
Amps 300
0 ChangeO Temp ON/A I Type 0 Overhead
Circuits 52
Switches 20
. Underground 0 NIA
Fixtures
0
Receptacles 25
$31,390.00
Fee
$280.00 D
Value
~~m.. ....
Appliances
UselNature
of Work
Suite A60 Oshkosh B Gosh I Interior alterations per plans
Inspections:
Type Service
Inspector Kevin Benner
---- not approved
Date 03/29/2006
Not Ready: The new conductors need to be installed and the temporary wiring shall be removed from the
raceway which the new conductors are to be installed.
DatelTime requested: 03/28/2006 ~OO PM -- Notice Type:
Access:
Phone Number:
Ready DatelTime: 03/28/2006 03:00 PM Requested by:
--
0 Reinspect Fee 0 Fee Wavied D Reinspect Fee Paid
ROYAL ELECTRIC INC Howard
approved w/cond. i
I
The circuit breaker that is installed is a 400A current adjustable Sq.D "STR" model unit. This C.B. settings are!
as follows: #1 .9, #2 .85 whick equals a 306 Amp setting. These settings were noted on the. WPS workcard
which I noted, signed and ieft with Howard & Roger the electricians on site.
Type Service
Inspector Kevin Benner
Date 03/30/2006
DatelTime requested: 03/29/2006 12:51 PM -- Notice Type:
Access:
Meet Howard on site
Phone Number:
Ready DatelTime: 03/30/2006 09:45 AM Requested by:
--
0 Reinspect Fee 0 Fee Wavied D Reinspect Fee Paid
ROYAL ELECTRIC INC